1. INTRODUCTION
The Patnode Substation is being constructed for the interconnection of Horizon Wind
Energys Marble River Wind Farm which consists of 73 wind turbine generators (WTGs)
each with a nominal rating of 3.0MW for a total generation capacity of 219MW. Patnode
Substation will be operated by NYPA when complete. TRC is providing protective relay
settings for all relays other than those for line protection at Patnode Substation. This
document provides the criteria used by TRC to complete the relay settings. A separate
document provides the relay setting criteria for the Marble River Wind Farm collector
substation.
04/10/12
Rev. 0
2.
2.1
TRC is only responsible for protective relays settings in Patnode Substation for breaker
failure, bus protection, and transformer protection. Relay settings for WPN1 or PND1
transmission line protection are provided by NYPA.
2.2
All impedance and short circuit contribution information in the supplied short circuit
model used for calculating relay settings is based on Horizon/EDPR information supplied
to the date of this document. Short circuit model information can be found in the Marble
River Settings Basis document.
2.3
All protective equipment for T2 and the 230kV system is located in the Patnode
Substation control house. All other protective equipment is located in the Marble River
Wind Farm collector station control house and documented in the Marble River Settings
Basis document.
2.4
NYPA has provided setting guidance and set points for the 230kV breaker reclosing and
sync-check relays. TRC has completed documentation of these settings and included
them in this document.
3.
PROTECTION OVERVIEW
3.1
The following table lists the protective devices covered by this document. The name,
model, brief description, and protective functions are provided. Refer to relay
calculations section for more detailed information.
Relay
87TBP/T2
Relay Type
7UT613
Relay Description
230kV Bus 2BE and T2
Protective
Elements
87T
Differential/Overcurrent
Protection Relay
04/10/12
Element Function
Bus and transformer
differential
50H
Phase IOC
50HN
Gnd IOC
51H
Phase TOC
Rev. 0
87TP/T2
87TS/T2
87BS/2BE
SEL-587
GE-T60
SEL-587Z
51NH
Gnd TOC
59N
Gnd OV
T2 Differential/Overcurrent
87T
Transformer differential
Protection Relay
50H
Phase IOC
50HN
Gnd IOC
51H
Phase TOC
51HN
Gnd TOC
51L
51LN
T2 Differential/Overcurrent
87T
Transformer differential
Protection Relay
50H
Phase IOC
50HN
Gnd IOC
51H
Phase TOC
51HN
Gnd TOC
51L
51N
59N
Gnd OV
87B
50/62BFP/2102
50/62BFP/2108
50/62BFP/2114
50/62BFS/2102
50/62BFS/2108
50/62BFS/2114
7SJ61
7SJ61
7SJ61
GE-C60
GE-C60
GE-C60
differential
50FD
62BF
Timer
50FD
62BF
Timer
50FD
62BF
Timer
50FD
62BF
Timer
50FD
62BF
Timer
50FD
62BF
Timer
3.2
The following table lists the lock out relays covered by this document. The name and
description of operation are provided.
04/10/12
Rev. 0
Lockout Relay
86TBP/T2
Function
87TBP/T2
Tripped By
Trips
87TBP/T2
Lockout
Blocks
Comments
2102-TC1
2102
Gnd OV element
2114-TC1
2114
trips T2MR
T2MR
T2MR
directly.
Initiates BF
86TP/T2
87TP/T2
87TP/T2
Lockout
86TS/T2
87TS/T2
87TS/T2
Lockout
2102-TC1
2102
Initiates BF
2114-TC1
2114
T2MR
T2MR
2102-TC2
2102
Gnd OV element
2114-TC2
2114
trips T2MR
T2MR
T2MR
directly.
Initiates BF
86BS/T2
87BS/2BE
87BS/2B3
Lockout
86BFP/2102
50/62BFP/2102
50/62BFP/2102
Lockout
2102-TC2
2102
2114-TC2
2114
T2MR
T2MR
2108-TC1
2108
2114-TC1
2114
T2MR
T2MR
Initiates BF
DTT-P/WPN1
86BFP/2108
50/62BFP/2108
50/62BFP/2108
Lockout
2102-TC1
2102
2114-TC1
2114
DTT-P/PND1
DTT-P/WPN1
86BFP/2114
50/62BFP/2114
50/62BFP/2114
Lockout
2102-TC1
2102
2108-TC1
2108
T2MR
T2MR
DTT-P/PND1
86BFS/2102
50/62BFS/2102
50/62BFS/2102
Lockout
2108-TC2
2108
2114-TC2
2114
T2MR
T2MR
DTT-S/WPN1
86BFS/2108
50/62BFS/2108
50/62BFS/2108
Lockout
2102-TC2
2102
2114-TC2
2114
DTT-S/PND1
04/10/12
Rev. 0
DTT-S/WPN1
86BFS/2114
50/62BFS/2114
50/62BFS/2114
Lockout
2102-TC2
2102
2108-TC2
2108
T2MR
T2MR
DTT-S/PND1
3.3
Relay Type
Relay Description
Protective
Element Function
Elements
79/2102
BE1-79M
Reclosing Relay
NA
79/2108
BE1-79M
Reclosing Relay
NA
79/2114
BE1-79M
Reclosing Relay
NA
25/27/2102
MLJ
NA
25/27/2108
MLJ
NA
25/27/2114
MLJ
NA
Relay Calculations
4.1
4.2
All fault current values used for the relay calculations are based on information available
as of the date of this document.
4.3
04/10/12
Any changes shall be approved by the settings engineer before record document is issued.
Rev. 0
PATNODE
87TBP/T2
04/10/12
Rev. 0
STATION:
PATNODE
DEVICE:
87TBP/T2
DATE:
LINE:
RELAY:
FID:
ENG:
4/6/2012
DEVICE CONFIGURATION
0103 Setting Group Change Option
0105 Protection Object
Disabled
3ph Trans.
Enabled
Disabled
0120 50/51
NOT USED
TOC ANSI
NOT USED
Phase Overcurrent for 230kV Only
0130 50/51#2
Disabled
NOT USED
0132 50/51#3
Disabled
NOT USED
0122 50N/51N
TOC ANSI
0134 50/51N#2
Disabled
NOT USED
0136 50/51N#3
Disabled
NOT USED
0124 50G/51G
Disabled
NOT USED
0138 50/51G#2
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
0143 24 Overexcitation
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
0152 27 Undervoltage
Disabled
NOT USED
0153 59 Overvoltage
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Flexible Functions
Enable #1
04/10/12
Rev. 0
STATION:
PATNODE
DEVICE:
87TBP/T2
DATE:
LINE:
RELAY:
FID:
ENG:
4/6/2012
SPARE
Binary Output 1- 6
Type
Conf.
