TEST REPORT FOR TRANSFORMER

DIFFERENTIAL
PROTECTION RELAY 7UT633

Power Transmission
Distribution
SUB STATION-400/220KV
GETCO KOSAMBA S/S

CUSTOMER: SIEMENS

PTD/7UT633

Page 1 of 7

1. RELAY DETAILS:
Make

: Siemens

Relay Type

: 7UT633

Panel Ref

: 218

MLFB

: 7UT63316EB921BB0/0S

Relay Sl.No

Rated current

: 1A

Aux Supply

: 220V DC

2. TRANSFORMER DETAILS:
Power

: 100MVA

HV Voltage

: 220KV

LV Voltage

: 66KV

HV Current

: 262.43A

LV Current

: 874.79A

HV CT Ratio

: 300/1A

LV CT Ratio

: 1200/1A

Vector Group

:Yyn0

Tested by M/s Siemens


Mr.

M/S SIEMENS
Mr.

WITNESSED BY M/S GETCO


Mr.

TEST REPORT FOR TRANSFORMER


DIFFERENTIAL
PROTECTION RELAY 7UT633

Power Transmission
Distribution
SUB STATION-400/220KV
GETCO KOSAMBA S/S

PTD/7UT633

Page 2 of 7

CUSTOMER: SIEMENS

2. MECHANICAL CHECKS AND VISUAL INSPECTION.


ITEM

DISCRIPTION

CHECKED

1.

Inspect for physical damage / defects

Yes

------

2.

Verify connections as per approved drawings

Yes

------

3.

Check of relay grounding.

Yes

------

4.

Leds operations Checked

Yes

------

5.

Date and Time set in the relay

Yes

------

6.

Input / Output Checked

Yes

------

7.

Disturbance Recorder Checked for all faults

Yes

------

3. SECONDARY INJECTION TEST:


Measurement Check
Applied Current (A)

Phase Ref.

Measured Current in Relay

HV

LV-1

HV (A)

LV(A)

R-N

1.000

1.00180

300

1197

Y-N

1.00240

1.0060

300

1200

B-N

1.00120

1.00300

299

1200

4. STABILITY TEST: Apply full load current on HV and LV side with balance angles

Tested by M/s Siemens


Mr.

M/S SIEMENS
Mr.

WITNESSED BY M/S GETCO


Mr.

TEST REPORT FOR TRANSFORMER


DIFFERENTIAL
PROTECTION RELAY 7UT633

Power Transmission
Distribution
SUB STATION-400/220KV
GETCO KOSAMBA S/S

HV

Page 3 of 7

CUSTOMER: SIEMENS

Applied Current (A)

Phase
Ref.

PTD/7UT633

Measured from relay display

LV

I diff

I rest.

0.8740

0.728180

0.00

1.98

0.874240

0.72860

0.01

2.00

0.874120

0.728300

0.00

1.99

Remarks

NO TRIP

5. SENSITIVITY TEST:
Apply full load current on HV and LV side with same angles
Applied Current (A)

Phase Ref.

HV

Measured from relay display

LV

I diff

I rest.

0.8740

0.728210

2.00

2.02

0.874240

0.728270

2.00

2.01

0.874120

0.728150

2.01

2.03

Remarks

TRIP

6. PICK UP TEST: Id>0.2


Side 1(HV)
Applying Current only on side 1(HV)
Applied Current (A)

Phase Ref.

Pick value(A)

Trip value(A)

0.223

0.263

0.219

0.261

0.220

0.262

RYB

0.141

0.174

Side 2(LV)

Tested by M/s Siemens


Mr.

M/S SIEMENS
Mr.

WITNESSED BY M/S GETCO


Mr.

TEST REPORT FOR TRANSFORMER


DIFFERENTIAL
PROTECTION RELAY 7UT633

Power Transmission
Distribution
SUB STATION-400/220KV
GETCO KOSAMBA S/S

CUSTOMER: SIEMENS

PTD/7UT633

Page 4 of 7

Applying current only on side2(LV)


Pick up Test
Applied Current (A)

Phase Ref.

