Sie sind auf Seite 1von 9

Tue Jan 08 2013 11:36:45

Settings (Enabled Features)

PAGE 1

UNIT 1 TG.489
C:\USERS\ADMIN\DESKTOP\
DEVICE DEFINITION
ORDER CODE: 489-P1-HI-A20-T
VERSION: 4.0X
SERIAL NUMBER: B3211623
DESCRIPTION: (NONE)
TEXT COLOR
SR489 SETUP
PREFERENCES
Default Message Cycle Time
Default Message Timeout
Parameter Averages Calc. Period
Temperature Display Units
Waveform Trigger Position
Waveform Memory Buffer

2.0 s
300 s
15 min
Celsius
25 %
8 x 28 Cycles

MESSAGE SCRATCHPAD
First Scratchpad Message
Second Scratchpad Message
Third Scratchpad Message
Fourth Scratchpad Message
Fifth Scratchpad Message

2x2.5MW MASLI SMAL HYDRO PROJECT


Text 2
Text 3
Text 4
GE MULTILIN 489 Generator Relay

COMMUNICATION
Ethernet IP Address
Ethernet Subnet Mask
Slave Address
Computer RS485 Baud Rate
Auxiliary RS485 Baud Rate

1. 1. 1. 1
255.255.252. 0
254
9600 baud
9600 baud

SYSTEM SETUP
CURRENT SENSING
Phase CT Primary
Ground CT
Ground CT Ratio

750 A
1 A Secondary
750 :1

VOLTAGE SENSING
VT Connection Type
Transformer Ratio
Neutral Voltage Connection

Wye
30.00 :1
No

GEN. PARAMETERS
Generator Rated MVA
Generator Rated Power Factor
Generator Voltage Phase-Phase
Generator Nominal Frequency
Generator Phase Sequence

3.125 MVA
0.80
3300 V
50 Hz
ABC

SERIAL START-STOP
Serial Start/Stop Initiation

Off

DIGITAL INPUTS
BREAKER STATUS
Breaker Status

Breaker Auxiliary a

GENERAL PURPOSE
GENERAL A
Assign Digital Input (A)
Input Name (A)
Asserted Digital Input State (A)
Block Input From Online (A)
General Input A Control
Pulsed Control Relay Dwell Time (A)
Control Relay A
General Input A Control Events
General Input A Alarm
Alarm Relays A
General Input A Alarm Delay
General Input A Alarm Events
General Input A Trip
Trip Relays A
General Input A Trip Delay

Input 1
Input A
Closed
0s
Off
0.0 s
No Relays
Off
Off
Relay 5
5.0 s
Off
Unlatched
Relay 1
5.0 s

DUAL SETPOINTS
Active Setpoint Group(Dual Setpoints)
Edit Setpoint Group(Dual Setpoints)

Group 1
Group 1

OUTPUT RELAYS

Tue Jan 08 2013 11:36:45

Settings (Enabled Features)

PAGE 2

UNIT 1 TG.489
C:\USERS\ADMIN\DESKTOP\
DEVICE DEFINITION
ORDER CODE: 489-P1-HI-A20-T
VERSION: 4.0X
SERIAL NUMBER: B3211623
DESCRIPTION: (NONE)
TEXT COLOR
1 TRIP
R1 Trip

All Resets

2 AUXILIARY
R2 Auxiliary

All Resets

3 AUXILIARY
R3 Auxiliary

All Resets

4 AUXILIARY
R4 Auxiliary

All Resets

5 ALARM
R5 Alarm

All Resets

6 SERVICE
R6 Service

All Resets

MONITORING
TRIP COUNTER
Trip Counter Alarm

Off

BREAKER FAILURE
Breaker Failure Alarm

Off

CURRENT DEMAND
Current Demand Period
Current Demand Alarm

15 min
Off

MW DEMAND
MW Demand Period
MW Demand Alarm

15 min
Off

MVAR DEMAND
Mvar Demand Period
Mvar Demand Alarm

15 min
Off

MVA DEMAND
MVA Demand Period
MVA Demand Alarm

15 min
Off

PULSE OUTPUT
Positive kWh Pulse Output Relays
Positive kWh Pulse Output Interval
Positive kvarh Pulse Output Relays
Positive kvarh Pulse Output Interval
Negative kvarh Pulse Output Relays
Negative kvarh Pulse Output Interval
Pulse Width