Binary Output 7
Type
Conf.
Binary Output 8
Trip T2MR
Type
Conf.
OUT
U
Type
Conf.
RELAY PICKUP
OUT
L
Type
Conf.
87 TRIP
OUT
L
Type
Conf.
87 A PH TRIP
OUT
L
Type
Conf.
87 B PH TRIP
OUT
L
Type
Conf.
87 C PH TRIP
OUT
L
Type
Conf.
50H TRIP
OUT
L
Type
Conf.
50HN TRIP
OUT
L
Not latched
CONFIGURATION: LEDS
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED 8
Type
Conf.
Type
Conf.
51H TRIP
OUT
L
Type
Conf.
51HN TRIP
OUT
L
Type
Conf.
59N TRIP
OUT
L
Type
Conf.
Test Mode
IntSP
U
LED 9
LED 10
LED 11
LED 12
LED 13
Type
04/10/12
10
Rev. 0
STATION:
PATNODE
DEVICE:
87TBP/T2
DATE:
LINE:
RELAY:
FID:
ENG:
4/6/2012
Conf.
LED 14
Type
Conf.
U
Protection Config. Error
OUT
U
INTERFACE: VD ADDRESSES
VD Address
SIPROTEC SYS VD Address
Proxy VD Address
SIPROTEC T103 VD Address
04/10/12
11
Rev. 0
STATION:
PATNODE
DEVICE:
87TBP/T2
DATE:
LINE:
RELAY:
FID:
ENG:
4/6/2012
Frame
Baud Rate
Max gap
IP Address
Subnet Mask
Link Layer
Access Authorization
Access Rights
Image 1
S1:M1+M2 S2:M3
Not Conn.
Not Conn.
Not Conn.
1A/5A
Side 1
0262 VT V4 assigned
Not Conn
0263 VT V4 used as
Vdelta
60
ABC
NOT USED
REQUIRED SETTING, NOT USED
Hz
Degrees
230
kV
233
MVA
04/10/12
12
Rev. 0
STATION:
PATNODE
DEVICE:
87TBP/T2
DATE:
LINE:
RELAY:
FID:
ENG:
4/6/2012
0313 Starpoint of S1
Isolated
Delta
34.5
kV
233
MVA
0323 Starpoint of S2
0324 Transf. Winding Connection S2
0325 Vector Group Numeral S2
Grounded
Wye
1
Dyn1 Transformer
S1
S1
Yes
2000
Yes
2000
Yes
4000
230
kV
111
0.17
0.05
04/10/12
13
Rev. 0
STATION:
PATNODE
DEVICE:
87TBP/T2
DATE:
LINE:
RELAY:
FID:
ENG:
4/6/2012
Set >=
0.049241
ON
OFF
ON
5th
0.3
sec.
sec.
1241A Slope 1
1242A Slope 1 Base Point
0.25
0
1243A Slope 2
0.5
1.5
0.1
sec.
Default Setting
15
cyc.
Default Setting
cyc.
cyc
04/10/12
Default Setting
20%
0
35%
0
14
Rev. 0
STATION:
PATNODE
DEVICE:
87TBP/T2
DATE:
LINE:
RELAY:
FID:
ENG:
4/6/2012
1.5
ON
oo
NOT USED
oo
NOT USED
8.62
T2 50H
Set 87TBP/T2 pickup the same as 87TP/T2
50H=
CTR=
21
240
Ins=
584.88
SET
0
1.6
A,sec
587 CTR
5040 A,pri
8.62 A,pu
50-1
8.62
5042
A,pu
A,pri
sec.
T2 51H
Set 87TBP/T2 pickup the same as 87TP/T2
51H=
CTR=
3.9
240
Ins=
584.88
SET
2.2
2025 51 Drop-Out
Instantaneous
A,sec
587 CTR
936 A,pri
1.60 A,pu
51
1.6
936
A,pu
A,pri
Mod. Inv.
OFF
Inactive
RESIDUAL GROUND
2201 50N, 51N Phase TOC
ON
oo
NOT USED
oo
NOT USED
1.23
T2 50NH
Set 87TBP/T2 pickup the same as 87TP/T2
50NH=
CTR=
Ins=
04/10/12
15
3
240
584.88
A,sec
587 CTR
720 A,pri
1.23 A,pu
Rev. 0
STATION:
PATNODE
DEVICE:
87TBP/T2
DATE:
LINE:
RELAY:
FID:
ENG:
4/6/2012
SET
0.25
50N-1
1.23
719
A,pu
A,pri
sec.
T2 51NH
Set 87TBP/T2 pickup the same as 87TP/T2
51NH=
CTR=
Ins=
0.6
A,sec
240
587 CTR
584.88
SET
Instantaneous
144 A,pri
0.25 A,pu
51N
0.25
146
A,pu
A,pri
VERY INV.
OFF
Inactive
Voltage
3V0
ON
Pickup Threshold
166
Enables Function
04/10/12
16
111
333
166.5
Nominal VT connection
3 times nominal
V,pri
Rev. 0
STATION:
PATNODE
DEVICE:
87TBP/T2
DATE:
LINE:
RELAY:
FID:
ENG:
4/6/2012
SET
Pickup
166
V,pri
Trip Delay
sec
sec
0.1
sec
YES
Dropout Ratio
0.95
Default Value
TIME SYNCHRONIZATION
IRIG B
Source
Fault Indication
Time Format
Offset to Signal
10 Min
mm/dd/yy
With Pickup
sec.
0.1
sec.
0.1
sec.
0.5
sec.
Max Setting
Default
04/10/12
17
Rev. 0
PATNODE
87TP/T2
04/10/12
18
Rev. 0
STATION:
PATNODE
DEVICE:
87TP/T2
DATE:
LINE:
RELAY:
FID:
ENG:
T2
SEL 058710325X1
R703-Z001
JK/TRC
4/06/2012
87TP/T2
TID=
PN T2
MVA=
233.00
(MVA)
VWDG1=
230.00
(kV)
VWDG2=
34.50
(kV)
Trans. 2 is an ANSI STD (DABY) connected delta (230 kV) high side with
a solidly grounded wye (34.5 kV) low side. (140/187/233 MVA)
The high side CT's are 1200/5 connected in wye.
The low side CT's are 4000/5 connected in wye.
TRCON=
DABY
CTCON=
YY
RZS=
CTR1=
240
(Wye)
CTR2=
800
(Wye)
DATC=
OFF
(Min)
PDEM=
N/A
QDEM=
N/A
NDEM=
N/A
TAP1 and TAP2 values are automatically calculated by relay if a value for MVA has
been entered.
