Settings (Enabled Features)

PAGE 1

BANORTE
52-1 TRF-1
DEVICE DEFINITION
ORDER CODE: 750-P5-G5-S5-HI-A20-R-E
VERSION: 7.4X
SERIAL NUMBER: B2752342
DESCRIPTION: ALIM. SUBESTACION TRF-1
INTERFACE:COM6: 9600 N 8 1
RELAY SETUP
FRONT PANEL
Flash Message Time
Default Message Timeout

4.0 s
300 s

PASSCODE
EVENT RECORDER
Event Recorder Function
Record Trip Events
Record Alarm Events
Record Set Time/Date Events

Enabled
Enabled
Enabled
Enabled

TRACE MEMORY
Buffer Organization
Trigger Position
Trigger on pickup
Trigger on dropout
Trigger on trip
Trigger on alarm
Trigger on control

16 x 512
25 %
Active
Inactive
Active
Inactive
Inactive

USER TEXT MESSAGES


User Text Message 1
User Text Message 2
User Text Message 3
User Text Message 4
User Text Message 5

52-TRF01
POTENCIA 2000 K.V.A.
23000/480 VOLTS
BAN0RTE-IXE
VERIFICADO:JULIO/26/2012

DATA LOGGER
Sample Rate
Buffer Org
Trigger Position(Relay Setup)
Trigger on alarm(Relay Setup)
Trigger on control(Relay Setup)
Trigger on dropout(Relay Setup)
Trigger on pickup(Relay Setup)
Trigger on trip(Relay Setup)
Channel 1 Source
Channel 2 Source
Channel 3 Source
Channel 4 Source
Channel 5 Source
Channel 6 Source
Channel 7 Source
Channel 8 Source

1 cycle
16 x 256
25 %
Inactive
Inactive
Inactive
Active
Active
Phase A Current
Phase B Current
Phase C Current
Neutral Current
Phase A-N Voltage
Phase B-N Voltage
Phase C-N Voltage
Frequency

INSTALLATION
: SR750/760 Operation

Ready

SERIAL PORTS
COM1 Baud Rate
COM1 Communication Hardware
Front Panel RS232 Baud Rate
COM2 Baud Rate

9600 Baud
RS485
9600 Baud
9600 Baud

MODBUS PROTOCOL
Slave Address

25

DNP COMMUNICATIONS
Transmission Delay
Data Link Confirmation Mode
Data Link Confirmation Timeout
Data Link Confirmation Retries
Select/Operate Arm Timer Duration
Write Time Interval

0 ms
Never
1000 ms
3
10000 ms
0 ms

SYSTEM SETUP
SENSING
Phase CT Primary
Ground CT Primary
Sensitive Ground CT Primary

300 A
300 A
1000 A

Thu Jul 26 14:08:16 2012

Settings (Enabled Features)

PAGE 2

BANORTE
52-1 TRF-1
DEVICE DEFINITION
ORDER CODE: 750-P5-G5-S5-HI-A20-R-E
VERSION: 7.4X
SERIAL NUMBER: B2752342
DESCRIPTION: ALIM. SUBESTACION TRF-1
INTERFACE:COM6: 9600 N 8 1
SENSING (continued from last page)
Bus VT Connection Type
Bus Nominal VT Secondary Voltage
Bus VT Ratio
Line VT Connection
Line Nominal VT Secondary Voltage
Line VT Ratio
Nominal Frequency
Phase Sequence
Cost of energy

