Sie sind auf Seite 1von 36

Bearing Insulation Testing

in
Rotating Machinery
by

Paul I. Nippes, PE
and Beth Galano
Magnetic Products and Services, Inc.
Holmdel, NJ 07733

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
Table of Contents
The value and problems of bearing insulation are addressed.
Examples of damage are provided where bearing insulation had been shorted
out, or was ineffective.
Examples for insulating bearings and couplings are shown.
Simplified diagrams for shaft current flow are presented.
An example of un-measureable, circulating bearing current from homo-polar
magnetic flux is presented
Safety during testing is stressed.
Methods for determining the integrity of bearing insulation are provided in the
form of IEEE Standards and MPS practices for testing bearing insulation.
Insulation testing methods with the unit operating are addressed.

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
WHY INSULATE BEARINGS ?

First insulated to block stray currents from destroying bearings in


electric motors and generators in the early 1900’s.
Bearing insulation continues to be installed at the outboard end of
electrical machines.
expensive to install and maintain
lowers the bearing support stiffness, adding complication to design and
vibration analysis
when OE is also a drive, electrical insulation is needed, either at the
coupling, and/or at the driven equipment as well.
In recent years, simple insulation installation is proving to be
inadequate to block bearing currents where electronic switching is
prevalent.
Two vital considerations:
resistance of the insulation
it’s capacitive impedance

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
Elementary representation of a motor driving a Load

DRIVEN-LOAD: PUMP, ELECTRIC MOTOR, SYNCHRONOUS,


COMPRESSOR, ETC. INDUCTION OR DIRECT CURRENT

ROTOR

OI L FILM
BEARING

STATOR ELECTRICAL INSULATION

Elementary diagram for considering shaft currents in typical motor - load arrangement

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
Elementary diagram for considering shaft currents in typical turbine - generator arrangement

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
“One method of insulating
bracket-type machine to
prevent flow of shaft
currents” in article “Bearing
Currents --- Their Origin and
Prevention” by C. T. Pearce,
of Westinghouse Electric,
1927

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
Modern method for insulating
bracket type machines in article
“Shaft Voltages – Shaft/Earth
Voltages – Bearing Currents”
Article “AR 170-220” by
Siemens Field Services and
Workshop Operations 04/1991

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
Modern open method to insulate pedestal bearings from article “Insulating
Rotating Machinery Against Stray Electrical Currents” by Michael M. Calistrat,
Paul I. Nippes and Ned Zeman, Preventative Maintenance Technology National
Conference -1997.

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
Modern hidden method to insulate pedestal bearings from article “Insulating Rotating Machinery
Against Stray Electrical Currents” by Michael M. Calistrat, Paul I. Nippes and Ned Zeman,
Preventative Maintenance Technology National Conference -1997.

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
Four different methods to insulate shaft couplings from article “Insulating Rotating Machinery Against Stray
Electrical Currents” by Michael M. Calistrat, Paul I. Nippes and Ned Zeman, Preventative Maintenance
Technology National Conference -1997.

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
VOLTAGE & RESISTANCE MEASUREMENTS
ELEMENTARY DIAGRAM FOR STRAY SHAFT CURRENT CIRCUIT MEASUREMENTS

DRIVEN LOAD SHAFT COUPLING MOTOR SHAFT

BEARING OIL FILM


STRAY
BEARING
POWER
SOURCE
AC/DC
INSULATION
VOLTS

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
VOLTAGE & RESISTANCE MEASUREMENTS
ELEMENTARY DIAGRAM FOR STRAY SHAFT CURRENT CIRCUIT
MEASUREMENTS

DRIVEN LOAD SHAFT COUPLING MOTOR SHAFT

BEARING OIL FILM


STRAY
BEARING
POWER
SOURCE
AC/DC
INSULATION
VOLTS

INSULATION

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
The actual shaft voltage circuits of a boiler feed pump installation in a large power plant

Insulation
needed
here

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
Boiler Feed Pump from a large Generator

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
ELECTRICAL CURRENT
DISCHARGE DAMAGE

PITTING, FROSTING

SPARK TRACKS

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
ELECTRICAL SPARK TRACKS

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
Example of localized circulating current due to through axial, or homopolar, magnetic flux in
the rotor, from an article “Bearing Currents --- Their Origin and Prevention” by C. T. Pearce,
of Westinghouse Electric, 1927

Measurement of current in the operating


machine is impossible.
Measurement of axial magnetic flux
difficult, if not impossible.