Manual calculation of TAP1 and TAP2 can be done as follows:
(Refer to Table 3.2 in SEL-587 Instruction Book for C1 and C2 values.)
TAP1 = (MVA x 1000 x C1)/((sqrt(3)) x VWDG1 x CTR1)
C1=
1.00
1.00
TAP1=
2.44
TAP2=
4.87
We are using a 5.0 Amp. Relay (In = 5) so the TAP range must be between
(0.1 x In and 32 x In) = (0.5 to 160) Checks out OK
04/10/12
19
Rev. 0
STATION:
PATNODE
DEVICE:
87TP/T2
DATE:
LINE:
RELAY:
FID:
ENG:
T2
SEL 058710325X1
R703-Z001
JK/TRC
4/06/2012
4.87
TAPmin=
2.44
TAPmax/TAPmin=
2.00
IN1=
N/A
Not Used
IN2=
N/A
Not Used
0.21
SET O87P=
0.30
Minimum fault is with weak utility source (Willis - Patnode Out of Service). A T2 lowside fault is 10,664A
with corresponding current on the highside of 1600A.
Min. T2 3Ph fault = 1600A,pri / (1200/5 CT) = 6.67A,sec
O87P times TAPmin = (0.30 x 2.437) = 0.731A,sec. Relay Operates
RESTRAINT SLOPE SETTINGS
SLP1=
25.00
(%)
Restraint Slope 1
SLP2=
50.00
(%)
Restraint Slope 2
IRS1=
3.00
(pu)
32.83
SET U87P=
8.00
TB1 MVA
INRUSH=
U87P=
(5 amp relay)
140 TIMES
17.57 AMP SEC
8
pu, TAP
12
EQUALS
EQUALS
1680.00 MVA
4217.17 AMP PRI
04/10/12
20
Rev. 0
STATION:
PATNODE
DEVICE:
87TP/T2
DATE:
LINE:
RELAY:
FID:
ENG:
T2
SEL 058710325X1
R703-Z001
JK/TRC
4/06/2012
PCT2=
15.00
(%)
PCT4=
13.00
(%)
35.00
TH5=
0.50
TH5D=
30.00
DCRB=
(%)
(cyc)
The SEL-587 relay allows use of even-harmonic restraint for added security during
inrush conditions. Setting HRSTR=Y allows the 2nd and 4th harmonic compensated
currents to be added to the restraint quantity.
HRSTR=
OFF
50P1D=
50P1TC=
04/10/12
21
Rev. 0
STATION:
PATNODE
DEVICE:
87TP/T2
DATE:
50P1H=
LINE:
RELAY:
FID:
ENG:
T2
SEL 058710325X1
R703-Z001
JK/TRC
4/06/2012
21.00
1057
TIMES
15.48 AMP SEC
EQUALS
1479.80 MVA
3714.62 AMP PRI
EQUALS
1680.00 MVA
4217.17 AMP PRI
140 TIMES
17.57 AMP SEC
12
17.57
1.2 EQUALS
TIMES
SET
50P1HC=
1.4
50P1PH
21.00
5040.00
3.90
PHASE TOC
Set to carry load and reach 34.5kV faults. Set TOC PU to approximatiely 150% of
T2 maximum rating and less than 40% of LS minimum 3ph SC (WPN1 Out of
Service).
40% of minimum fault is below margin for max load. Set pickup at minimum margin
for max load which is approx. 55% of minimum lowside fault.
Set TD to coordinate with downstream protection, transformer should clear in
approximately 1 sec for a low side fault.
Verify inrush will not cause any issues.
TB1 MAX (MVA)
233.00
3.66
TIMES
AMP SEC
1.50
EQUALS
349.50 MVA
877.32 AMP PRI
637.00
2.67
TIMES
AMP SEC
0.40
EQUALS
254.80 MVA
639.60 AMP PRI
SET
51P1P
3.90
936.00
amps sec
amps pri
SET 51P1C =
U1
US MODERATELY INVERSE
2.2
SET 51P1TC =
N/A
04/10/12
OFF
22
Rev. 0
STATION:
PATNODE
DEVICE:
87TP/T2
DATE:
LINE:
RELAY:
FID:
ENG:
T2
SEL 058710325X1
R703-Z001
JK/TRC
4/06/2012
50Q1D=
50Q1TC=
OFF
OFF
50N1D=
50N1TC=
Typically set 5 times TOC pickup and a maximum of 50% of minimum 230kV
phase to ground fault (WPN1 Out of Service).
3.00
50N1HC=
2340.00
4.88
TIMES
AMPS SEC
0.50
EQUALS
0.60
TIMES
EQUALS
SET
50N1H
3.00
720.00
0.60
04/10/12
T2 FLA=
585.00
1.46
TIMES
AMPS SEC
0.60
EQUALS
351.00
AMP PRI
NYPA pu =
176.00
DIVIDED
1.2
EQUALS
146.67
AMP PRI
23
Rev. 0
STATION:
PATNODE
DEVICE:
87TP/T2
DATE:
LINE:
RELAY:
FID:
ENG:
T2
SEL 058710325X1
R703-Z001
JK/TRC
4/06/2012
0.61
AMPS SEC
SET
51N1P
0.60
144.00
amps sec
amps Pri
SET 51N1C =
U3
US VERY INVERSE
1.0
SET 51N1TC =
N/A
OFF
50P2D=
50P2TC=
Not Used
OFF
50P2HC=
7.50
PHASE TOC
Set TOC pick up to 150% TB2 maximum MVA to carry load.
Set TD to coordinate with downstream protection.
TB1 MAX (MVA)
04/10/12
233.00
7.31
TIMES
AMP SEC
1.50
EQUALS
SET
51P2P
7.50
6000.00
349.50 MVA
5848.81 AMP PRI
amps sec
amps Pri
SET 51P2C =
U1
US MODERATELY INVERSE
1.2
24
Rev. 0
STATION:
PATNODE
DEVICE:
87TP/T2
DATE:
LINE:
RELAY:
FID:
ENG:
T2
SEL 058710325X1
R703-Z001
JK/TRC
4/06/2012
SET 51P2TC =
N/A
OFF
50Q2D=
50Q2TC=
OFF
NOT USED
OFF
50N2D=
50N2TC=
OFF
50N1HC=
NOT USED
External Torque Control - Not Used
2.50
NOT USED
Set TOC PU at 50% of bank full load rating. 233MVA = 3900A @ 34.5kV.