No Relays
10 kwh
No Relays
10 kvarh
No Relays
10 kvarh
200 ms

TRIP COIL MONITOR


Trip Coil Monitor Alarm

Off

VT FUSE FAILURE
VT Fuse Failure Alarm

Off

GEN. RUN HOURS


Initial Gen. Running Hour
Gen. Running Hour Alarm

0h
Off

PROTECTION
CURRENT ELEMENTS[SETPOINT GROUP 1]
OVERCURRENT ALARM[SETPOINT GROUP 1]
Overcurrent Alarm

Off

OFFLINE O/C[SETPOINT GROUP 1]


Offline Overcurrent Trip

Off

INADVERTENT ENERG.[SETPOINT GROUP 1]


Inadvertent Energize Trip

Off

Tue Jan 08 2013 11:36:45

Settings (Enabled Features)

PAGE 3

UNIT 1 TG.489
C:\USERS\ADMIN\DESKTOP\
DEVICE DEFINITION
ORDER CODE: 489-P1-HI-A20-T
VERSION: 4.0X
SERIAL NUMBER: B3211623
DESCRIPTION: (NONE)
TEXT COLOR
PHASE OVERCURRENT[SETPOINT GROUP 1]
Phase Overcurrent Trip
Voltage Lower Limit

Off
10 %

NEGATIVE SEQUENCE[SETPOINT GROUP 1]


Negative Sequence Alarm
Negative Sequence Alarm Relays
Neg. Sequence Alarm Pickup
Negative Sequence Alarm Delay
Negative Sequence Alarm Events
Negative Sequence O/C Trip
Negative Sequence O/C Trip Relays
Neg. Sequence O/C Trip Pickup
Neg. Sequence O/C Constant k
Neg. Sequence O/C Max. Time
Neg. Sequence O/C Reset Rate

Latched
Relay 5
15 % FLA
15.0 s
On
Latched
Relays 1-2-3-4
20 % FLA
1
10 s
0.0 s

GROUND O/C[SETPOINT GROUP 1]


Ground O/C Alarm
Ground O/C Trip
Ground O/C Trip Relays
Ground O/C Trip Pickup
Ground O/C Curve Shape
Ground O/C Curve Multiplier
Ground O/C Curve Reset

Off
Latched
Relays 1-2-3-4
0.25 x CT
ANSI Normally Inv.
0.10
Instantaneous

PHASE DIFFERENTIAL[SETPOINT GROUP 1]


Phase Differential Trip

Off

GROUND DIRECTIONAL[SETPOINT GROUP 1]


Ground Directional MTA
Ground Directional Alarm
Ground Directional Trip

0
Off
Off

HIGH-SET PHASE O/C[SETPOINT GROUP 1]


High-Set Phase O/C Trip
High-Set Phase O/C Trip Relays
High-Set Phase O/C Pickup
High-Set Phase O/C Delay

Latched
Relay 1
5.00 x CT
0.00 s

VOLTAGE ELEMENTS[SETPOINT GROUP 1]


UNDERVOLTAGE[SETPOINT GROUP 1]
Undervoltage Alarm
Undervoltage Trip

Off
Off

OVERVOLTAGE[SETPOINT GROUP 1]
Overvoltage Alarm
Overvoltage Alarm Relay
Overvoltage Alarm Pickup
Overvoltage Alarm Delay
Overvoltage Alarm Events
Overvoltage Trip
Overvoltage Trip Relay
Overvoltage Trip Pickup
Overvoltage Trip Delay
Overvoltage Curve Reset Rate
Overvoltage Curve Element

Latched
Relay 5
1.10 x Rated
3.0 s
On
Latched
Relay 1
1.15 x Rated
3.0 s
0.0 s
Definite Time

