Sie sind auf Seite 1von 8

PHASE FAILURE RELAYS

These relays are suitable for monitoring incoming 3-


phase supply from Mains (Electricity distribution
line). Being independent of load, they can be used for
any HP/KW rating of load.
MODELS
VSP D1, VSP D2, VPG D1, USP D1
P1 PFS1, P1 PFS2, P2 PFS1
S2 VMR1, S2 VMR2, S2 VMR3, S2 VMR6, S2 VMR8
D1 HLS1, HLV D2, ALV D2, VMR D2, VST D1,
D1 VMR1, D2 VMR1, D2 VMR2,
S1 VMR7, F3 VSR4

FEATURES PROTECTIONS / FUNCTIONS


• Fixed/adjustable unbalance settings • Phase Failure (Phase Loss / Single
• Fixed/adjustable under- Phasing),
voltage/over-voltage settings
• Phase sequence reversal,
• Fixed/adjustable trip delays
• Voltage Unbalance,
• Built-in or external power supply
• Resetting Auto / Manual / Remote • Under Voltage,
• Output contacts: 1 CO or 2 CO • Over Voltage
• Choice of enclosures (DIN-Rail, • Dry Run
Flush, Plug-in)
• Models with Micro-Controller based
design
• 2 Line Alpha-Numerac LCD display
(For F3 VSR4 model) Ordering Instructions
• Serial Communication (RS 232) Port
(for F3 VSR4 model) ü Product Family Name
• Use of SMD Technology ü Model Name
• User-friendly LED indications ü System Supply Voltage
& Frequency
ü Aux. Supply / Control
supply voltage
09
P H A S E F A I L U R E R E L A Y S
VSP D1 VSP D2 P2 PFS1 S1 VMR7
Phase Failure Relay Phase Failure Relay Phase Failure Relay Phase Sequence Relay

Phase Failure, Phase Failure, Phase Failure, Phase Sequence,


Unbalance, Phase Unbalance, Unbalance, Auto Reset,
Sequence, Phase Sequence, Phase Sequence, 1 CO output relay
Auto Reset, Auto/Manual/Remote Auto Reset, Adjustable
Fixed Unbalance Setting, Reset, Adjustable Unbalance Trip Settings,
1 CO output Relay Unbalance setting, Adjustable Trip Delay,
2 CO output relay 2 CO output relay

Supply Voltage 100-120/220-240/380-440 V AC ±20% 100-120/220-240/380-440 V AC ±20% 110/ 220/ 380/ 415 VAC ± 10%, 380 – 440 VAC, ± 20%, 3PH-3 Wire
System 50 / 60 Hz 50 / 60 Hz 50/ 60 Hz
Note: Mention specific voltage
( Fixed/wide range ) in order Auxiliary 100-120/220-240/380-440 V AC ±20% 100-120/220-240/380-440V AC ±20% Bulit-In Built-In from 3-Phase
Output Contacts 1 CO 2 CO 2 CO 1 CO
Trip Setting (Volts)
Phase Sequence Yes Yes Yes Yes
Phase Unbalance 40 V ±6 V (fixed) 30 V to 70 V ±6 V (adjustable) 30 V to 70 V ± 6 V (adjustable) -

Trip Time Delay


On Phase Failure/Unbalance 3.5 sec. ±1.5 sec. 3.5 sec. ±1.5 sec. 1 - 5 secs. (variable) Instant
For level sensing N.A. N.A. N.A. N.A.
Resetting Mode Auto Auto / Manual / Remote Auto Auto Reset
Weight 320 gms. 400 gms. 250 gms. 90 gms. (Approx.)
Dimensions (mm)
Overall (L x W x D) 76 x 30.5 x 117.5 76 x 56.5 x 117.5 80 x 35 x 95 90 x 18 x 60 (Approx.)
Mounting (L x W) 68 centre to centre / 35 mm rail Mounting 67 x 46 / 35 mm rail Mounting 11 Pin Plug- In 35 mm rail Mounting

• Wherever not specified


Contact Rating :
5A @ 230 V AC Aux Aux
(resistive) Supply Supply
• * Available on request. RYB R B Y R B R Y B RYB R B Y R B R Y B RYB R Y R B Y RYB R B Y R Y B