Delta
120.0 V
200.0 : 1
Vbn
120.0 V
120.0 : 1
60 Hz
ABC
5.0 cents/kWh

FLEXCURVE A
FlexCurve A Trip Time at 1.03 x PU
FlexCurve A Trip Time at 1.05 x PU
FlexCurve A Trip Time at 1.10 x PU
FlexCurve A Trip Time at 1.20 x PU
FlexCurve A Trip Time at 1.30 x PU
FlexCurve A Trip Time at 1.40 x PU
FlexCurve A Trip Time at 1.50 x PU
FlexCurve A Trip Time at 1.60 x PU
FlexCurve A Trip Time at 1.70 x PU
FlexCurve A Trip Time at 1.80 x PU
FlexCurve A Trip Time at 1.90 x PU
FlexCurve A Trip Time at 2.00 x PU
FlexCurve A Trip Time at 2.10 x PU
FlexCurve A Trip Time at 2.20 x PU
FlexCurve A Trip Time at 2.30 x PU
FlexCurve A Trip Time at 2.40 x PU
FlexCurve A Trip Time at 2.50 x PU
FlexCurve A Trip Time at 2.60 x PU
FlexCurve A Trip Time at 2.70 x PU
FlexCurve A Trip Time at 2.80 x PU
FlexCurve A Trip Time at 2.90 x PU
FlexCurve A Trip Time at 3.00 x PU
FlexCurve A Trip Time at 3.10 x PU
FlexCurve A Trip Time at 3.20 x PU
FlexCurve A Trip Time at 3.30 x PU
FlexCurve A Trip Time at 3.40 x PU
FlexCurve A Trip Time at 3.50 x PU
FlexCurve A Trip Time at 3.60 x PU
FlexCurve A Trip Time at 3.70 x PU
FlexCurve A Trip Time at 3.80 x PU
FlexCurve A Trip Time at 3.90 x PU
FlexCurve A Trip Time at 4.00 x PU
FlexCurve A Trip Time at 4.10 x PU
FlexCurve A Trip Time at 4.20 x PU
FlexCurve A Trip Time at 4.30 x PU
FlexCurve A Trip Time at 4.40 x PU
FlexCurve A Trip Time at 4.50 x PU
FlexCurve A Trip Time at 4.60 x PU
FlexCurve A Trip Time at 4.70 x PU
FlexCurve A Trip Time at 4.80 x PU
FlexCurve A Trip Time at 4.90 x PU
FlexCurve A Trip Time at 5.00 x PU
FlexCurve A Trip Time at 5.10 x PU
FlexCurve A Trip Time at 5.20 x PU
FlexCurve A Trip Time at 5.30 x PU
FlexCurve A Trip Time at 5.40 x PU
FlexCurve A Trip Time at 5.50 x PU
FlexCurve A Trip Time at 5.60 x PU
FlexCurve A Trip Time at 5.70 x PU
FlexCurve A Trip Time at 5.80 x PU
FlexCurve A Trip Time at 5.90 x PU
FlexCurve A Trip Time at 6.00 x PU
FlexCurve A Trip Time at 6.50 x PU
FlexCurve A Trip Time at 7.00 x PU
FlexCurve A Trip Time at 7.50 x PU
FlexCurve A Trip Time at 8.00 x PU
FlexCurve A Trip Time at 8.50 x PU
FlexCurve A Trip Time at 9.00 x PU
FlexCurve A Trip Time at 9.50 x PU

65000 ms
65000 ms
65000 ms
65000 ms
65000 ms
65000 ms
65000 ms
65000 ms
63495 ms
53565 ms
45975 ms
40005 ms
35190 ms
31245 ms
27975 ms
25215 ms
22860 ms
20835 ms
19080 ms
17550 ms
16200 ms
15000 ms
13935 ms
12990 ms
12135 ms
11370 ms
10665 ms
10035 ms
9450 ms
8925 ms
8445 ms
7995 ms
7590 ms
7215 ms
6855 ms
6540 ms
6240 ms
5955 ms
5685 ms
5445 ms
5220 ms
4995 ms
4800 ms
4605 ms
4425 ms
4260 ms
4110 ms
3960 ms
3810 ms
3675 ms
3555 ms
3435 ms
2910 ms
2505 ms
2175 ms
1905 ms
1680 ms
1500 ms
1350 ms

Thu Jul 26 14:08:16 2012

Settings (Enabled Features)

PAGE 3

BANORTE
52-1 TRF-1
DEVICE DEFINITION
ORDER CODE: 750-P5-G5-S5-HI-A20-R-E
VERSION: 7.4X
SERIAL NUMBER: B2752342
DESCRIPTION: ALIM. SUBESTACION TRF-1
INTERFACE:COM6: 9600 N 8 1
FLEXCURVE A (continued from last page)
FlexCurve A Trip Time at 10.0 x PU
FlexCurve A Trip Time at 10.5 x PU
FlexCurve A Trip Time at 11.0 x PU
FlexCurve A Trip Time at 11.5 x PU
FlexCurve A Trip Time at 12.0 x PU
FlexCurve A Trip Time at 12.5 x PU
FlexCurve A Trip Time at 13.0 x PU
FlexCurve A Trip Time at 13.5 x PU
FlexCurve A Trip Time at 14.0 x PU
FlexCurve A Trip Time at 14.5 x PU
FlexCurve A Trip Time at 15.0 x PU
FlexCurve A Trip Time at 15.5 x PU
FlexCurve A Trip Time at 16.0 x PU
FlexCurve A Trip Time at 16.5 x PU
FlexCurve A Trip Time at 17.0 x PU
FlexCurve A Trip Time at 17.5 x PU
FlexCurve A Trip Time at 18.0 x PU
FlexCurve A Trip Time at 18.5 x PU
FlexCurve A Trip Time at 19.0 x PU
FlexCurve A Trip Time at 19.5 x PU
FlexCurve A Trip Time at 20.0 x PU

1215 ms
1095 ms
1005 ms
915 ms
840 ms
780 ms
720 ms
660 ms
615 ms
570 ms
540 ms
495 ms
465 ms
435 ms
420 ms
390 ms
375 ms
345 ms
330 ms
315 ms
300 ms