VOLTS/HERTZ[SETPOINT GROUP 1]
Volts/Hertz Alarm
Volts/Hertz Alarm Relay
Volts/Hertz Alarm Pickup
Volts/Hertz Alarm Delay
Volts/Hertz Alarm Events
Volts/Hertz Trip
Volts/Hertz Trip Relay
Volts/Hertz Trip Pickup
Volts/Hertz Trip Delay
Volts/Hertz Trip Reset Rate
Volts/Hertz Trip Element

Latched
Relay 5
1.10 X Nominal
3.0 s
On
Latched
Relay 1
1.15 X Nominal
3.0 s
0.0
Curve #1

Tue Jan 08 2013 11:36:45

Settings (Enabled Features)

PAGE 4

UNIT 1 TG.489
C:\USERS\ADMIN\DESKTOP\
DEVICE DEFINITION
ORDER CODE: 489-P1-HI-A20-T
VERSION: 4.0X
SERIAL NUMBER: B3211623
DESCRIPTION: (NONE)
TEXT COLOR
PHASE REVERSAL[SETPOINT GROUP 1]
Phase Reversal Trip
Phase Reversal Trip Relay

Latched
Relays 1-2-3-4

UNDERFREQUENCY[SETPOINT GROUP 1]
Block Underfrequency from Online
Voltage Level Cutoff
Underfrequency Alarm
Underfrequency Alarm Relay
Underfrequency Alarm Level
Underfrequency Alarm Delay
Underfrequency Alarm Events
Underfrequency Trip
Underfrequency Trip Relay
Underfrequency Trip Level 1
Underfrequency Trip Delay 1
Underfrequency Trip Level 2
Underfrequency Trip Delay 2

1s
0.50 x Rated
Latched
Relay 5
47.50 Hz
3.0 s
On
Latched
Relay 1
47.00 Hz
3.0 s
46.00 Hz
1.0 s

OVERFREQUENCY[SETPOINT GROUP 1]
Block Overfrequency from Online
Voltage Level Cutoff (overfrequency)
Overfrequency Alarm
Overfrequency Alarm Relay
Overfrequency Alarm Level
Overfrequency Alarm Delay
Overfrequency Alarm Events
Overfrequency Trip
Overfrequency Trip Relay
Overfrequency Trip Level 1
Overfrequency Trip Delay1
Overfrequency Trip Level2
Overfrequency Trip Delay2

1s
0.70 x Rated
Latched
Relay 5
52.50 Hz
2.0 s
On
Latched
Relay 1
53.00 Hz
3.0 s
53.50 Hz
1.0 s

NEUTRAL O/V (FUND)[SETPOINT GROUP 1]


Neutral Overvoltage Alarm
Neutral Overvoltage Trip

Off
Off

NEUTRAL U/V (3RD)[SETPOINT GROUP 1]


Neutral Undervoltage Alarm
Neutral Undervoltage Trip

Off
Off

LOSS OF EXCITATION[SETPOINT GROUP 1]


Enable Voltage Supervision
Voltage Level
Circle 1 Trip
Circle 1 Trip Relay
Circle 1 Diameter
Circle 1 Offset
Circle 1 Trip Delay
Circle 2 Trip
Circle 2 Trip Relay
Circle 2 Diameter
Circle 2 Offset
Circle 2 Trip Delay

Yes
0.70 x Rated
Latched
Relay 1
18.0 Ohm sec
1.9 Ohm sec
3.0 s
Latched
Relay 1
22.8 Ohm sec
1.9 Ohm sec
3.0 s

DISTANCE[SETPOINT GROUP 1]
Fuse Failure Supervision
Zone 1 Trip
Zone 2 Trip

Off
Off
Off

POWER ELEMENTS[SETPOINT GROUP 1]


REACTIVE POWER ALARM[SETPOINT GROUP 1]
Block Mvar Element from Online
Reactive Power Alarm

1s
Off

REACTIVE POWER TRIP[SETPOINT GROUP 1]


Block Mvar Element from Online
Reactive Power Trip
Reactive Power Trip Relays
Positive Mvar Trip Level

1s
Latched
Relay 1
1.40 X Rated

Tue Jan 08 2013 11:36:45

Settings (Enabled Features)