3 Ph Phase Fail 3 Ph Phase Fail 3 Ph 3 Ph


Td : 2-5 Sec.
17

14

Unbalance
Td : 2-5 Sec. 3 9 >30 - 70 V Set Value
Td : 2-5 Sec. 1 11
16

13

13 14 11 10

1 4 11 8
18

15

13 15 11 12
16

13

R
L1
R
L1
R
L2 L2
Y Y
L3 L3
B
OFF
B
OFF
Y
ON ON
N/V N/V B
DOL STARTER DOL STARTER

1 2 3 4 5 6
1 2 3 VSP D2 P2 PFS1
VSP D1
AUX.
AUX. SUPPLY
SUPPLY
7 8 9 10 11 12
7 8 9
5 6 7
4 8
13 14 15 13 14 15 16 17 18
3 9
2 10
1 11

Bottom view

Relay contact position shown in 'Power off' condition

10
P H A S E F A I L U R E R E L A Y S
P1 PFS1 VPG D1 P1 PFS2 S2 VMR1
Phase Failure Relay +
Phase Failure Relay Low water level guard Phase Failure Relay Phase Failure Relay

C US

Phase Sequence, Single phasing, reverse phasing, Phase Failure, Unbalance, Microcontroller design,
Auto Reset, unbalanced supply, Auto reset, Phase Sequence, SMD Technology,
1 CO output relay 1 CO output contact Auto Reset, Phase Failure, Unbalance,
Suitable for any HP/kW rating fixed unbalance setting, Phase Sequence
submersible pumps 1 CO output relay Auto/Manual Reset,
Low water level guard for dry Adjustable Unbalance setting,
running protection 2 CO output relay

110/ 220/ 380/ 415 VAC ± 10%, 50 / 60 Hz 415VAC ± 20%, 50 Hz ± 3% 110 / 240 / 380 / 415 V AC ±10%, 50 / 60 Hz 100-120 / 220-240 / 380-440V AC, -25+20%, 48-63 Hz

Built-in Built-in Built-in Built In


1 CO 1 CO 1 CO 2 CO

Yes Yes Yes Yes


- 40 V ±6 V (fixed) 40V ± 6V (fixed) 4 % TO 20 % (Variable) ± 5% of full scale.

Instant 3.5 Sec ± 1.5 Sec 3.5 sec. ±1.5 sec. 4 Sec ± 1 Sec / RP-Instant
N.A. 3.5 Sec ± 1.5 Sec N.A. N.A.
Auto Reset Auto Reset Auto Auto/ Manual Reset (Selectable by Front Push Button)
90 gms. 300 gms. 175 gms. 100 gms (Approx.)

50 x 40 x 80 76 x 30.5 x 117.5 50 x40 x 80 90 X 35 X 60


8 Pin Plug - In 68 centre to centre / Panel Mounting & 8 - Pin Plug-in 35 mm Rail Mounting
35 mm rail Mounting

RYB R B Y R B R Y B
RYB R B Y R Y B RYB R B Y R B R Y B

3 Ph Phase Fail RYB R Y R B Y


Water Level
3 Ph /Reverse

3 Ph
Td : 3-5 Sec.
Td : 2-5 Sec.
7 8 1 3 Unbalance
8 11 >4 - 20 %
7 10

1 8 1 4 7 9 10 12

L1 R
R R
R Y
L2
Y B
Y L3 Y
B
B
B
N/V

P1 PFS1
OFF

4 5 ON

3 6 NO 4 5
1 2 3
8 7 3 6
2 7 VPG D1

1 8 2 7
NC PROD
Bottom view 1 8 7 8 9 1 8
13 14 15
WATER TANK
Bottom view

Relay contact position shown in 'Power off' condition


Relay Contact position shown in“Power off” Condition
Note: S2 Series - RoHS Product available on request. 11
CE marked VSP D1, VSP D2 available on request.
P H A S E F A I L U R E R E L A Y S
USP D1 S2 VMR2 HLV D2
Phase Failure Relay Phase Failure Relay Phase Failure with UV / OV Relay