FLEXCURVE B
FlexCurve B Trip Time at 1.03 x PU
FlexCurve B Trip Time at 1.05 x PU
FlexCurve B Trip Time at 1.10 x PU
FlexCurve B Trip Time at 1.20 x PU
FlexCurve B Trip Time at 1.30 x PU
FlexCurve B Trip Time at 1.40 x PU
FlexCurve B Trip Time at 1.50 x PU
FlexCurve B Trip Time at 1.60 x PU
FlexCurve B Trip Time at 1.70 x PU
FlexCurve B Trip Time at 1.80 x PU
FlexCurve B Trip Time at 1.90 x PU
FlexCurve B Trip Time at 2.00 x PU
FlexCurve B Trip Time at 2.10 x PU
FlexCurve B Trip Time at 2.20 x PU
FlexCurve B Trip Time at 2.30 x PU
FlexCurve B Trip Time at 2.40 x PU
FlexCurve B Trip Time at 2.50 x PU
FlexCurve B Trip Time at 2.60 x PU
FlexCurve B Trip Time at 2.70 x PU
FlexCurve B Trip Time at 2.80 x PU
FlexCurve B Trip Time at 2.90 x PU
FlexCurve B Trip Time at 3.00 x PU
FlexCurve B Trip Time at 3.10 x PU
FlexCurve B Trip Time at 3.20 x PU
FlexCurve B Trip Time at 3.30 x PU
FlexCurve B Trip Time at 3.40 x PU
FlexCurve B Trip Time at 3.50 x PU
FlexCurve B Trip Time at 3.60 x PU
FlexCurve B Trip Time at 3.70 x PU
FlexCurve B Trip Time at 3.80 x PU
FlexCurve B Trip Time at 3.90 x PU
FlexCurve B Trip Time at 4.00 x PU
FlexCurve B Trip Time at 4.10 x PU
FlexCurve B Trip Time at 4.20 x PU
FlexCurve B Trip Time at 4.30 x PU
FlexCurve B Trip Time at 4.40 x PU
FlexCurve B Trip Time at 4.50 x PU
FlexCurve B Trip Time at 4.60 x PU
FlexCurve B Trip Time at 4.70 x PU
FlexCurve B Trip Time at 4.80 x PU
FlexCurve B Trip Time at 4.90 x PU
FlexCurve B Trip Time at 5.00 x PU
FlexCurve B Trip Time at 5.10 x PU
FlexCurve B Trip Time at 5.20 x PU
FlexCurve B Trip Time at 5.30 x PU
FlexCurve B Trip Time at 5.40 x PU
FlexCurve B Trip Time at 5.50 x PU

12952 ms
11940 ms
9847 ms
6974 ms
5163 ms
3963 ms
3134 ms
2541 ms
2105 ms
1777 ms
1524 ms
1325 ms
1167 ms
1038 ms
933 ms
846 ms
772 ms
710 ms
657 ms
611 ms
572 ms
537 ms
506 ms
479 ms
455 ms
434 ms
414 ms
397 ms
381 ms
366 ms
353 ms
341 ms
330 ms
320 ms
310 ms
302 ms
293 ms
286 ms
279 ms
272 ms
266 ms
260 ms
254 ms
249 ms
244 ms
240 ms
235 ms

Thu Jul 26 14:08:16 2012

Settings (Enabled Features)