PAGE 5

UNIT 1 TG.489
C:\USERS\ADMIN\DESKTOP\
DEVICE DEFINITION
ORDER CODE: 489-P1-HI-A20-T
VERSION: 4.0X
SERIAL NUMBER: B3211623
DESCRIPTION: (NONE)
TEXT COLOR
REACTIVE POWER TRIP[SETPOINT GROUP 1] (continued from last page)
Negative Mvar Trip Level
Positive Mvar Trip Delay
Negative Mvar Trip Delay

0.75 X Rated
10.0 s
1.0 s

REVERSE POWER ALARM[SETPOINT GROUP 1]


Block Reverse Power from Online
Reverse Power Alarm
Reverse Power Alarm Relays
Reverse Power Alarm Level
Reverse Power Alarm Delay
Reverse Power Alarm Events

10 s
Latched
Relay 5
0.05 x Rated MW
10.0 s
On

REVERSE POWER TRIP[SETPOINT GROUP 1]


Block Reverse Power from Online
Reverse Power Trip
Reverse Power Trip Relays
Reverse Power Trip Level
Reverse Power Trip Delay

10 s
Latched
Relay 1
0.05 x Rated MW
10.0 s

LOW FORWARD POWER ALARM[SETPOINT GROUP 1]


Block Low Fwd Power From Online
Low Forward Power Alarm

0s
Off

LOW FORWARD POWER TRIP[SETPOINT GROUP 1]


Block Low Fwd Power From Online
Low Forward Power Trip

0s
Off

RTD TEMPERATURE[SETPOINT GROUP 1]


RTD TYPES[SETPOINT GROUP 1]
Stator RTD Type
Bearing RTD Type
Ambient RTD Type
Other RTD Type

100 Ohm Platinum


100 Ohm Platinum
100 Ohm Platinum
100 Ohm Platinum

RTD #1[SETPOINT GROUP 1]


RTD#1 Application
RTD#1 Name
RTD#1 Alarm
RTD#1 Trip
RTD #2[SETPOINT GROUP 1]
RTD#2 Application
RTD#2 Name
RTD#2 Alarm
RTD#2 Trip
RTD #3[SETPOINT GROUP 1]
RTD#3 Application
RTD#3 Name
RTD#3 Alarm
RTD#3 Trip
RTD #4[SETPOINT GROUP 1]
RTD#4 Application
RTD#4 Name
RTD#4 Alarm
RTD#4 Trip
RTD #5[SETPOINT GROUP 1]
RTD#5 Application
RTD#5 Name
RTD#5 Alarm
RTD#5 Trip
RTD #6[SETPOINT GROUP 1]
RTD#6 Application
RTD#6 Name
RTD#6 Alarm
RTD#6 Trip

Stator
Off
Off
Stator
Off
Off
Stator
Off
Off
Stator
Off
Off
Stator
Off
Off
Stator
Off
Off

Tue Jan 08 2013 11:36:45

Settings (Enabled Features)

PAGE 6

UNIT 1 TG.489
C:\USERS\ADMIN\DESKTOP\
DEVICE DEFINITION
ORDER CODE: 489-P1-HI-A20-T
VERSION: 4.0X
SERIAL NUMBER: B3211623
DESCRIPTION: (NONE)
TEXT COLOR
RTD #7[SETPOINT GROUP 1]
RTD#7 Application
RTD#7 Name
RTD#7 Alarm
RTD#7 Trip
RTD #8[SETPOINT GROUP 1]
RTD#8 Application
RTD#8 Name
RTD#8 Alarm
RTD#8 Trip
RTD #9[SETPOINT GROUP 1]
RTD#9 Application
RTD#9 Name
RTD#9 Alarm
RTD#9 Trip
RTD #10[SETPOINT GROUP 1]
RTD#10 Application
RTD#10 Name
RTD#10 Alarm
RTD#10 Trip
RTD #11[SETPOINT GROUP 1]
RTD#11 Application
RTD#11 Name
RTD#11 Alarm
RTD#11 Trip
RTD #12[SETPOINT GROUP 1]
RTD#12 Application
RTD#12 Name
RTD#12 Alarm
RTD#12 Trip

Bearing
Off
Off
Bearing
Off
Off
Bearing
Off
Off
Bearing
Off
Off
Other
Off
Off
Ambient
Off
Off

