Sie sind auf Seite 1von 1

FB 2201 - 2213

Digital Output
with Position Feed Back

Product features
• Zone 1 or Zone 2 mounted • Line monitor (LFD)
• Output for intrinsic safety solenoid valves depends on version
• Output for sounders and LED • Permanently self-monitoring
(only without LFD) • Output with watch dog circuit for fatal errors
• Positive- or negative logic selectable • EMC to EN 61326 or NE21
depending on version

Input:
Volt-free mech. contacts or 2-wire proximity
2
Signal type
2-wire-initiators EN/IEC 60947-5-6 / NAMUR
on > 2.1 mA
Switching points
off < 1.2 mA
Hysteresis 0.2 mA
Line fault (LFD) < 1 mA
short > 6 mA

Output:
with line monitor (LFD) short circuit protected (see below)
Watch dog Output OFF 0.5 s after serious fault
Power consumption 0.52 W - 1.8 W depending on version

Explosion protection:
Category II 2 (1/2) GD EEx d [ia] IIC
Approval PTB 97 ATEX 1047 U
sensor circuit Uo ) 14 V, ISC ) 16 mA, Po ) 55 mW
IIC Safety values (linear) Co ) 418 nF, Lo ) 5 mH
output circuit see table

Ordering details
Uout/V Ra/1 Limit/mA LFD/1 Uo/V IO/mA PO/mW CO/nF LO/mH Type Order No.
22.0 315 50 20...2000 24.9 91 558 79 1 FB 2201 B GHG 127 0000 B2201
24.0 210 75 1) 110...1200 27.8 183 1270 227 1) 1.9 1) FB 2202 B GHG 127 0000 B2202
24.0 360 50 70...2000 27.8 91.5 636 69 0.4 FB 2203 B GHG 127 0000 B2203
22.0 220 50 220...1300 24.2 145 872 92 0.27 FB 2204 B GHG 127 0000 B2204
22.0 220 50 2) 220...1300 24.2 145 872 92 0.27 FB 2204 D GHG 127 0000 D2204
22.8 290 50 150...2000 25.2 108 681 74 0.5 FB 2205 B GHG 127 0000 B2205
25.3 329 – 25...3500 27.8 108 751 81 0.19 FB 2212 B GHG 127 0000 B2212
25.3 329 – 2) 25...3500 27.8 108 751 81 0.19 FB 2212 D GHG 127 0000 D2212
26.7 509 – 40...7000 28.7 68 485 69 0.4 FB 2213 B GHG 127 0000 B2213
OUT
26.7 509 – 2) 40...7000 28.7 68 485 69 0.4 FB 2213 D GHG 127 0000 D2213
1)
only group II B
2)
output without LFD no longer required since the test pulse can be deactivated via software
+1 –4 1 4 for modules delivered after March 07.
CH1 CH2

10k
2,2k

+ + + - - -
1 2 3 4 5 6

Ra
UOUT

FB
LBRemote I/O
Remote I/O

2/19

Das könnte Ihnen auch gefallen