Pick value(A)

Trip value(A)

0.182

0.217

0.181

0.218

0.180

0.218

RYB

0.123

0.145

Formula:
1ph trip=(full load current/CT ratio)*Id set value*1.5
1ph pickup=80% of 1ph trip value
3ph trip= (Full load current/CT ratio)*Id set value.
3ph pick up=80% of 3ph trip value

7. SLOPE CHARACTERISTICS
SLOPE-1:30%

Deccreasing LV side Current

Tested by M/s Siemens


Mr.

M/S SIEMENS
Mr.

WITNESSED BY M/S GETCO


Mr.

TEST REPORT FOR TRANSFORMER


DIFFERENTIAL
PROTECTION RELAY 7UT633

Power Transmission
Distribution
SUB STATION-400/220KV
GETCO KOSAMBA S/S

CUSTOMER: SIEMENS

Applied Current (A)

Measured From relay


display (A)

Phase Ref.
HV

LV

I diff

I rest.

R-N

0.8070

0.364180

0.33

1.34

Y-N

0.807240

0.36460

0.33

1.34

B-N

0.807120

0.364300

0.33

1.34

PTD/7UT633

Page 5 of 7

%Slope

30.05%

Slope 1= (I diff)/ (I rest-base point 1)

SLOPE-2: 70%

Increasing LV side Current


Phase Ref.

Applied Current (A)@ Trip

Measured From relay display (A)

HV

LV

I diff

I rest.

R-N

7.1680

1.456180

6.20

10.20

Y-N

7.168240

1.45660

6.20

10.20

B-N

7.168120

1.456300

6.20

10.20

%Slope

70.21%

Slope=(Idiff/(I rest-Base point 2)

8. HARMONICS BLOCKING CHECK


2nd Harmonics
Parallel 50HZ and 100HZ above current on HV side, then reduce 100HZ current below set value.
Below set value -

Trip

Above set value -

Blocked

Tested by M/s Siemens


Mr.

M/S SIEMENS
Mr.

WITNESSED BY M/S GETCO


Mr.

TEST REPORT FOR TRANSFORMER


DIFFERENTIAL
PROTECTION RELAY 7UT633

Power Transmission
Distribution
SUB STATION-400/220KV
GETCO KOSAMBA S/S

Page 6 of 7

CUSTOMER: SIEMENS

Injected Current on HV (A)

PTD/7UT633

50HZ Source

100HZ Source

100HZ Current (A)


@Trip

R-N

10

1180

0.143

15

14

Y-N

1240

160

0.143

15

14

B-N

1120

1300

0.143

15

13

Phase Ref.

Set %

Operated %

5th Harmonics
Parallel 50HZ and 250HZ above current on HV side, then reduce 250HZ current below set value
Below set value -

Trip

Above set value -

Blocked
Injected Current on HV(A)

50HZ Source

250HZ Source

250HZ Current(A)
@Trip

R-N

10

1180

0.242

25

24

Y-N

1240

160

0.243

25

24

B-N

1120

1300

0.243

25

24

Phase Ref.

Set %

Operated %

10. LBB
Settings: 0.4A, T-1 0sec, T-2 0.2sec
Phase ref
Injected current in Amps
R
0.4 A

Tested by M/s Siemens


Mr.

M/S SIEMENS
Mr.

Optd time in sec(T-1)


0.04

Optd time in sec(T-2)


0.233

WITNESSED BY M/S GETCO


Mr.

TEST REPORT FOR TRANSFORMER


DIFFERENTIAL
PROTECTION RELAY 7UT633

Power Transmission
Distribution
SUB STATION-400/220KV
GETCO KOSAMBA S/S

CUSTOMER: SIEMENS

PTD/7UT633

Page 7 of 7

0.4 A

0.03

0.232

0.4 A

0.03

0.233

RYB

0.4 A

0.03

0.231

REMARKS:
Relay found healthy on all aspects

Tested by M/s Siemens


Mr.

M/S SIEMENS
Mr.

WITNESSED BY M/S GETCO


Mr.