RTD-ALARMS[SETPOINT GROUP 1]
Open RTD Sensor Alarm
RTD Short/Low Temp Alarm

Off
Off

THERMAL MODEL[SETPOINT GROUP 1]


THERMAL SETUP[SETPOINT GROUP 1]
Enable Thermal Model

No

OVERLOAD CURVES[SETPOINT GROUP 1]


Select Curve Style
Standard Overload Curve Number

Standard
4

CURRENT ELEMENTS[SETPOINT GROUP 2]


OVERCURRENT ALARM[SETPOINT GROUP 2]
Overcurrent Alarm

Off

OFFLINE O/C[SETPOINT GROUP 2]


Offline Overcurrent Trip

Off

INADVERTENT ENERG.[SETPOINT GROUP 2]


Inadvertent Energize Trip

Off

PHASE OVERCURRENT[SETPOINT GROUP 2]


Phase Overcurrent Trip

Off

NEGATIVE SEQUENCE[SETPOINT GROUP 2]


Negative Sequence Alarm
Negative Sequence O/C Trip

Off
Off

GROUND O/C[SETPOINT GROUP 2]


Ground O/C Alarm
Ground O/C Trip

Off
Off

PHASE DIFFERENTIAL[SETPOINT GROUP 2]


Phase Differential Trip

Off

Tue Jan 08 2013 11:36:45

Settings (Enabled Features)

PAGE 7

UNIT 1 TG.489
C:\USERS\ADMIN\DESKTOP\
DEVICE DEFINITION
ORDER CODE: 489-P1-HI-A20-T
VERSION: 4.0X
SERIAL NUMBER: B3211623
DESCRIPTION: (NONE)
TEXT COLOR
GROUND DIRECTIONAL[SETPOINT GROUP 2]
Ground Directional MTA
Ground Directional Alarm
Ground Directional Trip

0
Off
Off

HIGH-SET PHASE O/C[SETPOINT GROUP 2]


High-Set Phase O/C Trip

Off

VOLTAGE ELEMENTS[SETPOINT GROUP 2]


UNDERVOLTAGE[SETPOINT GROUP 2]
Undervoltage Alarm
Undervoltage Trip

Off
Off

OVERVOLTAGE[SETPOINT GROUP 2]
Overvoltage Alarm
Overvoltage Trip

Off
Off

VOLTS/HERTZ[SETPOINT GROUP 2]
Volts/Hertz Alarm
Volts/Hertz Trip

Off
Off

PHASE REVERSAL[SETPOINT GROUP 2]


Phase Reversal Trip

Off

UNDERFREQUENCY[SETPOINT GROUP 2]
Block Underfrequency from Online
Voltage Level Cutoff
Underfrequency Alarm
Underfrequency Trip

1s
0.50 x Rated
Off
Off

OVERFREQUENCY[SETPOINT GROUP 2]
Block Overfrequency from Online
Voltage Level Cutoff (overfrequency)
Overfrequency Alarm
Overfrequency Trip

1s
0.50 x Rated
Off
Off

NEUTRAL O/V (FUND)[SETPOINT GROUP 2]


Neutral Overvoltage Alarm
Neutral Overvoltage Trip

Off
Off

NEUTRAL U/V (3RD)[SETPOINT GROUP 2]


Neutral Undervoltage Alarm
Neutral Undervoltage Trip

Off
Off

LOSS OF EXCITATION[SETPOINT GROUP 2]


Enable Voltage Supervision
Circle 1 Trip
Circle 2 Trip

No
Off
Off

DISTANCE[SETPOINT GROUP 2]
Fuse Failure Supervision
Zone 1 Trip
Zone 2 Trip

Off
Off
Off

POWER ELEMENTS[SETPOINT GROUP 2]


REACTIVE POWER ALARM[SETPOINT GROUP 2]
Block Mvar Element from Online
Reactive Power Alarm

1s
Off

REACTIVE POWER TRIP[SETPOINT GROUP 2]


Block Mvar Element from Online
Reactive Power Trip

1s
Off

REVERSE POWER ALARM[SETPOINT GROUP 2]


