116 Section Eleven
Range B is provided to allow limited excursions of voltage outside the range A limits
that necessarily result from practical design and operating conditions. The supplying
utility is expected to take action within a reasonable time to restore service voltages
to range A limits. The user is expected to take action within a reasonable time to
restore utilization voltages to range A limits. Insofar as practical, utilization
equipment may be expected to give acceptable performance outside range A but
within range B. When voltages occur outside the limits of range B, prompt corrective
action should be taken.
‘The voltage tolerance limits in ANSI C84.1-1989 are based on ANSI/NEMA
‘MG1-1978, “Motors and Generators,” which establishes the voltage tolerance limits
of the standard low-voltage induction motor at #10 percent of nameplate voltage
ratings of 230 and 460 V. Since motors represent the major component of utilization
equipment, they were given primary consideration in the establishment of this
voltage standard,
‘The best way to show the voltages in a distribution system is by using a 120-V base,
‘This cancels the transformation ratios between systems so that the actual voltages
vary solely on the basis of voltage drops in the system. Any voltage may be converted
to a 120-V base by dividing the actual voltage by the ratio of transformation to the
120-V base. For example, the ratio of transformation for a 480-V system is 480/120,
or 4, s0 460 V in a 480-V system would be 460/4, or 115 V.
‘The tolerance limits of the 460-V motor as they relate to the 120-V base become
115 V + 10 percent, or 126.5 V, and 115 V~ 10 percent, or 103.5 V. The problem is
to decide how this tolerance range of 23 V should be divided between the primary
distribution system, the distribution transformer, and the secondary distribution
system that make up the regulated distribution system. The solution adopted by
American National Standards Committee C84 is shown in Table 11.1.8,
11.1.8 Standard Voltage Profile for a Regulated
Power-Distribution System, 120-V Base
TABLE 11.1.8
Range A Range B
Maximum allowable voltage 126(125+) 127
Voltage-drop allowance for the primary distribution feeder 9 13
‘Minimum primary service voltage na ns
Voltage drop allowance for the distribution transformer 3 ‘
Minimum low-voltage service voltage 114 0
‘Voltage drop allowance for the building wiring 64) 644)
Minimum utilzation voltage 108(1104 ) 104(1064 |
*For utilization voltages of 120-600 V,
+ For building wiring circuits supplying lighting equipment,
(vom IBBE Std. 241-1990. Copyright 1990 IEEE. AU ight reserved)
11.1.9 Voltage Profile of the Limits of Range A,
ANSI C84.1-1989 (see page 11.7)
11.1.10 Voltage Ratings of Standard Motors
(see page 11.7)