Short circuit Impedance Measurement Example:

The nameplate information for one particular three-winding transformer is as per below.

The impedances given are all on 60 MVA base. In this case tap no. 5 is the principal
tapping, so consider the impedances as HV-LV 19.32%, HV-TV 33.08% and LV-TV
9.93%.
The impedance quoted for each pair of windings is with a voltage applied to the first
winding, the second winding shorted, and all other windings open circuit. Refer IEC
60076.1:2005 Power Transformers - Part 1: General.