Sie sind auf Seite 1von 4

Nama : Febry Ardianto

NRP : 2208100178

Tugas ANALISA SISTEM TENAGA


SIMULASI MENGGUNAKAN MATLAB
HUBUNG SINGKAT 3 FASA PADA BUS 4
>>
%Problem :
SHORT CIRCUIT
%
The Fault Current, bus voltage and line current is use
%
the lgfault, llfault, and dlgfault functions
% Impedansi Urutan
zdata1 = [ 0 4 0.0000 0.20000
0 5 0.0000 0.20000
1 2 0.0000 0.10000
1 3 0.0000 0.10000
1 4 0.0000 0.05000
2 3 0.0000 0.10000
2 5 0.0000 0.05000];
zdata0 = [ 0
0
0
1
1
1
2
2

2
4
5
2
3
4
3
5

0.0000 0.05000
0.0000 0.14000
0.0000 0.14000
0.0000 0.30000
0.0000 0.30000
0.0000 0.05000
0.0000 0.30000
999999 9999999];

% Jenis Gangguan
zdata2 = zdata1
Zbus0 = zbuild(zdata0)
Zbus1 = zbuild(zdata1)
Zbus2 = Zbus1;
disp('(a) Symmetrical three-phase fault')
symfault(zdata1, Zbus1)
zdata2 =
0
0
1.0000
1.0000
1.0000
2.0000
2.0000

4.0000
5.0000
2.0000
3.0000
4.0000
3.0000
5.0000

0
0
0
0
0
0
0

0.2000
0.2000
0.1000
0.1000
0.0500
0.1000
0.0500

Zbus0 =
0.0000 + 0.1080i 0.0000 + 0.0216i 0.0000 + 0.0648i 0.0000 + 0.0795i -0.0000 + 0.0000i
0.0000 + 0.0216i 0.0000 + 0.0443i 0.0000 + 0.0330i 0.0000 + 0.0159i -0.0000 + 0.0000i
0.0000 + 0.0648i 0.0000 + 0.0330i 0.0000 + 0.1989i 0.0000 + 0.0477i -0.0000 + 0.0000i
0.0000 + 0.0795i 0.0000 + 0.0159i 0.0000 + 0.0477i 0.0000 + 0.0955i -0.0000 + 0.0000i
-0.0000 + 0.0000i -0.0000 + 0.0000i -0.0000 + 0.0000i -0.0000 + 0.0000i 0.0000 + 0.1400i
Zbus1 =
0 + 0.1397i
0 + 0.1103i
0 + 0.1250i
0 + 0.1118i
0 + 0.0882i

0 + 0.1103i
0 + 0.1397i
0 + 0.1250i
0 + 0.0882i
0 + 0.1118i

0 + 0.1250i
0 + 0.1250i
0 + 0.1750i
0 + 0.1000i
0 + 0.1000i

0 + 0.1118i
0 + 0.0882i
0 + 0.1000i
0 + 0.1294i
0 + 0.0706i

0 + 0.0882i
0 + 0.1118i
0 + 0.1000i
0 + 0.0706i
0 + 0.1294i

(a) Symmetrical three-phase fault


Warning: See help sprintf for valid escape sequences.
> In symfault at 38
Enter Faulted Bus No. -> 4
Enter Fault Impedance Zf = R + j*X in complex form (for bolted fault enter 0). Zf = 0
Balanced three-phase fault at bus No. 4
Total fault current = 7.7273 per unit
Bus Voltages during fault in per unit
Bus
No.
1
2
3
4
5

Voltage
Magnitude
0.1364
0.3182
0.2273
0.0000
0.4545

Angle
degrees
0.0000
0.0000
0.0000
0.0000
0.0000

Line currents for fault at bus No. 4


From
To
Current Angle
Bus
Bus Magnitude degrees
1
4
2.7273 -90.0000
2
1
1.8182 -90.0000
2
3
0.9091 -90.0000
3
1
0.9091 -90.0000
G
4
5.0000 -90.0000
4
F
7.7273 -90.0000
G
5
2.7273 -90.0000
5
2
2.7273 -90.0000
Another fault location? Enter 'y' or 'n' within single quote ->