Corrections possible:
1) Degauss if cause is a residual
magnetism source.
2) Install a significant non-magnetic
member into the flux path.

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
Example of Through Magnetism generating Eddy Currents

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
Example of Through Magnetism generating Eddy Currents –
currents discharge at outside edges passing through the babbitt

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
IMPEDANCE EFFECT OF DIFFERENT FREQUENCY CURRENTS THROUGH BEARING, SEAL AND/OR COUPLING INSULATION

Of major concern is the ineffectiveness of bearing insulation when subjected to high frequency voltages and more particularly the
voltage spikes associated with electronic wave generation and switching. The exact bearing insulation impedance is difficult to
determine. A simple calculation of the resistive and capacitive components of the bearing insulation reveals a significantly lowered
capacitive impedance compared to the ideal resistive component and thus controls, along with the bearing oil film, the amount of
current through the bearing. Insulation is reduced inverse to the ratio of the frequencies. The resistive component will decrease over
time due to oil impurities and insulation deterioration over time .
Impedance vs. Frequency

1E+13
2.12E+12
1E+12
Limits of
2.12E+11 Resistance
1E+11

1E+10 l/A Ratios


0.02119
1E+09 0.042354
0.063518
1E+08 0.084682
Z (ohm ) 0.105846
1E+07 0.12701
0.148174
1E+06 0.169338
0.211667
100000

10000

1000

100
10 60 110 160 210 260 310 360
Freq (Hz)

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
Expanded capacitive impedance for different frequency currents through bearing, seal and/or coupling insulation
demonstrating the effect of the ratio of insulation thickness (i) to the insulation effective area (a) or a/i

Impedance vs. Frequency

300

250

l/A Ratios
0.02119
200
0.042354
Z (ohm ) 0.063518
0.084682
150 0.105846
0.12701
0.148174
0.169338
100
0.211667

50

0
0 500 1000 1500 2000 2500 3000 3500
Freq (Hz)

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
SAFETY FIRST WHEN MAKING SHAFT
VOLTAGE MEASUREMENTS

Wear hard hat, face shield, safety shoes.


Place voltage measuring brush onto the shaft
only after you are certain that no rotating
element, such as a keyway or bolt is in the zone
of brush contact.
Move measuring brush to the shaft very slowly
and stand to the side.

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
Same as IEEE 112, basically

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
”Safeguarding Machinery Worldwide “
www.gaussbusters.com
PART I – ACCEPTANCE AND PERFORMANCE TESTING IEEE
Std 115-1995

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
”Safeguarding Machinery Worldwide “
www.gaussbusters.com
BEARING INSULATION CONDITION BY MEASUREMENTS

Comparative evaluation of the bearing insulation is possible on electrical


machines if there is access to shaft, the bearing sleeve, its housing or pedestal.

Open access to insulated pedestals and bearing housings make it convenient


for voltmeter, ohmmeter or other reliable and safe measurements.

A disadvantage of open access is the ease for shorting around the insulation by
instrumentation, shielded cables, un-insulated bolts and dowels etc.

No access, such as completely isolated bearings, both electrically and


physically, protects from accidental shorting, and is generally safe from
insulation shorting, except for wires run internal to the isolated bearing, such
as temperature detectors.

A disadvantage of no access is the inability to make insulation measurements.


However, this can be overcome by installation of an isolated metallic separator
in the bearing insulation making a or sandwich having an insulated wire
brought out for making measurements.

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
AN ALTERNATE PROCEDURE TO FOLLOW:

READ AND RECORD VOLTAGE VALUES, WITH THE UNIT OPERATING USING
A HAND-HELD BRUSH AND A RELIABLE METER.

RECORD SPEED AND LOAD AND IF THERE IS SHAFT GROUNDING,

PHOTOGRAPH AND DESCRIBE THE SHAFT GROUNDING,

HOW IT IS CONNECTED ELECTRICALLY AND

WHERE IT IS LOCATED ON THE UNIT.