C US

Phase Failure, Unbalance, Microcontroller design, Phase Failure, Unbalance,


Phase Sequence, Auto Reset, SMD Technology, Phase Sequence, under voltage,
Fixed Unbalance Setting, Phase Failure, Unbalance, Over Voltage, Manual / Remote
1 CO output relay Phase Sequence, under voltage, reset, Fixed Unbalance setting,
Over Voltage, Auto reset,
Adjustable UV/OV settings,
Fixed Unbalance setting,
2 CO output relay
Fixed UV/OV settings,
2 CO output relay

Supply Voltage
415 VAC ± 20%, 50 Hz ± 3% 100-110-120 / 220-230-240 / 380-415-440V AC -25+20%,
Note: Mention specific voltageSystem Selectable by Front Knob, 48-63 HZ 110 / 240 / 380 / 415 / 440 V AC ±20%, 50 / 60 Hz
( Fixed/wide range ) in order
Auxiliary Built In Built In (from 3 Phase) 110 V (Fixed) or (220-230-240) or (380-415-440) VAC
Output Contacts 1 CO 2 CO 2 CO
Trip Setting (Volts)
Phase Sequence Yes Yes Yes
Phase Unbalance 60 V± 6 V (fixed) 10% (Fixed) ± 10% 40 V ±6 V (fixed)
Under For 380-440V AC 80% to 95% (adjustable)
Voltage For 220-240V AC
For 100-120V AC
N.A ± 20% (Fixed)
Over For 380-440V AC 105% to 120% (adjustable)
Voltage For 220-240V AC
For 100-120V AC
Trip Time Delay
On Phase Failure 3.5 sec. ± 1.5 sec. 2 - 5 Sec. (Fixed) / RP-Instant 3.5 secs. ± 1.5 sec
On UV/OV Less than 2 secs. for OV & 2 - 5 secs for UV
Resetting Mode Auto Reset Auto Reset Manual / Remote
Weight 100 gms (Approx.) 100 gms (Approx.) 430 gms.
Dimensions (mm)
Overall (L x W x D) 76 x 30.5 x 117.5 90 X 35 X 60 76 x 56.5 x 117.5
Mounting (L x W) 68 centre to centre / 35 mm rail Mounting 35 mm Rail Mounting 67 x 46 / 35 mm rail Mounting

• Wherever not specified OV


OV
Contact Rating : RYB R Y R B Y RYB RYB RY R B Y
Aux
UV
Unbalance /
5A @ 230 V AC 3 Ph
Phase Fail
3 Ph Phase fail
UV
Supply
RYB R B RBY RYB
(resistive) Td : 2-5 Sec.
Td : 2-5 Sec.
Td : 2-5 Sec.
3 Ph Unbal./

• * CE marked products 1 2 7 8 10 11
Phase Fail
Td : 2-5 Sec.
available on request. 13 14 16 17

1 3 7 9 10 12 13 15 16 18

R
R
M
L L
Y O
A Y O
A R
L1
L
D D
B B Y
L2 O
MOTOR
A
L3 D
B

OFF ON
N/V
DOL STARTER

USP D1

1 2 3 4 5 6
HLV D2

AUX.
SUPPLY
7 8 9 10 11 12

13 14 1516 17 18

Relay contact position shown in ‘Power off' condition


Note: S2 Series - RoHS Product available on request.
CE marked HLV D2, ALV D2, VMR D2 available on request.
12
P H A S E F A I L U R E R E L A Y S
ALV D2 VMR D2 S2 VMR6
Phase Failure with UV / OV Relay Phase Failure with UV / OV Relay Phase Failure with UV / OV Relay

Phase Failure, Unbalance, Phase Failure, Unbalance, Phase Failure, Unbalance, Phase
Phase Sequence, under voltage, Phase Sequence, under voltage, Sequence,
Over Voltage, Auto Reset, Over Voltage, Auto Reset, Under Voltage, Over Voltage, Auto
Fixed Unbalance setting, Fixed Unbalance setting, Reset, Fixed Unbalance Settings,
Adjustable UV/OV settings, Adjustable UV/OV settings, Adjustable UV/ OV Settings, Neutral
2 CO output relay 2 CO output relay Fail, 2 CO output relay

415 V AC ± 20%
110 / 240 / 380 / 415 / 440 V AC ±20%, 50 / 60 Hz 110/220/230/240/380/415/440 V AC ±20%, 50/60 Hz
110 V (Fixed) or (220-230-240) or (380-415-440) VAC ±20% selectable 110/220/230/240/380/415/440 V AC ±20%, 50/60 Hz Built-In
2 CO 2 CO 2 CO