PAGE 4

BANORTE
52-1 TRF-1
DEVICE DEFINITION
ORDER CODE: 750-P5-G5-S5-HI-A20-R-E
VERSION: 7.4X
SERIAL NUMBER: B2752342
DESCRIPTION: ALIM. SUBESTACION TRF-1
INTERFACE:COM6: 9600 N 8 1
FLEXCURVE B (continued from last page)
FlexCurve B Trip Time at 5.60 x PU
FlexCurve B Trip Time at 5.70 x PU
FlexCurve B Trip Time at 5.80 x PU
FlexCurve B Trip Time at 5.90 x PU
FlexCurve B Trip Time at 6.00 x PU
FlexCurve B Trip Time at 6.50 x PU
FlexCurve B Trip Time at 7.00 x PU
FlexCurve B Trip Time at 7.50 x PU
FlexCurve B Trip Time at 8.00 x PU
FlexCurve B Trip Time at 8.50 x PU
FlexCurve B Trip Time at 9.00 x PU
FlexCurve B Trip Time at 9.50 x PU
FlexCurve B Trip Time at 10.0 x PU
FlexCurve B Trip Time at 10.5 x PU
FlexCurve B Trip Time at 11.0 x PU
FlexCurve B Trip Time at 11.5 x PU
FlexCurve B Trip Time at 12.0 x PU
FlexCurve B Trip Time at 12.5 x PU
FlexCurve B Trip Time at 13.0 x PU
FlexCurve B Trip Time at 13.5 x PU
FlexCurve B Trip Time at 14.0 x PU
FlexCurve B Trip Time at 14.5 x PU
FlexCurve B Trip Time at 15.0 x PU
FlexCurve B Trip Time at 15.5 x PU
FlexCurve B Trip Time at 16.0 x PU
FlexCurve B Trip Time at 16.5 x PU
FlexCurve B Trip Time at 17.0 x PU
FlexCurve B Trip Time at 17.5 x PU
FlexCurve B Trip Time at 18.0 x PU
FlexCurve B Trip Time at 18.5 x PU
FlexCurve B Trip Time at 19.0 x PU
FlexCurve B Trip Time at 19.5 x PU
FlexCurve B Trip Time at 20.0 x PU
LOGIC INPUTS
LOGIC INPUT SETUP
LOGIC INPUT SETUP
Logic Input 1
Logic Input 2
Logic Input 3
Logic Input 4
Logic Input 5
Logic Input 6
Logic Input 7
Logic Input 8
Logic Input 9
Logic Input 10
Logic Input 11
Logic Input 12
Logic Input 13
Logic Input 14
Logic Input 15
Logic Input 16
Logic Input 17
Logic Input 18
Logic Input 19
Logic Input 20
Logic Input 1 Asserted Logic
Logic Input 2 Asserted Logic
Logic Input 3 Asserted Logic
Logic Input 4 Asserted Logic
Logic Input 5 Asserted Logic
Logic Input 6 Asserted Logic
Logic Input 7 Asserted Logic
Logic Input 8 Asserted Logic
Logic Input 9 Asserted Logic
Logic Input 10 Asserted Logic
Logic Input 11 Asserted Logic
Logic Input 12 Asserted Logic
Logic Input 13 Asserted Logic

231 ms
227 ms
223 ms
220 ms
216 ms
201 ms
189 ms
179 ms
170 ms
163 ms
156 ms
151 ms
146 ms
141 ms
137 ms
134 ms
131 ms
128 ms
125 ms
122 ms
120 ms
118 ms
116 ms
114 ms
112 ms
111 ms
109 ms
108 ms
107 ms
105 ms
104 ms
103 ms
102 ms

Logic Input 1
Logic Input 2
Logic Input 3
Logic Input 4
Logic Input 5
Logic Input 6
Logic Input 7
Logic Input 8
Logic Input 9
Logic Input 10
Logic Input 11
Logic Input 12
Logic Input 13
Logic Input 14
Logic Input 15
Logic Input 16
Logic Input 17
Logic Input 18
Logic Input 19
Logic Input 20
Contact Close
Contact Close
Contact Close
Contact Close
Contact Close
Contact Close
Contact Close
Contact Close
Contact Close
Contact Close
Contact Close
Contact Close
Contact Close

Thu Jul 26 14:08:16 2012

Settings (Enabled Features)

PAGE 5

BANORTE
52-1 TRF-1
DEVICE DEFINITION
ORDER CODE: 750-P5-G5-S5-HI-A20-R-E
VERSION: 7.4X
SERIAL NUMBER: B2752342
DESCRIPTION: ALIM. SUBESTACION TRF-1
INTERFACE:COM6: 9600 N 8 1
LOGIC INPUT SETUP (continued from last page)
Logic Input 14 Asserted Logic

Contact Close

BREAKER FUNCTIONS
BREAKER FUNCTIONS
52b Contact

Input 1

USER INPUTS
USER INPUT A
User Input A Name

User Input A

USER INPUT B
User Input B Name

User Input B

USER INPUT C
User Input C Name

User Input C

USER INPUT D
User Input D Name

User Input D

USER INPUT E
User Input E Name

User Input E

USER INPUT F
User Input F Name

User Input F

USER INPUT G
User Input G Name

User Input G

USER INPUT H
User Input H Name

User Input H

USER INPUT I
User Input I Name

User Input I

USER INPUT J
User Input J Name

User Input J

USER INPUT K
User Input K Name

User Input K

USER INPUT L
User Input L Name

User Input L

USER INPUT M
User Input M Name

User Input M

USER INPUT N
User Input N Name

User Input N

USER INPUT O
User Input O Name

User Input O

USER INPUT P
User Input P Name

User Input P

USER INPUT Q
User Input Q Name

User Input Q

USER INPUT R
User Input R Name

User Input R

USER INPUT S
User Input S Name

User Input S

USER INPUT T
User Input T Name

User Input T

OUTPUT RELAYS
1 TRIP
1 TRIP Seal In Time

0.04 s

Thu Jul 26 14:08:16 2012

Settings (Enabled Features)

