Type :- MIF-II
Make:- G.E
Testing Set:- MPRT8430 (Megger)
Settings Of Relay
Settings
Value
Description
Name of Feeder
Ip
200
Primary Current
In
Frequency
50 Hz
Rated Frequency
Curve
Very Inverse
Curve Used
Yes/ No
Yes
Pick Up
3.5 A
Yes/ No
Yes
Tap
1.0A
3.5A
Td
0.4
Tap Multiple
Tap Multiple
Tap Multiple
1A
Tp
0.1
Tap Multiple
Tap Multiple
Tap Multiple
Yes/ No
Yes
I>>
7.5A
Instantaneous Setting
Yes/ No
Yes
I>>
2.0 A
Instantaneous Setting
Pick Up Test
Phase
Tap Setting
Pick Up
Red Phase
3.5A
3.5A
Yellow Phase
3.5A
3.51A
Blue Phase
3.5A
3.5A
Earth Fault
1A
1.0A
Test Current
Status
7.00
5.153
Trip
14.00
1.763
Trip
21.00
1.070
Trip
Test Current
Test Time
Status
5.155
Trip
14
1.763
Trip
21
1.071
Trip
Test Current
Test Time
Status
5.154
Trip
14
1.760
Trip
21
1.068
Trip
Test Current
Test Time
Status
Trip
Trip
Trip
Setting
Test Current
Status
7.50
7.51
Trip
Setting
Test Current
Status
7.5
7.51
Trip
Setting
Test Current
Status
7.5
7.51
Trip
Setting
Test Current
Status
2.01
Trip