Set TD to coordinate with downstream protection.
3900.00
2.44
TIMES
AMPS SEC
0.50
EQUALS
SET
51N2P
2.50
2000.00
SET 51N2C =
04/10/12
U1
25
Rev. 0
STATION:
PATNODE
DEVICE:
87TP/T2
DATE:
LINE:
RELAY:
FID:
ENG:
T2
SEL 058710325X1
R703-Z001
JK/TRC
4/06/2012
4.0
SET 51N2TC =
N/A
LTRP=
Set LTRP = N, Resets when current is below threshold - Using an ext. LOR
MINIMUM TRIP DURATION TIME DELAY:
Minimum time that the output trip contacts remain closed. Set to coordinate with bkr
trip times plus a 3 cycle margin. (3 cyc breaker + 3 cyc = 6 cyc)
SET
TDURD
EQUAL
6.00
cycles
0.00
(cyc)
TXDO=
0.00
(cyc)
TYPU=
0.00
(cyc)
TYDO=
0.00
(cyc)
NFREQ=
60.00
(cyc)
PHROT=
ABC
GLOBAL VARIABLES
NA
Y=
NA
04/10/12
MTU1=
50P1T+51P1T+
26
Rev. 0
STATION:
PATNODE
DEVICE:
87TP/T2
DATE:
LINE:
RELAY:
FID:
ENG:
T2
SEL 058710325X1
R703-Z001
JK/TRC
4/06/2012
50N1T+51N1T
MTU2=
51P2T + 51N2T
MTU3=
87R + 87U
MER=
OUTPUT SETTINGS:
OUTPUTS:
SET
SET
SET
SET
OUT1=
OUT2=
OUT3=
OUT4=
PORT 1
PROTO=
MOD
SPEED=
9600
PARITY=
STOP=
SLAVEID=
04/10/12
27
Rev. 0
STATION:
PATNODE
DEVICE:
87TP/T2
DATE:
LINE:
RELAY:
FID:
ENG:
T2
SEL 058710325X1
R703-Z001
JK/TRC
4/06/2012
04/10/12
28
Rev. 0
PATNODE
87TS/T2
04/10/12
29
Rev. 0
STATION:
DEVICE:
PATNODE
87TS/T2
DATE:
LINE:
T2
RELAY:
T60-N03-VFH-F8F-H6P-M8F-R7A
FID:
5.5x
ENG:
JK/TRC
4/6/2012
Command Password
Setting Password
5 min
30 min
5 min
Enabled
1.0 s
300 s
25%
Enabled
30 min
0.020 pu
1.0 V
19200
None
0 ms
04/10/12
30
Rev. 0
STATION:
DEVICE:
PATNODE
87TS/T2
DATE:
LINE:
T2
RELAY:
T60-N03-VFH-F8F-H6P-M8F-R7A
FID:
5.5x
ENG:
JK/TRC
4/6/2012
COM2 - RS485
NONE
DNP Address
25
Enabled
0.0 hr
Disabled
04/10/12
31
Rev. 0
STATION:
DEVICE:
PATNODE
87TS/T2
DATE:
LINE:
T2
RELAY:
T60-N03-VFH-F8F-H6P-M8F-R7A
FID:
5.5x
ENG:
JK/TRC
4/6/2012
5
Automatic Overwrite
30%
Trigger Source
AC Input Waveforms
64 samples/cycle
Digital Channel 2
SRC1 50DD OP
Digital Channel 3
Digital Channel 4
Digital Channel 5
Digital Channel 6
Digital Channel 7
Digital Channel 8
Digital Channel 9
Digital Channel 10
Digital Channel 11
Digital Channel 12
Digital Channel 13
Digital Channel 14
PHASE TOC1 OP
Digital Channel 15
PHASE IOC1 OP
Digital Channel 16
NEUTRAL TOC1 OP
Digital Channel 17
NEUTRAL IOC1 OP
Digital Channel 18
PHASE TOC2 OP
Digital Channel 19
NEUTRAL TOC2 OP
Digital Channel 20
GROUND TOC3 OP
SPARE
04/10/12
Analog Channel 1
Analog Channel 2
32
Rev. 0
STATION:
DEVICE:
PATNODE
87TS/T2
DATE:
LINE:
T2
RELAY:
T60-N03-VFH-F8F-H6P-M8F-R7A
FID:
5.5x
ENG:
JK/TRC
4/6/2012
Analog Channel 3
Analog Channel 4
Analog Channel 5
Analog Channel 6
Analog Channel 7
Analog Channel 8
Analog Channel 9
Analog Channel 10
SRC1
I_1 Mag
Analog Channel 11
SRC1
I_2 Mag
Analog Channel 12
SRC1
I_0 Mag
Analog Channel 13
SRC2
I_1 Mag
Analog Channel 14
SRC2
I_2 Mag
Analog Channel 15
SRC2
I_0 Mag
Tracking Frequency
Analog Channel 16
Continuous
OFF
Rate
60000 msec
Thermal Exponential
Power Method
Thermal Exponential
Interval
15 MIN
Trigger
OFF
TRIPBUS 1 OP
04/10/12
33
Rev. 0
STATION:
DEVICE:
PATNODE
87TS/T2
DATE:
LINE:
T2
RELAY:
T60-N03-VFH-F8F-H6P-M8F-R7A
FID:
5.5x
ENG:
JK/TRC
4/6/2012
Enabled
Enabled
Enabled
Disabled
Enabled
Enabled
Enabled
87TS/T2
04/10/12
4000 A
5A
600 A
5A
34
Rev. 0
STATION:
DEVICE:
PATNODE
87TS/T2
DATE:
LINE:
T2
RELAY:
T60-N03-VFH-F8F-H6P-M8F-R7A
FID:
5.5x
ENG:
JK/TRC
4/6/2012
1200 A
5A
1A
1A
Wye
66.4
VT M5: VT Ratio
2000
CONNECTED AT 66.4V
60 Hz
Phase Rotation
ABC
SRC 1 (SRC 1)
T2 230KV
Enabled
SRC 1
SOURCE 1: Phase CT
M1
SOURCE 1: Ground CT
None
SOURCE 1: Phase VT
M5
SOURCE 1: Auxiliary VT
None
SOURCE 2: Name
SRC 2
DEFAULT VALUE
ASSIGN 230KV AS SOURCE 1
DEFAULT VALUE
SOURCE 2: Phase CT
F1
SOURCE 2: Ground CT
F1
SOURCE 2: Phase VT
None
SOURCE 2: Auxiliary VT
None
T2 is an ANSI STD (DABY) connected delta (230kV) high side with a solidy grounded
wye (34.5kV) low side. T2 is rated 140/187/233MVA.