PAGE 6

BANORTE
52-1 TRF-1
DEVICE DEFINITION
ORDER CODE: 750-P5-G5-S5-HI-A20-R-E
VERSION: 7.4X
SERIAL NUMBER: B2752342
DESCRIPTION: ALIM. SUBESTACION TRF-1
INTERFACE:COM6: 9600 N 8 1
2 CLOSE
2 CLOSE Seal In Time

0.04 s

3 AUXILIARY
3 AUXILIARY Name
3 AUXILIARY Non-operated State
3 AUXILIARY Output Type

DISPARO
De-energized
Latched

4 AUXILIARY
4 AUXILIARY Name
4 AUXILIARY Non-operated State
4 AUXILIARY Output Type

AUXILIARY
De-energized
Self-Resetting

5 AUXILIARY
5 AUXILIARY Name
5 AUXILIARY Non-operated State
5 AUXILIARY Output Type

AUXILIARY
De-energized
Self-Resetting

6 AUXILIARY
6 AUXILIARY Name
6 AUXILIARY Non-operated State
6 AUXILIARY Output Type

ALARMA
De-energized
Self-Resetting

7 AUXILIARY
7 AUXILIARY Name
7 AUXILIARY Non-operated State
7 AUXILIARY Output Type

AUXILIARY
De-energized
Self-Resetting

PROTECTION
PHASE CURRENT
PHASE TIME OVERCURRENT 1
Phase Time Overcurrent 1 Function
Phase Time Overcurrent 1: Relay 3
Phase Time Overcurrent 1: Relay 4
Phase Time Overcurrent 1: Relay 5
Phase Time Overcurrent 1: Relay 6
Phase Time Overcurrent 1: Relay 7
Phase Time Overcurrent 1 Pickup(Setpoints)
Phase Time Overcurrent 1 Curve
Phase Time Overcurrent 1 Multiplier
Phase Time Overcurrent 1 Reset

Trip
Operate
Do Not Operate
Operate
Operate
Do Not Operate
0.20 x CT
IEC Curve C
1.50
Instantaneous

PHASE INSTANTANEOUS OVERCURRENT 1


Phase Instantaneous Overcurrent 1 Function
Phase Instantaneous Overcurrent 1: Relay 3
Phase Instantaneous Overcurrent 1: Relay 4
Phase Instantaneous Overcurrent 1: Relay 5
Phase Instantaneous Overcurrent 1: Relay 6
Phase Instantaneous Overcurrent 1: Relay 7
Phase Instantaneous Overcurrent 1 Pickup(Setpoints)
Phase Instantaneous Overcurrent 1 Delay
Phases Required for Operation(O/C 1)

Trip
Operate
Do Not Operate
Operate
Operate
Do Not Operate
3.50 x CT
0.00 s
Any One

GROUND CURRENT
GROUND TIME OVERCURRENT
Ground Time Overcurrent Function
Ground Time Overcurrent: Relay 3
Ground Time Overcurrent: Relay 4
Ground Time Overcurrent: Relay 5
Ground Time Overcurrent: Relay 6
Ground Time Overcurrent: Relay 7
Ground Time Overcurrent Pickup(Setpoints)
Ground Time Overcurrent Curve
Ground Time Overcurrent Multiplier
Ground Time Overcurrent Reset

Trip
Operate
Do Not Operate
Operate
Operate
Do Not Operate
0.10 x CT
Very Inverse
1.00
Instantaneous

GROUND INSTANTANEOUS OVERCURRENT


Ground Instantaneous Overcurrent Function
Ground Instantaneous Overcurrent: Relay 3
Ground Instantaneous Overcurrent: Relay 4

Trip
Operate
Do Not Operate

Thu Jul 26 14:08:16 2012

Settings (Enabled Features)

PAGE 7

BANORTE
52-1 TRF-1
DEVICE DEFINITION
ORDER CODE: 750-P5-G5-S5-HI-A20-R-E
VERSION: 7.4X
SERIAL NUMBER: B2752342
DESCRIPTION: ALIM. SUBESTACION TRF-1
INTERFACE:COM6: 9600 N 8 1
GROUND INSTANTANEOUS OVERCURRENT (continued from last page)
Ground Instantaneous Overcurrent: Relay 5
Ground Instantaneous Overcurrent: Relay 6
Ground Instantaneous Overcurrent: Relay 7
Ground Instantaneous Overcurrent Pickup(Setpoints)
Ground Instantaneous Overcurrent Delay

Operate
Operate
Do Not Operate
1.00 x CT
0.00 s

NEUTRAL CURRENT
NEUTRAL TIME OVERCURRENT 1
Neutral Time Overcurrent 1 Function
Neutral Time Overcurrent 1: Relay 3
Neutral Time Overcurrent 1: Relay 4
Neutral Time Overcurrent 1: Relay 5
Neutral Time Overcurrent 1: Relay 6
Neutral Time Overcurrent 1: Relay 7
Neutral Time Overcurrent 1 Pickup(Setpoints)
Neutral Time Overcurrent 1 Curve
Neutral Time Overcurrent 1 Multiplier
Neutral Time Overcurrent 1 Reset Time