Yes Yes Yes


40 V ±6 V (fixed) 94 V ±6 V (fixed) 94 V ± 6 V ph- ph (fixed)
80% to 95% (adjustable) 80% to 95% (adjustable) 75% to 95% of 415 VAC

105% to 120% (adjustable) 105% to 120% (adjustable) 105% to 125% of 415 VAC

3.5 secs. ± 1.5 sec 3.5 secs. ± 1.5 sec 5 sec. ± 1 sec for UB/SP/UV/OV, Instant for RP,
Less than 2 secs. Less than 2 secs. Less than 2 secs. for NF.
Auto Reset Auto Reset Auto Reset
400 gms. 400 gms. 110 gms.

76x 56.5 x 117.5 76x 56.5 x 117.5 90 x 35 x 60


67 x 46 / 35 mm rail Mounting 67 x 46 / 35 mm rail Mounting 35 mm rail mounting

OV
OV OV RYBN RY RBYN RYBN
UV UV Unbalance /
Aux Aux UV
Supply Supply
3 Ph-N Phase fail

RYB R B RBY RYB RYB R B RBY RYB Td : 5 Sec.


T On Td : 5 Sec. T On
3 Ph Unbal./
Phase Fail
3 Ph Unbal./
Phase Fail 5 Sec. 5 Sec.
Td : 2-5 Sec. Td : 2-5 Sec. 7 8 10 11
13 14 16 17 13 14 16 17

13 15 16 18 13 15 16 18
7 9 10 12

R
L1 L1 L
R R
L L Y O
L2 O L2 A
R Y
L3
MOTOR
A
D
Y
L3
MOTOR
O
A B D
D
B B N

OFF ON OFF ON
N/V N/V OFF
N/V
DOL STARTER DOL STARTER ON

DOL STARTER

S2 VMR6

1 2 3 4 5 6 1 2 3 4 5 6
ALV D2
VMR D2
AUX. AUX.
SUPPLY SUPPLY
7 8 9 10 11 12 7 8 9 10 11 12

13 14 1516 17 18 13 14 1516 17 18

Relay contact position shown in 'Power off' condition

Note: Product available on request - P2 PFV1, P2 SMV1


13
P H A S E F A I L U R E R E L A Y S
S2 VMR8 D1 HL S1 VST D1
Phase Failure Relay Phase Failure with UV / OV Relay Phase Failure with Under Voltage

Phase Failure, Unbalance, Phase Failure, Unbalance, Phase Failure, Phase Sequence,
Phase Sequence, Phase Sequence, under voltage, Auto Reset,
Under Voltage, Over Voltage, under voltage, Over Voltage, Adjustable trip delay,
Auto Reset, Fixed Unbalance Auto reset, Fixed Unbalance Adjustable UV setting,
Settings, Fixed UV/ OV setting, Fixed UV/OV settings, 1 CO output relay
Settings, 2 CO output relay 2 CO output relay Selectable range of supply
voltage

Supply Voltage 100-110-120/220-230-240/380-415-440V AC+20,-25%,


System
Note: Mention specific voltage 415 V AC ± 20% 48-63 Hz 240 / 415 / 575 V AC 3 Phase (±15% selectable)
( Fixed/wide range ) in order
Auxiliary Built-In Built-in Selectable by Front Knob Built-in
Output Contacts 2 CO 2 CO 1 CO
Trip Setting (Volts)
Phase Sequence Yes Yes Yes
Phase Unbalance 40 V ± 4 V (10 % ± 10% of set value-fixed) 10% (Fixed) N.A.
Under For 380-440V AC 85% of 415 V AC (fixed) 75% of system supply (Fixed) 80% of V set
Voltage For 220-240V AC
For 100-120V AC

Over For 380-440V AC 110 % of 415 V AC (fixed) 120% of system supply (Fixed) N.A.
Voltage For 220-240V AC
For 100-120V AC