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
MPS Shaft Voltage Measurements
Measure and record the voltages, AC and DC separately if using a standard voltmeter, or
as displayed if using a VCM and/or an oscilloscope :
a) Shaft end to end voltages across the driver (motor), and then across the load,.
b) Shaft voltages combined overall end to end. Should equal the sum of voltages in a)
and indicates that the measuring brush and ground interconnections are continuous.
c) Shaft voltages to ground at the OB and IB shaft locations, First, open circuit, then
with 1k Ohm and 1 Ohm resistor in parallel across the voltmeter leads. Voltage drops
indicates: w/ 1 K Ohm = electrostatic source; w/ 1 Ohm = residual magnetic source.
d) Repeat item c) for the load shaft voltages for the OB and IB shaft locations.
e) With voltages of reasonable values in a)-c), it is expected that the highest shaft
voltage measured is across the motor/generator shaft outboard end to ground. A low
voltage indicates either low source voltage or shorting of the shaft to ground
f) If individual voltages measured in a) thru d) are basically equal to zero, voltage
measurements will not suffice to evaluate the condition of the bearing insulation and it will
be necessary to conduct the same readings using an ohmmeter, but without the patallel
resistors. A decision to do nothing at this stage may be justified because of the low
voltages measured, however this may not be a permanent situation and bearing resistance
remains unchecked. Unit shut-down measurement of the insulation may be needed
following the procedures of IEEE 115, 112 and 113.
g) To continuously track the shaft grounding current/voltage install an MPS Voltage-
Current monitor and reliable shaft grounding and voltage sending brushes.

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
Measuring Devices
Hand-held VCM readings Storage Oscilloscope Readings

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
EARLY WARNING PROVIDED BY SHAFT GROUNDING AND
VOLTAGE SENSING BRUSH SIGNALS TO THE MPS VCM

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
CONFIGURATION # TG
DUAL GROUNDING BRUSHES, DUAL VCM’S IN ONE BOX, DUAL VOLTAGE SENSING

DUAL SHAFT
BONDING TO LOWER BEARING CASING
GROUNDING
AND FROM THERE TO GROUND
BRUSHES
HP TURB. IP TURB. EXCITER

LP TURB. GENERATOR

SHAFT VOLTAGE SHAFT VOLTAGE


SENSING BRUSH SB # 1 SENSING BRUSH SB # 2

TAPPED RESISTORS VOLTAGE SPIKE


OR CURRENT SHUNTS AND TRANSIENTS
VCM-E/NSII
ABSORBER
EASY ACCESS
SHAFT CURRENT AND VOLTAGE
FOR ALARM
SIGNALS-OUT FOR CONTINUOUS
SETTINGS.
TRENDING AND ALARMING

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
Shaft Condition VCM and grounding brushes that provide early warning of problems
via monitoring shaft voltages and grounding currents

Single/Standard VCM’s Shown

VCM-E FEATURES:
1.Attaches to both an insulated shaft grounding brush for
current measurement, and to a shaft voltage sensing brush for
shaft voltage measurement.
2.Continuously monitors and outputs 4-20 ma signals for shaft
grounding currents and shaft voltages.
3.Alarms when shaft riding brushes are worn or need
adjustment.
4.Alarms on high grounding brush current or high shaft
voltage.
5.Reduces costly parts replacement.
6.Ideal for critical, large or high speed rotating machinery
requiring uninterrupted shaft grounding, while providing
reliable unit condition monitoring data.

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
Summary and Conclusions
¾ Consider bearing insulation employed and comparative impedance
values using the characteristic graphs previously presented
showing bearing insulation ratios of thickness to gross area (t/A)
as a function of different shaft voltage frequencies.
¾ Familiarize and follow bearing insulation testing standards per
IEEE, both for operating units and those at standstill.
¾ Routinely perform bearing tests with the unit running, per MPS’
recommendations and most importantly stress safety during
testing.
¾ Educate personnel to be “on-the-watch” for damage where the
bearing insulation had either been shorted out, or is ineffective.

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
LETTER OF INQUIRY ON BEARING INSULATION TESTING –PAGE 1

Mr. Nippes,
This is to request your opinion and thoughts on the following voltage measurement approach. The machine in question is a
typical large STG with double insulation at the bearing and seal on the CE of the generator. A single test lead is connected
from the metal between the insulation halves.