Number Of Windings
Reference Winding Selection
Phase Compensation
04/10/12
PER T2 NAMEPLATE
Automatic Selection
Internal (software)
35
Rev. 0
STATION:
DEVICE:
PATNODE
87TS/T2
DATE:
LINE:
T2
RELAY:
T60-N03-VFH-F8F-H6P-M8F-R7A
FID:
5.5x
ENG:
JK/TRC
4/6/2012
100 kW
65C (oil)
10 kW
OA
35 C
Thermal Capacity
100.00 kWh/C
2.00 min
WINDING 1: Connection
Delta
WINDING 1: Grounding
0.0 deg
10.0000 ohms REQUIRED ENTRY, NOT USED
SRC 2 (SRC 2) ASSOCIATE 34.5KV WINDING WITH WITH WINDING 2
140.000 MVA
Wye
WINDING 2: Grounding
Within zone
WINDING 2: Resistance
34.500 kV
WINDING 2: Connection
-30.0 deg
10.0000 ohms REQUIRED ENTRY, NOT USED
04/10/12
36
Rev. 0
STATION:
DEVICE:
DATE:
PATNODE
87TS/T2
LINE:
T2
RELAY:
T60-N03-VFH-F8F-H6P-M8F-R7A
FID:
5.5x
ENG:
JK/TRC
4/6/2012
04/10/12
FlexLogic Entry 1
FlexLogic Entry 2
FlexLogic Entry 3
FlexLogic Entry 4
FlexLogic Entry 5
FlexLogic Entry 6
FlexLogic Entry 7
FlexLogic Entry 8
FlexLogic Entry 9
FlexLogic Entry 10
FlexLogic Entry 11
PHASE TOC1 OP
FlexLogic Entry 12
FlexLogic Entry 13
NEUTRAL TOC1 OP
FlexLogic Entry 14
FlexLogic Entry 15
PHASE TOC2 OP
FlexLogic Entry 16
FlexLogic Entry 17
NEUTRAL TOC2 OP
FlexLogic Entry 18
FlexLogic Entry 19
GROUND TOC3 OP
FlexLogic Entry 20
FlexLogic Entry 21
SRC1 50DD OP
FlexLogic Entry 22
FlexLogic Entry 23
SRC2 50DD OP
FlexLogic Entry 24
FlexLogic Entry 25
NEUTRAL OV1 OP
FlexLogic Entry 26
FlexLogic Entry 27
TRIPBUS 1 OP
FlexLogic Entry 28
FlexLogic Entry 29
TRIPBUS 2 OP
FlexLogic Entry 30
37
Rev. 0
STATION:
DEVICE:
PATNODE
87TS/T2
DATE:
LINE:
T2
RELAY:
T60-N03-VFH-F8F-H6P-M8F-R7A
FID:
5.5x
ENG:
JK/TRC
4/6/2012
FlexLogic Entry 31
OR (15)
FlexLogic Entry 32
FlexLogic Entry 33
END
ALL CALCULATIONS ARE BASED ON ASPEN ONELINER CASE MARBLE RIVER WFr1.
THE GE RELAY USES PICKUP SETTINGS IN PER UNIT VALUES, 5A BASE
T2 RATINGS:
BASE=
MAX=
140 MVA
233 MVA
CTR=
Vll=
240
230 KV
I,base=
I,max=
351.43 A,pri
584.88 A,pri
1.46 A,sec
2.44 A,sec
0.29 A,pu
0.49 A,pu
2.93 A,sec
4.87 A,sec
0.59 A,pu
0.97 A,pu
19.52 A,sec
32.49 A,sec
3.90 A,pu
6.50 A,pu
17.57 A,sec
3.51 A,pu
800
34.5 KV
I,base=
I,max=
2342.87 A,pri
3899.21 A,pri
120.00
34.50 KV
I,base=
I,max=
2342.87 A,pri
3899.21 A,pri
T2 INRUSH:
I. FACTOR=
12.00
I, INRUSH =
4217.17 A,pri
04/10/12
38
1 phase
Rev. 0
STATION:
DEVICE:
PATNODE
87TS/T2
DATE:
LINE:
T2
RELAY:
T60-N03-VFH-F8F-H6P-M8F-R7A
FID:
5.5x
ENG:
JK/TRC
4/6/2012
A,pri
A,sec
A,pu
33.26
0.00
6.65
0.00
0.00
0.00
SRC 1
SRC 2
8782.00
6114.00
Iint,pu=
A,sec
A,pu
A,pri
36.59
7.32
7.64
1.53
7983.00
0.00
7.32
Fault values are taken for close in faults external to the zone of protection.
SRC 1
SRC 2
Iint,pu=
SRC 1
SRC 2
1.53
Iint,pu=
0.00
7.18
7.18
Maximum current relay will see for through fault=
7.18
Enabled
Pickup
0.300 pu
Slope 1
25%
Break 1
1.500 pu
Break 2
8.000 pu
Slope 2
98%
Adapt. 2nd
2-Out-Of-3
20.0 % fo
Disabled
10.0 % fo
Block
OFF
Target
Self-reset
Events
Enabled
04/10/12
Enabled
39
Rev. 0
STATION:
DEVICE:
PATNODE
87TS/T2
DATE:
LINE:
T2
RELAY:
T60-N03-VFH-F8F-H6P-M8F-R7A
FID:
5.5x
ENG:
JK/TRC
4/6/2012
Pickup
8.000 pu
RECOMMENDED SETTING
Set Inst. Differential to recommended setting and verify pickup is
greater than inrush and through faults.