Block Reverse Power from Online
Reverse Power Alarm

1s
Off

REVERSE POWER TRIP[SETPOINT GROUP 2]


Block Reverse Power from Online
Reverse Power Trip

1s
Off

Tue Jan 08 2013 11:36:45

Settings (Enabled Features)

PAGE 8

UNIT 1 TG.489
C:\USERS\ADMIN\DESKTOP\
DEVICE DEFINITION
ORDER CODE: 489-P1-HI-A20-T
VERSION: 4.0X
SERIAL NUMBER: B3211623
DESCRIPTION: (NONE)
TEXT COLOR
LOW FORWARD POWER ALARM[SETPOINT GROUP 2]
Block Low Fwd Power From Online
Low Forward Power Alarm

0s
Off

LOW FORWARD POWER TRIP[SETPOINT GROUP 2]


Block Low Fwd Power From Online
Low Forward Power Trip

0s
Off

RTD TEMPERATURE[SETPOINT GROUP 2]


RTD TYPES[SETPOINT GROUP 2]
Stator RTD Type
Bearing RTD Type
Ambient RTD Type
Other RTD Type

100 Ohm Platinum


100 Ohm Platinum
100 Ohm Platinum
100 Ohm Platinum

RTD #1[SETPOINT GROUP 2]


RTD#1 Application
RTD#1 Name
RTD#1 Alarm
RTD#1 Trip
RTD #2[SETPOINT GROUP 2]
RTD#2 Application
RTD#2 Name
RTD#2 Alarm
RTD#2 Trip
RTD #3[SETPOINT GROUP 2]
RTD#3 Application
RTD#3 Name
RTD#3 Alarm
RTD#3 Trip
RTD #4[SETPOINT GROUP 2]
RTD#4 Application
RTD#4 Name
RTD#4 Alarm
RTD#4 Trip
RTD #5[SETPOINT GROUP 2]
RTD#5 Application
RTD#5 Name
RTD#5 Alarm
RTD#5 Trip
RTD #6[SETPOINT GROUP 2]
RTD#6 Application
RTD#6 Name
RTD#6 Alarm
RTD#6 Trip
RTD #7[SETPOINT GROUP 2]
RTD#7 Application
RTD#7 Name
RTD#7 Alarm
RTD#7 Trip
RTD #8[SETPOINT GROUP 2]
RTD#8 Application
RTD#8 Name
RTD#8 Alarm
RTD#8 Trip
RTD #9[SETPOINT GROUP 2]
RTD#9 Application
RTD#9 Name
RTD#9 Alarm
RTD#9 Trip
RTD #10[SETPOINT GROUP 2]

Stator
Off
Off
Stator
Off
Off
Stator
Off
Off
Stator
Off
Off
Stator
Off
Off
Stator
Off
Off
Bearing
Off
Off
Bearing
Off
Off
Bearing
Off
Off

Tue Jan 08 2013 11:36:45

Settings (Enabled Features)

PAGE 9

UNIT 1 TG.489
C:\USERS\ADMIN\DESKTOP\
DEVICE DEFINITION
ORDER CODE: 489-P1-HI-A20-T
VERSION: 4.0X
SERIAL NUMBER: B3211623
DESCRIPTION: (NONE)
TEXT COLOR
RTD #10[SETPOINT GROUP 2] (continued from last page)
RTD#10 Application
RTD#10 Name
RTD#10 Alarm
RTD#10 Trip
RTD #11[SETPOINT GROUP 2]
RTD#11 Application
RTD#11 Name
RTD#11 Alarm
RTD#11 Trip
RTD #12[SETPOINT GROUP 2]
RTD#12 Application
RTD#12 Name
RTD#12 Alarm
RTD#12 Trip

Bearing
Off
Off
Other
Off
Off
Ambient
Off
Off

RTD-ALARMS[SETPOINT GROUP 2]
Open RTD Sensor Alarm
RTD Short/Low Temp Alarm

Off
Off

THERMAL MODEL[SETPOINT GROUP 2]


THERMAL SETUP[SETPOINT GROUP 2]
Enable Thermal Model

No

OVERLOAD CURVES[SETPOINT GROUP 2]


Select Curve Style
Standard Overload Curve Number

Standard
4