Spinal Cord Injury Center Design Guide

July 1990 (Rev. Jan. 2004)

Lithotripsy Scrub 28-B


Function:
This space is intended to support the Lithotripsy Room described on the previous sheet. Staff will scrub
here prior to entering the Lithotripsy Room. Visual and voice communication should exist between the
two rooms.

Space Requirement:
30 NSF

Architectural:
Finish Code:
9-A
Floor Finish:
Resilient Sheet*
Base:
Resilient Sheet*
Wall Finish:
Plaster/Special Coating**
Ceiling:
Plaster/Paint
Ceiling Height:
9'-0"
Noise (STC Rating):
N/A
Slab Depression:
None
Special Construction: Hardware:
Doors:
None
Windows:
Observation Window, see SD 08110-4.DWG
*Heat-Welded Seams, see Mspec #09666
**See Mspec #09815

HVAC:
Temperature:
Summer: 72@50%RH
Winter:
82@30%RH
Min. Air Changes/Hour: 6
Min. % Outside Air:
15%
Pressure:
Negative
% Filtration:
30%(PF)/85%(AF)
Noise Criteria:
A/C Loads:
Lights:
75w
Equipment: People:
100w, sensible
130w, latent

Electrical:
Lighting Levels:
Gen. Illum: 50fc
Emergency Power: -

Office of Facilities Management

165

Recovery Room 29
Function:
This space is intended to accommodate patients after Lithotripsy procedures. Here they will be monitored
until the effects of general anesthesia have worn off. This space is provided only when Lithotripsy is
approved and located in the SCI GU Clinic.

Space Requirement:
300 NSF

Architectural:
Finish Code:
1-U
Floor Finish:
Vinyl Composition Tile
Base:
Vinyl
Wall Finish:
Veneer Plaster/Paint
Ceiling:
Acoustical Tile
Ceiling Height:
9'-0"
Noise (STC Rating):
35
Slab Depression:
None
Special Construction:
Hardware:
69
Doors:
4'-0" x 7'-0" wood or metal, optional glass view panel.
Windows:
None Required

HVAC:
Temperature:
Summer: 72@50%RH
Winter:
82@30%RH
Min. Air Changes/Hour: 8
Min. % Outside Air:
15%
Pressure:
Positive
% Filtration:
30%(PF)/85%(AF)
Noise Criteria:
35
A/C Loads:
Lights:
800w
Equipment: 1000w
People:
390w, sensible
330w, latent

Electrical:
Lighting Levels:
Gen. Illum: 30fc
Over Bed: 100fc
Emergency Power:
Overbed Lights
One Receptacle per PBPU
Nurse Call
Medical Gases

Office of Facilities Management