Thank you for the interesting e-mail. You are fortunate to have the metal member between insulation halves.
However, as you discover, inconsistent readings are confusing
Often we may have a low megger reading between the test lead and ground (or possibly indication of a short circuit). When
this condition exists we do not know for certain if both insulation halves are shorted and, if they are, if the oil film is or is not
providing adequate protection against electrical discharge and pitting. Obviously, we would not intend to operate for an
extended period of time with this condition but the question always arises concerning whether we might be experiencing
damage or not during short term operation until repairs are made. A viable and consistent test approach to make this
determination would be very helpful.

Is the unit operating when you make megger readings? What is the applied megger voltage? Megger readings may be
influenced by stray voltages on an operating unit. It is preferable to fires make voltage readings, AC and DC, or with
an MPS hand-held VCM. If there is voltage, megger or resistance readings may be inconsistent , especially if done on
the operating machine.

Have you had any experience with measuring the voltage drop between the test lead and ground and between the test lead
and the shaft as a tool to determine if one or both insulation halves are shorted?

I believe the best way to test the insulation is to connect electrically the shaft to the metal separating the insulation.
Make voltage readings from this interconnection to the lower bearing housing on the operating machine.
Next remove the interconnection insulation and measure the voltage between the metal separating the insulation and
the shaft, both AC and DC or with an MPS hand-held VCM. If a notable voltage is detected chances are that the
intervening insulation, plus the resistance of the shaft oil films, for all bearings, is high and most likely protective.
If, in the above two tests the voltage is zero, an ohmmeter or low voltage megger unit according to IEEE Testing
Standards can be utilized to measure the combined insulation resistance of the oil films. If you use a 500 V megger,
false readings can occur due to possible tracking impurities on the insulation, and in some cases, the 500 V megger will
set up a tracking path. It is preferable to use the 115V with light bulb in series as listed in IEEE 112 and 115.

”Safeguarding Machinery Worldwide “


www.gaussbusters.com
LETTER OF INQUIRY ON BEARING INSULATION TESTING –PAGE 2
Have you measured current flow in the ground path to determine if random discharges across the oil film might be occurring
or is this approach only useful for a sustained current flow?

It is virtually impossible to intercept the current path for inserting a current shunt and it can be equally difficult to
encircle the current path to ground for measure bearing AC currents. Bearing through current can be diverted from
the bearing through a shaft grounding brush, however will not be equal to the through-bearing current. The brush
current to ground can be measured using a current shunt signal to an MPS voltage current monitor, or VCM,
providing both intermittent and sustained readings, alarms and 4-20ma signals.
Do you think the oil film alone (in the absence of a mechanical problem that minimized the normal clearances) would be
sufficient to prevent electrical damage for voltages in the 10 to 20 volt range even if both insulation halves were shorted?

The answer is “YES”, and even higher voltages are possible for an ideal bearing oil film. You are correct to inquire if
the oil film may have contact or conduction and this may occur at any bearing, affecting tests made on the shaft
insulation. The oil film is an excellent isolator, but over time it is seldom without either contact or impurities. Very
often bearing problems do not occur until long after initial installation. This indicates increased impurity deposits or
mechanical distortion/wear would be the cause for bearing current damage. With the many variables involved, a
simple, consistent test routine is not easy to set up. Possibilities include a logic chart based upon findings and
combinations of. A satisfactory logic chart may eventually be available.
Are there other methods or approaches that you have found to be useful?

Experience is that shaft voltages, bearing contact and impurities in the oil create conditions leading to bearing/ seal
and gear currents. Sustained current in bearings, seals etc. often come from electromagnetic asymmetries in electrical
machines or from high residual magnetism. Damage is usually rapid and severe and, in absence of a shaft-voltage
current monitor, first detection is an increase in vibration and temperature.
2005. Your inquiry is well timed since I am currently composing a presentation for EPRI for delivery at the LEMUG
session in New Haven, CT, August 15-17,

”Safeguarding Machinery Worldwide “


www.gaussbusters.com

Das könnte Ihnen auch gefallen