I,unrst=
I, inr.=
I, trhflt=
8
3.51
7.18
228%
111%
OFF
Target
Self-reset
Events
Enabled
Enabled
SRC 1 (SRC 1) T2 51H
Phasor
0.78 pu
Set 87TS/T2 pickup the same as 87TP/T2
51H=
CTR=
3.9
240
CTP=
1200
SET
04/10/12
A,sec
936 A,pri
0.78 A,pu
PTOC1
0.78
936
A,pu
A,pri
Instantaneous
Disabled
40
Rev. 0
STATION:
DEVICE:
DATE:
PATNODE
87TS/T2
LINE:
T2
RELAY:
T60-N03-VFH-F8F-H6P-M8F-R7A
FID:
5.5x
ENG:
JK/TRC
4/6/2012
OFF
OFF
OFF
Self-reset
Enabled
Enabled
Phasor
1.5 pu
Set 87TS/T2 pickup the same as 87TP/T2
51L=
CTR=
7.5
800
CTP=
4000
SET
A,sec
6000 A,pri
1.5 A,pu
PTOC2
1.5
6000
A,pu
A,pri
Instantaneous
Disabled
OFF
OFF
OFF
Self-reset
Enabled
Enabled
SRC 1 (SRC 1) T2 50H
4.2 pu
Set 87TS/T2 pickup the same as 87TP/T2
50H=
CTR=
21
240
CTP=
1200
SET
04/10/12
A,sec
5040 A,pri
4.2 A,pu
PIOC1
4.2
5040
A,pu
A,pri
0.00 s
41
Rev. 0
STATION:
DEVICE:
DATE:
PATNODE
87TS/T2
LINE:
T2
RELAY:
T60-N03-VFH-F8F-H6P-M8F-R7A
FID:
5.5x
ENG:
JK/TRC
4/6/2012
0.00 s
OFF
OFF
OFF
Self-reset
Enabled
Enabled
SRC 1 (SRC 1) T2 51HN
Phasor
0.12 pu
Set 87TS/T2 pickup the same as 87TP/T2
51HN=
CTR=
0.6
240
CTP=
1200
SET
144 A,pri
0.12 A,pu
NTOC1
0.12
144
A,pu
A,pri
Instantaneous
OFF
Self-reset
Enabled
Enabled
A,sec
Phasor
0.5 pu
Set 87TS/T2 pickup the same as 87TP/T2
04/10/12
42
51LN=
CTR=
2.5
800
CTP=
4000
A,sec
2000 A,pri
0.5 A,pu
Rev. 0
STATION:
DEVICE:
DATE:
PATNODE
87TS/T2
LINE:
T2
RELAY:
T60-N03-VFH-F8F-H6P-M8F-R7A
FID:
5.5x
ENG:
JK/TRC
4/6/2012
SET
NTOC2
0.5
2000
A,pu
A,pri
Instantaneous
OFF
Self-reset
Enabled
Enabled
SRC 1 (SRC 1) T2 50HN
0.6 pu
Set 87TS/T2 pickup the same as 87TP/T2
50HN=
CTR=
3
240
CTP=
1200
SET
0.00 s
0.00 s
OFF
Self-reset
Enabled
A,sec
720 A,pri
0.6 A,pu
NIOC1
0.6
720
A,pu
A,pri
Enabled
SRC 2 (SRC 2) T2 51N
Phasor
3.33 pu
Set 87TS/T2 pickup the same as 87TP/T2
51N=
04/10/12
43
2.5
A,sec
2000 A,pri
Rev. 0
STATION:
DEVICE:
PATNODE
87TS/T2
DATE:
LINE:
T2
RELAY:
T60-N03-VFH-F8F-H6P-M8F-R7A
FID:
5.5x
ENG:
JK/TRC
4/6/2012
CTR=
800
CTP=
600
SET
3.33 A,pu
NTOC2
3.33
1998
A,pu
A,pri
Instantaneous
OFF
Self-reset
Enabled
Enabled
SRC 1
1.5
66.4
199.2
3
1.5
SET
Nominal VT connection
3 times nominal
pu, value of 3V0. 66.4V is V,base
pu
NOV1
1.5
99.6
V,pu
V,pri
Def. Time
5.0
OFF
Self-reset
Enabled
04/10/12
44
Rev. 0
STATION:
DEVICE:
PATNODE
87TS/T2
DATE:
LINE:
T2
RELAY:
T60-N03-VFH-F8F-H6P-M8F-R7A
FID:
5.5x
ENG:
JK/TRC
4/6/2012
USE TRIP BUS 1 FOR ALL PROTECTIVE ELEMENTS THAT WILL TRIP 86TS/T2.
Trip Bus 1 Function
Trip Bus 1 Block
04/10/12
Enabled
OFF
NO BLOCK TRIP
0.00 s
NO PICK-UP DELAY
0.1 s
T2 87
T2 87
NEUTRAL IOC1 OP
T2 50HN
NEUTRAL TOC1 OP
T2 51HN
PHASE IOC1 OP
T2 50H
PHASE TOC1 OP
T2 51H
PHASE TOC2 OP
T2 51L
NEUTRAL TOC2 OP
T2 51LN
GROUND TOC3 OP
T2 51N
OFF
OFF
OFF
OFF
45
Rev. 0
STATION:
DEVICE:
PATNODE
87TS/T2
DATE:
LINE:
T2
RELAY:
T60-N03-VFH-F8F-H6P-M8F-R7A
FID:
5.5x
ENG:
JK/TRC
4/6/2012
OFF
OFF
OFF
Disabled
OFF
Self-reset
Enabled
Enabled
OFF
NO BLOCK TRIP
0.00 s
NO PICK-UP DELAY
0.1 s
NEUTRAL OV1 OP
SPARE
Disabled
OFF
Self-reset
Enabled
59N Protection
04/10/12
46
Rev. 0
STATION:
DEVICE:
PATNODE
87TS/T2
DATE:
LINE:
T2
RELAY:
T60-N03-VFH-F8F-H6P-M8F-R7A
FID:
5.5x
ENG:
JK/TRC
4/6/2012
84 Vdc
Cont Op 1
TRIPBUS 1 OP
OFF
Enabled
Cont Op 2
TRIPBUS 2 OP
OFF
Enabled
04/10/12
47
Rev. 0
STATION:
DEVICE:
PATNODE
87TS/T2
DATE:
LINE:
T2
RELAY:
T60-N03-VFH-F8F-H6P-M8F-R7A
FID:
5.5x
ENG:
JK/TRC
4/6/2012
INPUTS/OUTPUTS: RESETTING
NOT USED - LEAVE AT DEFAULT
INPUTS/OUTPUTS: TELEPROTECTION
NOT USED - LEAVE AT DEFAULT
04/10/12
48
Rev. 0
PATNODE
COORDINATION CURVES
04/10/12
49
Rev. 0
700
2
3
4
5
7
1000
1. SEL 50/51H T2 SEL3xx/5xxMI TD=2.200
CTR=1200:5 Pickup=3.9A Inst=5040A TP@5=0.7491s
700
500
1000
10
100
1000
10000
500
400
400
300
200
200
4. FDR 1 DOC 51 SEL-STI TD=5.000
CTR=2000:5 Pickup=0.6A (Dir) No inst. TP@5=0.5358s
100
70
100
70
50
50
A. Transf. damage curve. 140.00 MVA. Category 4
Linked to curve no. 1. Z= 9.7 percent.
