Sie sind auf Seite 1von 1

Load capacities of threaded hanger rods are indicated in the table below:

Nominal Rod Diameter


(inches)
3/8
1/2
5/8
3/4
7/8
1
1 1/8
1 1/4
1 1/2
1 3/4
2
2 1/4
2 1/2
3
3 1/4
3 1/2
4
4 1/2
5

Root Area of Thread


(in2)
0.07
0.13
0.20
0.30
0.42
0.55
0.69
0.89
1.29
1.74
2.30
3.02
3.72
5.62
6.72
7.92
10.6
13.7
17.2

Maximum Load 1)
(lbs)
600
1100
1800
2700
3800
4900
6200
8000
11600
14700
20700
27200
33500
50600
60500
71300
95400
123000
154000

(kg)
270
500
820
1220
1720
2220
2810
3630
5260
6670
9390
12340
15200
22960
27440
32340
43270
55780
69900

1)

The maximum loads in the table above are based on allowable tensile stress of 12 kpsi reduced by 25% to 9 kpsi allowable stress.
Note that hangers supporting steam, water, air or gas piping systems should be able to carry the
weight of piping, insulation, valves and other equipment - and water for hydrostatic pressure
testing - without exceeding 80% of the supporting hangers yield strength (not exceeding 16 kpsi
for steel of unknown properties)