Trip
Operate
Do Not Operate
Operate
Operate
Operate
0.10 x CT
Very Inverse
1.00
Instantaneous

NEUTRAL INSTANTANEOUS OVERCURRENT 1


Neutral Instantaneous Overcurrent 1 Function
Neutral Instantaneous Overcurrent 1: Relay 3
Neutral Instantaneous Overcurrent 1: Relay 4
Neutral Instantaneous Overcurrent 1: Relay 5
Neutral Instantaneous Overcurrent 1: Relay 6
Neutral Instantaneous Overcurrent 1: Relay 7
Neutral Instantaneous Overcurrent 1 Pickup(Setpoints)
Neutral Instantaneous Overcurrent 1 Delay

Trip
Operate
Do Not Operate
Operate
Operate
Do Not Operate
1.00 x CT
0.00 s

VOLTAGE
BUS UNDERVOLTAGE 1
Bus Undervoltage 1 Function
Bus UnderVoltage 1: Relay 3
Bus UnderVoltage 1: Relay 4
Bus UnderVoltage 1: Relay 5
Bus UnderVoltage 1: Relay 6
Bus UnderVoltage 1: Relay 7
Bus Undervoltage 1 Pickup(Setpoints)
Bus Undervoltage 1 Curve
Bus Undervoltage 1 Delay
Bus Undervoltage 1 Phases Required for Operation
Bus Undervoltage 1 Minimum Operating Voltage

Trip
Do Not Operate
Operate
Do Not Operate
Operate
Do Not Operate
0.85 x VT
Definite Time
5.0 s
All Three
0.00 x VT

BUS UNDERVOLTAGE 2
Bus Undervoltage 2 Function
Bus UnderVoltage 2: Relay 3
Bus UnderVoltage 2: Relay 4
Bus UnderVoltage 2: Relay 5
Bus UnderVoltage 2: Relay 6
Bus UnderVoltage 2: Relay 7
Bus Undervoltage 2 Pickup(Setpoints)
Bus Undervoltage 2 Curve
Bus Undervoltage 2 Delay
Bus Undervoltage 2 Phases Required for Operation
Bus Undervoltage 2 Minimum Operating Voltage

Alarm
Do Not Operate
Do Not Operate
Do Not Operate
Do Not Operate
Do Not Operate
0.90 x VT
Definite Time
1.5 s
All Three
0.50 x VT

OVERVOLTAGE 1
Overvoltage 1 Function
Overvoltage 1: Relay 3
Overvoltage 1: Relay 4
Overvoltage 1: Relay 5
Overvoltage 1: Relay 6
Overvoltage 1: Relay 7
Overvoltage 1 Pickup(Setpoints)
Overvoltage 1 Delay
Overvoltage 1 Phases Required for Operation

Alarm
Do Not Operate
Do Not Operate
Do Not Operate
Do Not Operate
Do Not Operate
1.05 x VT
1.5 s
All Three

FREQUENCY
UNDERFREQUENCY 1
Underfrequency 1 Function

Trip

Thu Jul 26 14:08:16 2012

Settings (Enabled Features)

PAGE 8

BANORTE
52-1 TRF-1
DEVICE DEFINITION
ORDER CODE: 750-P5-G5-S5-HI-A20-R-E
VERSION: 7.4X
SERIAL NUMBER: B2752342
DESCRIPTION: ALIM. SUBESTACION TRF-1
INTERFACE:COM6: 9600 N 8 1
UNDERFREQUENCY 1 (continued from last page)
Underfrequency 1: Relay 3
Underfrequency 1: Relay 4
Underfrequency 1: Relay 5
Underfrequency 1: Relay 6
Underfrequency 1: Relay 7
Underfrequency 1 Pickup(Setpoints)
Underfrequency 1 Delay
Underfrequency 1 Minimum Operating Voltage
Underfrequency 1 Minimum Operating Current

Do Not Operate
Operate
Do Not Operate
Operate
Do Not Operate
58.00 Hz
3.00 s
0.70 x VT
0.00 x CT

FAULT LOCATOR
Length of Feeder
Units of Length
Zpos (Resistive) of Feeder
Zpos (Inductive) of Feeder
Zzero (Resistive) of Feeder
Zzero (Inductive) of Feeder

0.1
km
0.01 Ohm
0.01 Ohm
0.01 Ohm
0.01 Ohm

ANALOG INPUT
SETUP
Analog Input Name (10 words)
Analog Input Units (3 words)
Analog Input Range
Analog Input Minimum Value
Analog Input Maximum Value