40
40
30
30
20
20
5
S
E
C
O
N
D
S
10
10
1
4
.7
.7
.5
.5
.4
.4
.3
.3
.2
.2
.1
.1
.07
.07
.05
.05
.04
.04
.03
.03
.02
.02
.01
10
100
7
MVA
TIME-CURRENT CURVES
1000
@ Voltage 34.5-230kV
10000
3
By
JK/TRC
No.
Comment Applicable to Feeders 1 through 8 (var. feeder instantaneous per settings basis)
04/10/12
Date 03/20/12
50
Rev. 0
.01
1000
10
100
1000
700
10000
2
3
4
5
7
1000
1. SEL 50/51H T2 SEL3xx/5xxMI TD=2.200
CTR=1200:5 Pickup=3.9A Inst=5040A TP@5=0.7491s
Ia= 1945.0A (8.1 sec A) T= 1.60s
700
500
400
500
400
300
200
100
70
100
50
40
70
50
40
FAULT DESCRIPTION:
Close-In Fault on: 0 JB-T91 34.5kV - 0 WTG 91 0.65kV 1T 3LG
30
30
20
20
5
S
E
C
O
N
D
S
10
10
1
4
A 2
2
.7
.7
.5
.5
.4
.4
.3
.3
.2
.2
.1
.1
.07
.07
.05
.05
.04
.04
.03
.03
.02
.02
Fault I=19729.6A
.01
10
100
5
7
CURRENT (A)
TIME-CURRENT CURVES
For
1000
@ Voltage 34.5-230kV
10000
3
By
JK/TRC
No.
Comment Applicable to Feeders 1 through 8 (var. feeder instantaneous per settings basis)
04/10/12
Date 03/20/12
51
Rev. 0
.01
1000
10
100
1000
10000
2
3
4
5
7
1000
1. SEL 50/51H T2 SEL3xx/5xxMI TD=2.200
CTR=1200:5 Pickup=3.9A Inst=5040A TP@5=0.7491s
Ia= 1396.6A (5.8 sec A) T=9999s
700
700
500
400
500
400
300
200
100
70
100
50
40
70
50
40
FAULT DESCRIPTION:
Close-In Fault on: 0 JB-T91 34.5kV - 0 WTG 91 0.65kV 1T 3LG
30
30
20
20
5
S
E
C
O
N
D
S
10
10
3
4
A 2
2
.7
.7
.5
.5
.4
.4
.3
.3
.2
.2
.1
.1
.07
.07
.05
.05
.04
.04
.03
.03
.02
.02
Fault I=9311.1 A
.01
10
100
5
7
CURRENT (A)
TIME-CURRENT CURVES
For
1000
@ Voltage 34.5-230kV
10000
3
By
JK/TRC
No.
Comment Applicable to Feeders 1 through 8 (var. feeder instantaneous per settings basis)
04/10/12
Date 03/20/12
52
Rev. 0
.01
1000
10
100
1000
10000
2
3
4
5
7
1000
1. SEL 50/51H T2 SEL3xx/5xxMI TD=2.200
CTR=1200:5 Pickup=3.9A Inst=5040A TP@5=0.7491s
Ia= 483.5A (2.0 sec A) T=9999s
700
700
500
400
500
400
300
200
200
4. FDR 1 DOC 51 SEL-STI TD=5.000
CTR=2000:5 Pickup=0.6A (Dir) No inst. TP@5=0.5358s
Ia= 8417.0A (21.0 sec A) T= 0.26s
100
70
100
70
FAULT DESCRIPTION:
Close-In Fault on: 0 106-L-1 34.5kV - 0 WTG 106-L 0.65kV 1T 3LG
50
50
40
40
30
30
20
20
5
S
E
C
O
N
D
S
10
10
3
4
.7
.7
.5
.5
.4
.4
.3
.3
.2
.2
.1
.1
.07
.07
.05
.05
.04
.04
.03
.03
.02
.02
Fault I=9207.0 A
.01
10
2
Feeder Phase Coordin
For
100
5
7
CURRENT (A)
TIME-CURRENT CURVES
1000
@ Voltage 34.5-230kV
10000
3
By
JK/TRC
No.
Comment Applicable to Feeders 1 through 8 (var. feeder instantaneous per settings basis)
04/10/12
Date 03/20/12
53
Rev. 0
.01
1000
10
100
1000
700
10000
2
3
4
5
7
1000
1. SEL 50/51H T2 SEL3xx/5xxMI TD=2.200
CTR=1200:5 Pickup=3.9A Inst=5040A TP@5=0.7491s
Ia= 864.6A (3.6 sec A) T=9999s
700
2. SEL 51L T2 SEL3xx/5xxMI TD=1.200
CTR=4000:5 Pickup=7.5A No inst. TP@5=0.4086s
Ia= 5764.3A (7.2 sec A) T=9999s
500
400
500
400
300
200
200
4. FDR 1 DOC 51 SEL-STI TD=5.000
CTR=2000:5 Pickup=0.6A (Dir) No inst. TP@5=0.5358s
Ia= 5765.6A (14.4 sec A) T= 0.27s
100
70
100
70
FAULT DESCRIPTION:
Close-In Fault on: 0 106-L-1 34.5kV - 0 WTG 106-L 0.65kV 1T 3LG
50
50
40
40
30
30
20
20
5
S
E
C
O
N
D
S
10
10
3
4
.7
.7
.5
.5
.4
.4
.3
.3
.2
.2
.1
.1
.07
.07
.05
.05
.04
.04
.03
.03
.02
.02
Fault I=5765.7 A
.01
10
2
Feeder Phase Coordin
For
100
5
7
CURRENT (A)
TIME-CURRENT CURVES
1000
@ Voltage 34.5-230kV
10000
3
By
JK/TRC
No.
Comment Applicable to Feeders 1 through 8 (var. feeder instantaneous per settings basis)
04/10/12
Date 03/20/12
54
Rev. 0
.01
0.10
1000
10
100
700
700
500
1000
500
400
400
FAULT DESCRIPTION:
Bus Fault on:
0 WTG 125
300
300
0.65 kV LL Type=B-C
200
200
100
100
70
70
50
50
40
40
30
30
20
20
2
S
E
C
O
N
D
S
10
10
3
1
.7
.7
.5
.5
.4
.4
.3
.3
.2
.2
.1
.1
.07
.07
.05
.05
.04
.04
.03
.03
.02
.02
Fault MVA=34.9
.01
0.10
1
MVA
TIME-CURRENT CURVES
For
@ Voltage .65-34.5kV
Marble River Feeder DOC, Sys. Minimum, End of longest feeder (8)
10
3
By
JK/TRC
No.
