Sie sind auf Seite 1von 4

TIGERFLOW Booster Sizing Worksheet

06/24/2015

Job Name:
Customer:

I. Pressure Required:
A. Pressure required at highest fixture

PSI

(Estimate 30-40 PSIG +/-, or specifed requirement)

B. Static head

(building height =

C. Piping and system friction loss


D. Required system processing

ft)

0.0

PSI

(10% of static head)

0.0

PSI

(A + B + C)

0.0

PSI

E. Subtract minimum suction pressure at pump station

PSI

(Minimum suction pressure at street minus pressure


drop through backflow prevention and / or water meter)

F. Subtotal

0.0

PSI

G. Internal booster station loss

5.0

PSI

H. Total pump boost (differential) pressure required (F + G)

5.0

PSI

I. Convert pump boost PSI to TDH

11.6

ft, TDH)

(D + E)

(PSI x 2.31 =

II. Fixture Unit Table:

Fixture
Bathroom group flush valve
Bathroom group flush tank
Lavatory
Urinal - flush valve
Water closet - flush valve
Water closet - flush valve
Bathtub - public
Bathtub - private
Bathtub - immersion
Shower (standard)
Sink - kitchen
Sink - kitchen
Sink - services
Garbage disposal
Garbage disposal
Dishwasher
Dishwasher
Washing machine
Washing machine
Ice machine
Steam tables
Hose connection - 3/4"

TIGERFLOW Systems, Inc., Copyright 2007

Use

Fixture
Units

Public
Private
Public
Public
Public
Private
Public
Private
Public
Public
Public
Private
Public
Public
Private
Public
Private
Public
Private
Public
Public
Public

8
6
2
5
10
5
4
2
20
4
4
2
3
3
2
6
2
4
2
1
1
6

No. of
Fixtures

Total
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

Sheet 1 of 4

TIGERFLOW Booster Sizing Worksheet

06/24/2015

Total Fixture Units

Typical System GPM


Fixture
Units
0
100
300
600
900
1200
1500
1650
1750
2000
2200
2500
3000
4000
5000
6000
7000
8000
10000

Apts /
Office
0.0
70
80
100
120
140
150
170
180
190
210
220
250
300
350
400
450
500
550

Hotel /
Motel
0.0
80
90
120
125
150
170
180
190
200
220
240
275
350
400
450
500
550
600

Hospital /
School /
Prison
100.0
100
100
130
140
160
190
200
210
220
230
260
300
375
450
500
550
600
650

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

Apts /
Office
0.0

Hotel /
Motel
0.0

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

IV. Total System Demand (GPM):

A. System demand

(Total Chart III)

Hospital /
School /
Prison
100.0 GPM

B. Special duty demands

GPM

(Cooling tower makeup, etc.)

C. Total systems demand

GPM

Duplex: (0 - 300 GPM)


11.6 ft, head
% of System GPM

50-50
33-67
65-65
100-100

Pump #1
GPM
HP
0.0
0.00
0.0
0.00
0.0
0.00
0.0
0.00

Pump #2
GPM
HP
0.0
0.00
0.0
0.00
0.0
0.00
0.0
0.00

Triplex: (301 - 3000+ GPM)


11.6 ft, head
% of System GPM

10-50-50

Pump #1
GPM
HP
0.0
0.00

TIGERFLOW Systems, Inc., Copyright 2007

Pump #2
GPM
HP
0.0
0.00

Pump #3
GPM
HP
0.0
0.00

Sheet 2 of 4

TIGERFLOW Booster Sizing Worksheet


20-40-40
33-33-33
50-50-50

0.0
0.0
0.0

0.00
0.00
0.00

0.0
0.0
0.0

06/24/2015

0.00
0.00
0.00

0.0
0.0
0.0

0.00
0.00
0.00

VI. Maximum Flow Rate (GPM) per Header Size:


Size
Flow
(inches) (GPM)
3
4
6
8
10

300
600
1000
1800
2800

Minimum header size for this job =

3 Inch

TIGERFLOW Systems, Inc.


4034 Mint Way
Dallas, Texas 75237
214-337-8780

TIGERFLOW Systems, Inc., Copyright 2007

Sheet 3 of 4

TIGERFLOW Booster Sizing Worksheet

06/24/2015

800-783-6756
214-333-2742 FAX
www.tigerflow.com

TIGERFLOW Systems, Inc., Copyright 2007

Sheet 4 of 4