ANALOG INPUT
uA
0-20 mA
0 uA
20000 uA

THRESHOLD 1
Analog Input Threshold 1 Name

ANALOG THRESHLD 1

THRESHOLD 2
Analog Input Threshold 2 Name

ANALOG THRESHLD 2

OVERFREQUENCY
Overfrequency Function
Overfrequency: Relay 3
Overfrequency: Relay 4
Overfrequency: Relay 5
Overfrequency: Relay 6
Overfrequency: Relay 7
Overfrequency Pickup(Setpoints)
Overfrequency Delay

Alarm
Do Not Operate
Do Not Operate
Do Not Operate
Do Not Operate
Do Not Operate
62.00 Hz
2.0 s

COIL MONITOR 1
Coil Monitor 1 Name

Trip Coil Monitor

COIL MONITOR 2
Coil Monitor 2 Name

Close Coil Monitor

CONTROL
SETPOINT GROUPS
SETPOINT GROUPS
Active Setpoint Group(Setpoints)
Edit Setpoint Group(Setpoints)

Group 1
Active Group

PROTECTION
PHASE CURRENT[SETPOINT GROUP 1]
PHASE TIME OVERCURRENT 1[SETPOINT GROUP 1]
Phase Time Overcurrent 1 Function
Phase Time Overcurrent 1: Relay 3
Phase Time Overcurrent 1: Relay 4
Phase Time Overcurrent 1: Relay 5
Phase Time Overcurrent 1: Relay 6
Phase Time Overcurrent 1: Relay 7
Phase Time Overcurrent 1 Pickup(Setpoints)
Phase Time Overcurrent 1 Curve
Phase Time Overcurrent 1 Multiplier
Phase Time Overcurrent 1 Reset

Trip
Operate
Do Not Operate
Operate
Operate
Do Not Operate
0.20 x CT
IEC Curve C
1.50
Instantaneous

PHASE INSTANTANEOUS OVERCURRENT 1[SETPOINT GROUP 1]


Phase Instantaneous Overcurrent 1 Function

Trip

Thu Jul 26 14:08:16 2012

Settings (Enabled Features)

PAGE 9

BANORTE
52-1 TRF-1
DEVICE DEFINITION
ORDER CODE: 750-P5-G5-S5-HI-A20-R-E
VERSION: 7.4X
SERIAL NUMBER: B2752342
DESCRIPTION: ALIM. SUBESTACION TRF-1
INTERFACE:COM6: 9600 N 8 1
PHASE INSTANTANEOUS OVERCURRENT 1[SETPOINT GROUP 1] (continued from last page)
Phase Instantaneous Overcurrent 1: Relay 3
Operate
Phase Instantaneous Overcurrent 1: Relay 4
Do Not Operate
Phase Instantaneous Overcurrent 1: Relay 5
Operate
Phase Instantaneous Overcurrent 1: Relay 6
Operate
Phase Instantaneous Overcurrent 1: Relay 7
Do Not Operate
Phase Instantaneous Overcurrent 1 Pickup(Setpoints)
3.50 x CT
Phase Instantaneous Overcurrent 1 Delay
0.00 s
Phases Required for Operation(O/C 1)
Any One
GROUND CURRENT[SETPOINT GROUP 1]
GROUND TIME OVERCURRENT[SETPOINT GROUP 1]
Ground Time Overcurrent Function
Ground Time Overcurrent: Relay 3
Ground Time Overcurrent: Relay 4
Ground Time Overcurrent: Relay 5
Ground Time Overcurrent: Relay 6
Ground Time Overcurrent: Relay 7
Ground Time Overcurrent Pickup(Setpoints)
Ground Time Overcurrent Curve
Ground Time Overcurrent Multiplier
Ground Time Overcurrent Reset

Trip
Operate
Do Not Operate
Operate
Operate
Do Not Operate
0.10 x CT
Very Inverse
1.00
Instantaneous

GROUND INSTANTANEOUS OVERCURRENT[SETPOINT GROUP 1]


Ground Instantaneous Overcurrent Function
Ground Instantaneous Overcurrent: Relay 3
Ground Instantaneous Overcurrent: Relay 4
Ground Instantaneous Overcurrent: Relay 5
Ground Instantaneous Overcurrent: Relay 6
Ground Instantaneous Overcurrent: Relay 7
Ground Instantaneous Overcurrent Pickup(Setpoints)
Ground Instantaneous Overcurrent Delay

Trip
Operate
Do Not Operate
Operate
Operate
Do Not Operate
1.00 x CT
0.00 s

NEUTRAL CURRENT[SETPOINT GROUP 1]


