Beruflich Dokumente
Kultur Dokumente
2
U/L SE
480/277V
Bolt-On
3P4W
3000A
Cu
BUS MTL:
LABEL:
VOLTAGE:
Silver Plate
PLATE:
STYLE:
RATING: Fully
65000A
BUS BRACING (RMS SYM)
65000A
DEV. MIN. INT. RATING (RMS SYM)
ACCESS TO:
CLASS:
PHASE:
AMPERE:
2.5
3.12
CONDUIT SPACE
(TYPICAL ALL SECTIONS)
TC = TOP
BC = BOTTOM
.625 DIA
(TYP)
Switchboard/Device Information
Circuit No.
Device
Amps
Main
Gen
SS30
SS30
3000
3000
Poles
3
3
Nameplate
Notes
MAIN
GENERATOR
5
5
NOTES:
1. Shipping splits between each section, ship each section separately.
2. Main - Generator ground fault wired per SB70491GF SH1.
3. Standard 2-breaker ATO circuit wired per SB70491ATO SH1 - 11.
Use IRV2LR2 PLC program.
4. ATO circuit to include 1kVA UPS & Exercise Timer.
5. Main & Generator furnished with integral ground fault protection,
bell alarm w/ lockout, (8) auxiliary switches, 120V shunt trip, hidden "ON" button,
phase failure protection, padlock provision, limited access pushbutton cover,
120V electric operator, 120V remote close solenoid, LSIG programmer.
JOB NAME:
MADE BY:
PO
REL BY:
PO
P7.10
ISSUED:
09/25/07
P Oliver
CUSTOMER:
MATERIALES GENE
APARTADO 6-1892 EL DOR
00000
PLANT:
11/5/07
NO
DATE
MONTERREY
RELEASE
REVISIONS
MARK:
PO
INITIALS
178SB70491E
SHEET
1 of 2
ITEM