GENETICS PHARMA

DEHUMIDIFYING LOAD INPUT SHEET

Section
No.

Temp.
(Deg F)

RH%

Min.
Air Ch./Hr
(ACH)

2x24.5 Sft/2
24.5+4 Sft/2
24.5+4 Sft/3
24.5+4 Sft/4

20
20
20
20

45
45
45
45

20
20
20
20

930
380
1920
1740

2
2
2
2

24.5 Sft/2
24.5 Sft/2

20
20

40
40

30
30

560
600

2
2

Film Coating
Comp-1
Comp-2
Comp-3
Corr
Ent
M/t Transfer

24.5 Sft/2
24.5 Sft/2
24.5 Sft/2
24.5 Sft/2
24.5 Sft/4
24.5 Sft/4
24.5 + 4 Sft/2

20
20
20
20
20
20
20

45
45
45
45
45
45
45

30
30
30
30
20
20
20

730
510
870
930
520
130
200

1
2
2
2
0
0
1

GRANULATION
Dry Mixing
Drying
Wet Granulation

24.5 Sft/2
24.5 Sft/2
24.5 +4 Sft/2

20
20
20

45
45
45

25
25
25

850
950
3850

2
2
3

Room Description

No. of
Persons

CAPSULE
Capsule filling
Powder Mixing

Supply Air
(CFM)

BLISTERING
Blistering
Buffer
Blistering Area-1
Blistering Area-2

Required Room Conditions

Door OR Pass
Box Size/No of
Openings/hr
(Sq ft/ Nos.)

TABLETS

ROOM CONSTRUCTION: MASONARY WALLS, RCC ROOF, PCC FLOOR


WEIGHT OF PRODUCT EACH SECTION BEFORE DRYING =100 KG, AFTER DRYING=90 KG
NO WATER BODY PRESENT INSIDE THE ROOMS
AMBIENT CONDITIONS:
a
SUMMER: 118 Deg F DB/ 74.6 Deg WB
b
WINTER: 34 Deg F DB/ 25% RH
c
MONSOON: 109 Deg F DB/ 70% RH
8
OUTSIDE AIR RATE: 10 % OF SUPPLY AIR AT AHU INLET
9