Trip Time Delay


On Phase Sequence 2 - 5 sec. fixed for UB/SP/UV 2-5 sec. UB/SP
On SP/UV/OV Instant for RP/OV Less than 2 secs. UV/OV, Instant RP 0.2 - 10 secs. (same for UV & SP)
Resetting Mode Auto Reset Auto Auto
Weight 150 gms. 200 gms. 300 gms.
Dimensions (mm)
Overall (L x W x D) 110 x 35 x 60 76 x 30.5 x 117.5 76 x 30.5 x 117.5
Mounting (L x W) Screw Mounting 68 centre to centre / 35 mm rail Mounting 68 centre to centre / 35 mm rail Mounting

• Wherever not specified OV


RYB RY R B Y
OV RYB RY R B Y
Contact Rating : RYB RY RYB
Unbalance /
RBY RYB
Unbalance / 3 Ph
Phase fail UV
UV
5A @ 230 V AC 3 Ph
UV
3 Ph Phase fail Phase fail
Td :0.2-10 Sec.
(resistive) T On Td : 3.5 Sec.
T On Td T On
180 2-5
3 1 6 4 Sec. Sec.
13 14 1 2 13 14

3 2 6 5 13 15 1 3 13 15

L1
R R L
L L
O L2 O
Y O Y
A A A
B D L3 D
D B

OFF
OFF ON
N/V
N/V
18 16 15 28 26 25
ON
DOL STARTER

1 2 3

S2 VMR8

VST D1

L3 L2 L1
D1 HLS1

7 8 9

13 14 15

Relay contact position shown in ‘Power off' condition

Note: S2 Series - RoHS Product available on request.


14
P H A S E F A I L U R E R E L A Y S
D1 VMR1 D2 VMR1 D2 VMR2
Phase Failure with UV / OV Relay Phase Failure with UV / OV (3Ø-3W) Phase Failure with UV / OV (3Ø-4W)

R R

C US C US

Suitable for 3 Ph-3W system, Suitable for 3 Ph-4W system,


Phase Failure, Unbalance, Microcontroller design, Microcontroller design,
Phase sequence, Under & Over Absolute values of UV/OV settings, Absolute values of UV/OV settings
voltage, Auto Reset, Phase Failure, Unbalance, Phase Phase Failure, Unbalance, Phase
fixed unbalance setting, Sequence, under voltage, Over Voltage, Sequence, under voltage, Over Voltage
Adjustable UV/OV settings, Auto/Manual reset, Adjustable settings Auto/Manual reset, Adjustable settings for
for Unbalance, UV/OV and trip delays, Unbalance, UV/OV and trip delays,
fixed trip delay,
2 CO output relay 2 CO output relay
2 CO output relay

100-120/220-240/380-440 VAC±20%, 3Ph-3Wire, 48-63 Hz 100-120 / 220-240 / 380-440V AC -25%+20%, 48-63 Hz 100-120 / 220-240 / 380-440V AC -25%+20%, 48-63 Hz
Built-in Built In (from 3 Phases) Built In (from 3 Phases)
2 CO 2 CO 2 CO

Yes Yes Yes


10% (fixed) 4 % - 20 % [Variable] 4 % - 20 % [Variable]
285-425V AC [Variable] 285-425V AC [Variable] 165-245V AC [Variable]
165-225V AC [Variable] 165-225V AC [Variable] 95-135V AC [Variable]
75-115V AC [Variable] 75-115V AC [Variable] 45-65V AC [Variable]

400-520V AC [Variable] 400-520V AC [Variable] 230-310V AC [Variable]


230-290V AC [Variable] 230-290V AC [Variable] 130-170V AC [Variable]
105-140V AC [Variable] 105-145V AC [Variable] 60-80V AC [Variable]

3.5 secs ± 1.5 sec. Instant Instant


3.5 secs ± 1.5 sec. 1 To 10 Sec [Variable) 1 To 10 Sec [Variable)
Auto Auto/ Manual Reset (External NC Push Buttons) Auto/ External Manual Reset (External NC Push Buttons)
430 gms. 300 gms. 300 gms.