NEUTRAL TIME OVERCURRENT 1[SETPOINT GROUP 1]
Neutral Time Overcurrent 1 Function
Neutral Time Overcurrent 1: Relay 3
Neutral Time Overcurrent 1: Relay 4
Neutral Time Overcurrent 1: Relay 5
Neutral Time Overcurrent 1: Relay 6
Neutral Time Overcurrent 1: Relay 7
Neutral Time Overcurrent 1 Pickup(Setpoints)
Neutral Time Overcurrent 1 Curve
Neutral Time Overcurrent 1 Multiplier
Neutral Time Overcurrent 1 Reset Time

Trip
Operate
Do Not Operate
Operate
Operate
Operate
0.10 x CT
Very Inverse
1.00
Instantaneous

NEUTRAL INSTANTANEOUS OVERCURRENT 1[SETPOINT GROUP 1]


Neutral Instantaneous Overcurrent 1 Function
Neutral Instantaneous Overcurrent 1: Relay 3
Neutral Instantaneous Overcurrent 1: Relay 4
Neutral Instantaneous Overcurrent 1: Relay 5
Neutral Instantaneous Overcurrent 1: Relay 6
Neutral Instantaneous Overcurrent 1: Relay 7
Neutral Instantaneous Overcurrent 1 Pickup(Setpoints)
Neutral Instantaneous Overcurrent 1 Delay

Trip
Operate
Do Not Operate
Operate
Operate
Do Not Operate
1.00 x CT
0.00 s

VOLTAGE[SETPOINT GROUP 1]
BUS UNDERVOLTAGE 1[SETPOINT GROUP 1]
Bus Undervoltage 1 Function
Bus UnderVoltage 1: Relay 3
Bus UnderVoltage 1: Relay 4
Bus UnderVoltage 1: Relay 5
Bus UnderVoltage 1: Relay 6
Bus UnderVoltage 1: Relay 7
Bus Undervoltage 1 Pickup(Setpoints)
Bus Undervoltage 1 Curve
Bus Undervoltage 1 Delay
Bus Undervoltage 1 Phases Required for Operation
Bus Undervoltage 1 Minimum Operating Voltage

Trip
Do Not Operate
Operate
Do Not Operate
Operate
Do Not Operate
0.85 x VT
Definite Time
5.0 s
All Three
0.00 x VT

BUS UNDERVOLTAGE 2[SETPOINT GROUP 1]

Thu Jul 26 14:08:16 2012

Settings (Enabled Features)

PAGE 10

BANORTE
52-1 TRF-1
DEVICE DEFINITION
ORDER CODE: 750-P5-G5-S5-HI-A20-R-E
VERSION: 7.4X
SERIAL NUMBER: B2752342
DESCRIPTION: ALIM. SUBESTACION TRF-1
INTERFACE:COM6: 9600 N 8 1
BUS UNDERVOLTAGE 2[SETPOINT GROUP 1] (continued from last page)
Bus Undervoltage 2 Function
Bus UnderVoltage 2: Relay 3
Bus UnderVoltage 2: Relay 4
Bus UnderVoltage 2: Relay 5
Bus UnderVoltage 2: Relay 6
Bus UnderVoltage 2: Relay 7
Bus Undervoltage 2 Pickup(Setpoints)
Bus Undervoltage 2 Curve
Bus Undervoltage 2 Delay
Bus Undervoltage 2 Phases Required for Operation
Bus Undervoltage 2 Minimum Operating Voltage

Alarm
Do Not Operate
Do Not Operate
Do Not Operate
Do Not Operate
Do Not Operate
0.90 x VT
Definite Time
1.5 s
All Three
0.50 x VT

OVERVOLTAGE 1[SETPOINT GROUP 1]


Overvoltage 1 Function
Overvoltage 1: Relay 3
Overvoltage 1: Relay 4
Overvoltage 1: Relay 5
Overvoltage 1: Relay 6
Overvoltage 1: Relay 7
Overvoltage 1 Pickup(Setpoints)
Overvoltage 1 Delay
Overvoltage 1 Phases Required for Operation

Alarm
Do Not Operate
Do Not Operate
Do Not Operate
Do Not Operate
Do Not Operate
1.05 x VT
1.5 s
All Three

FREQUENCY[SETPOINT GROUP 1]
UNDERFREQUENCY 1[SETPOINT GROUP 1]
Underfrequency 1 Function
Underfrequency 1: Relay 3
Underfrequency 1: Relay 4
Underfrequency 1: Relay 5
Underfrequency 1: Relay 6
Underfrequency 1: Relay 7
Underfrequency 1 Pickup(Setpoints)
Underfrequency 1 Delay
Underfrequency 1 Minimum Operating Voltage
Underfrequency 1 Minimum Operating Current

Trip
Do Not Operate
Operate
Do Not Operate
Operate
Do Not Operate
58.00 Hz
3.00 s
0.70 x VT
0.00 x CT