HUBUNG SINGKAT 1 FASA PADA BUS 4


>>
%Problem :
SHORT CIRCUIT
%
The Fault Current, bus voltage and line current is use
%
the lgfault, llfault, and dlgfault functions
% Impedansi Urutan
zdata1 = [ 0 4 0.0000 0.20000
0 5 0.0000 0.20000
1 2 0.0000 0.10000
1 3 0.0000 0.10000
1 4 0.0000 0.05000
2 3 0.0000 0.10000
2 5 0.0000 0.05000];
zdata0 = [ 0
0
0
1
1
1
2
2

2
4
5
2
3
4
3
5

0.0000 0.05000
0.0000 0.14000
0.0000 0.14000
0.0000 0.30000
0.0000 0.30000
0.0000 0.05000
0.0000 0.30000
999999 9999999];

% Jenis Gangguan
zdata2 = zdata1
Zbus0 = zbuild(zdata0)
Zbus1 = zbuild(zdata1)
Zbus2 = Zbus1;
disp('(b) Line-to-ground fault' )
lgfault(zdata0, Zbus0, zdata1, Zbus1, zdata2, Zbus2)
zdata2 =
0
0
1.0000
1.0000
1.0000
2.0000
2.0000

4.0000
5.0000
2.0000
3.0000
4.0000
3.0000
5.0000

0
0
0
0
0
0
0

0.2000
0.2000
0.1000
0.1000
0.0500
0.1000
0.0500

Zbus0 =
0.0000 + 0.1080i 0.0000 + 0.0216i 0.0000 + 0.0648i 0.0000 + 0.0795i -0.0000 + 0.0000i
0.0000 + 0.0216i 0.0000 + 0.0443i 0.0000 + 0.0330i 0.0000 + 0.0159i -0.0000 + 0.0000i
0.0000 + 0.0648i 0.0000 + 0.0330i 0.0000 + 0.1989i 0.0000 + 0.0477i -0.0000 + 0.0000i
0.0000 + 0.0795i 0.0000 + 0.0159i 0.0000 + 0.0477i 0.0000 + 0.0955i -0.0000 + 0.0000i
-0.0000 + 0.0000i -0.0000 + 0.0000i -0.0000 + 0.0000i -0.0000 + 0.0000i 0.0000 + 0.1400i

Zbus1 =
0 + 0.1397i
0 + 0.1103i
0 + 0.1250i
0 + 0.1118i
0 + 0.0882i

0 + 0.1103i
0 + 0.1397i
0 + 0.1250i
0 + 0.0882i
0 + 0.1118i

0 + 0.1250i
0 + 0.1250i
0 + 0.1750i
0 + 0.1000i
0 + 0.1000i

0 + 0.1118i
0 + 0.0882i
0 + 0.1000i
0 + 0.1294i
0 + 0.0706i

0 + 0.0882i
0 + 0.1118i
0 + 0.1000i
0 + 0.0706i
0 + 0.1294i

(b) Line-to-ground fault


Line-to-ground fault analysis
Enter Faulted Bus No. -> 4
Enter Fault Impedance Zf = R + j*X in complex form (for bolted fault enter 0). Zf = 0
Single line to-ground fault at bus No. 4
Total fault current = 8.4679 per unit
Bus Voltages during the fault in per unit
Bus
No.
1
2
3
4
5

-------Voltage Magnitude------Phase a
Phase b
Phase c
0.1445
0.9578
0.9578
0.4570
0.9152
0.9152
0.3008
0.9350
0.9350
0.0000
0.9557
0.9557
0.6015
0.9168
0.9168

Line currents for fault at bus No. 4


From To -----Line Current Magnitude---Bus Bus Phase a Phase b
Phase c
1
4
2.8906 0.0981
0.0981
2
1
1.9270 0.0654
0.0654
2
3
0.9635 0.0327
0.0327
3
1
0.9635 0.0327
0.0327
4
F
8.4679 0.0000
0.0000
5
2
1.9925 0.9962
0.9962
Another fault location? Enter 'y' or 'n' within single quote ->