76 x 30.5 x 117.5 76 X 56.5 X 117.5 76 X 56.5 X 117.5


68 centre to centre / 35 mm rail Mounting 67 x 46 / 35 mm rail Mounting 67 x 46 / 35 mm rail Mounting

OV RYB RY R B Y OV
RYB RY R B Y
RYB RY R B Y OV
Unbalance / Unbalance / UV
3 Ph Phase fail
UV
Unbalance / UV 3 Ph N Phase fail

Td : 3.5 Sec.
3 Ph Phase fail
Td : 1-10 Sec.
Td : 1-10 Sec. Td : 1-10 Sec.
Td : 1-10 Sec.
13 14 1 2 13 14 16 17
13 14 16 17

13 15 1 3
13 15 16 18 13 15 16 18

L R L R
O O L
A Y A Y O
D D
A
B B D
N

DOL STARTER
MANUAL MANUAL
RESET RESET
PB PB

D2 VMR 1 D2 VMR 2

Relay contact position shown in 'Power off' condition

Note: Product available on request - P2 PFV1, P2 SMV1


15
P H A S E F A I L U R E R E L A Y S
S2 VMR3 F3 VSR4
Phase Failure with UV / OV Relay Voltage Scanner [3 Ph – 3 W/ 4 W]

C US

Microcontroller design,
SMD Technology,
3-Phase 3-Wire or 3-Phase 4-Wire voltage
Absolute values of UV/OV settings,
monitoring & display, Phase Failure, Unbalance,
Phase Failure, Unbalance, Phase
Phase Sequence, under voltage, Over Voltage,
Sequence, under voltage, Over Voltage
Auto / Manual Reset, Adjustable unbalance trip
Auto/Manual reset, Adjustable settings
setting, Adjustable under/over voltage settings,
for Unbalance, UV/OV and trip delays,
adjustable trip delay, RS232 communication port,
2 CO output relay
2 CO output relay, True RMS Values

Supply Voltage
System
Note: Mention specific voltage 100-120 / 220-240 / 380-440V AC -25%+20%, 48-63 Hz 415 V AC + 20%,-30% (3 Ph-3 W or 3 Ph-4 W selectable)
( Fixed/wide range ) in orderAuxiliary Built In (from 3 Phases) 90-270 V AC/DC, 50 Hz/ (60 Hz) ± 3%
Output Contacts 2 CO 2 CO & RS 232 (optional)
Trip Setting (Volts)
Phase Sequence Yes Yes
Phase Unbalance 4 % - 20 % [Variable] 1 - 20 % (Adjustable)
Under For 380-440V AC 285-425V AC [Variable] 1 - 80V below nominal voltage (for 3 Ph. 3 W)
Voltage For 220-240V AC 165-225V AC [Variable] 1 - 50V below nominal voltage (for 3 Ph. 4 W)
For 100-120V AC 75-115V AC [Variable]

Over For 380-440V AC 400-520V AC [Variable] 1 - 60V above nominal voltage (for 3 Ph. 3 W)
Voltage For 220-240V AC 230-290V AC [Variable] 1 - 25V above nominal voltage (for 3 Ph. 4 W)
For 100-120V AC 105-145V AC [Variable]

Trip Time Delay


On Phase Sequence Instant 3.5 ± 1.5 sec. / RP-Instant
On SP/UV/OV 1 To 10 Sec [Variable) 1 - 59 secs. or 1-5 mins Selectable
Resetting Mode Auto/ Manual Reset [Selectable] Auto/ Manual Reset [Selectable]
Weight 110 gms (Approx.) 800 gms
Dimensions (mm)
Overall (L x W x D) 90 X 35 X 60 96 x 96 x 130
Mounting (L x W) 35 mm Rail Mounting 92 x 92 mm

• Wherever not specified RYB RY R B Y OV


RESET RESET
S.P.
RESET
UB > SET
RESET
R.P.
RESET

Contact Rating : Unbalance / UV


OV SET
OV HYST.

5A @ 230 V AC 3 Ph Phase fail LINE B Y R


UV HYST.

(resistive) Td : 1-10 Sec. UV SET


Td : 1-10 Sec.

7 8 10 11 T2 T2 UV T2
OV UV UB/SP UB/SP UB/SP

LED
T1

9 12 RELAY
7 10
C - NO
T1 = POWER ON DELAY T2 = TRIP DELAY

R L
O
Y A
D
B

R Y B N +VE VE
AUX. SUPPLY
SYSTEM SUPPLY 90-270 VAC/DC

RS232

C1 NO1 NC1 C2 NO2 NC2

Relay position shown in 'Power off' condition

Note: S2 Series - RoHS Product available on request.


16