04/10/12
Date 03/20/12
55
Rev. 0
100
.01
1000
10
100
1000
700
1000
700
500
400
400
300
200
100
200
100
70
70
50
50
40
40
30
30
20
S
E
C
O
N
D
S
10000
20
10
10
7
1
.7
.7
.5
.5
.4
.4
.3
.3
.2
.2
.1
.1
.07
.07
.05
.05
.04
.04
.03
.03
.02
.02
.01
10
100
5
7
CURRENT (A)
TIME-CURRENT CURVES
For
1000
@ Voltage 34.5kV
10000
3
By
JK/TRC
No.
04/10/12
Date 03/20/12
56
Rev. 0
.01
1000
10
100
1000
10000
700
1000
700
500
400
400
300
200
100
100
70
70
50
50
40
40
30
30
20
20
5
4
S
E
C
O
N
D
S
10
10
4
3
1
.7
.7
.5
.5
.4
.4
.3
.3
.2
.2
.1
.1
.07
.07
.05
.05
.04
.04
.03
.03
.02
.02
.01
10
100
5
7
CURRENT (A)
TIME-CURRENT CURVES
For
1000
@ Voltage 230kV
10000
3
By
JK/TRC
No.
04/10/12
Date 04/06/12
57
Rev. 0
.01
PATNODE
87BS/2BE
04/10/12
58
Rev. 0
STATION:
PATNODE
DEVICE:
87BS/2BE
DATE:
LINE:
RELAY:
FID:
ENG:
3/20/2012
400
RID=
87BS/2BE
TID=
PN BUS 2BE
NUM OF CT'S=
CT DATA:
2102
CT OHMS/TURN:
Rct:
2114
T2 HIGH SIDE
0.00219
0.00219
0.00242
0.8760
0.8760
0.9660
600
600
600
Es:
CABLE DATA:
2102
2114
T2 HIGH SIDE
CABLE LENGTH:
220
245
340
CABLE SIZE:
#10 CU
#10 CU
#10 CU
CABLE RES:
1.02
1.02
1.02
0.2244
0.2499
0.3468
Rlead:
CT RESISTANCE IN OHMS
CT VOLTS AT KNEE
CT TO REL PANEL IN FT
Fault values from Aspen Oneliner Case: Marble River WFr1 and NYISO CY11
THRU FAULT DATA:
Individual current values seen by breaker are assuming breaker 2108 is open. A worst case through
fault is for a T2 bushing fault.
2102
2114
T2 HIGH SIDE
6620
2170
8780
PRI AMP
5220
1930
7150
PRI AMP
59
Rev. 0
STATION:
PATNODE
DEVICE:
87BS/2BE
DATE:
LINE:
RELAY:
FID:
ENG:
3/20/2012
in this scenario.
ALL IN
WILLIS OUT
DULEY OUT
9700
970
PRI AMP
7980
PRI AMP
Rct=
P=
Rlead=
IF=
N=
Vr=
2102
2114
T2 HIGH SIDE
0.8760
1
0.2244
6620
400
0.8760
1
0.2499
2170
400
0.9660
1
0.3468
8780
400
OHMS
18
29
VOLTS
OHMS
PRI AMP
CT RATIO
600
600
600
VOLTS
2102
2114
T2 HIGH SIDE
0.8760
2
0.2244
5220
400
0.8760
2
0.2499
1930
400
0.9660
2
0.3468
7150
400
OHMS
17
30
VOLTS
Rct=
P=
Rlead=
IF=
N=
Vr=
OHMS
PRI AMP
CT RATIO
600
600
600
VOLTS
04/10/12
30
volts
1.50
45
volts
60
Rev. 0
STATION:
PATNODE
DEVICE:
87BS/2BE
DATE:
LINE:
RELAY:
FID:
ENG:
3/20/2012
45
400
3
0.0060
0.0225
0.0000
volts
ct ratio
num of ct's
amp
amp
amp
Imin=
16.20
amps pri
CHECK TO INSURE MOV SIZE IS ADEQUATE. USE FIG 3.10 IN SEL INST
BOOK. USE MAX SECONDARY FAULT CURRENT AND MAX CT KNEE VOLTS
3PH BUS FLT:
9700
CT RATIO:
400
24
amps sec
Es=
600
volts
amps pri
FROM FIG 3.10 IN SEL INST BOOK, SEC FLT CURRENT = 24 AMPS AND CT
VOLTS Es = 600 LIES JUST BELOW 1 MOV. THIS RELAY HAS TWO MOV'S
TDURD
EQUAL
6.00
cycles
04/10/12
SET
87A1P
EQUAL
45
SET
87A2P
EQUAL
OFF
SET
87B1P
EQUAL
45
61
volts
volts
Rev. 0
STATION:
PATNODE
DEVICE:
87BS/2BE
DATE:
LINE:
RELAY:
FID:
ENG:
3/20/2012
SET
87B2P
EQUAL
OFF
SET
87C1P
EQUAL
45
SET
87C2P
EQUAL
OFF
volts
OFF
OFF
NOT USED
NOT USED
50B1P=
50B2P=
OFF
OFF
NOT USED
NOT USED
50C1P=
50C2P=
OFF
OFF
NOT USED
NOT USED
OFF
NOT USED
51AP=
OFF
NOT USED
51BP=
OFF
NOT USED
51CP=
OFF
NOT USED
OFF
NOT USED
51G2P=
OFF
NOT USED
OFF
NOT USED
OFF
OFF
NOT USED
NOT USED
OFF
04/10/12
NOT USED
62
Rev. 0
STATION:
PATNODE
DEVICE:
87BS/2BE
DATE:
LINE:
RELAY:
FID:
ENG:
3/20/2012
CFD
EQUAL
60.00
cycles
DEMAND METERING
DMTC=
PDEMP=
GDEMP=
QDEMP=
15
OFF
OFF
OFF
NFREQ=
60
PHROT=
ABC
DATE_F=
MDY
TR LOGIC:
Not Used
cyc
SET
TR1
EQUAL
SET
TR2
EQUAL
SET
TR3
EQUAL
SET
ULTR1
EQUAL
SET
ULTR2
EQUAL
SET
ULTR3
EQUAL
CLOSE LOGIC:
SET
04/10/12
52A
EQUAL
0
63
Rev. 0
STATION:
PATNODE
DEVICE:
87BS/2BE
DATE:
LINE:
RELAY:
FID:
ENG:
3/20/2012
SET
CL
EQUAL
SET
ULCL
EQUAL
ER1
EQUAL
SET
ER2
EQUAL
Not Used
OUTPUT SETTINGS:
OUTPUTS:
SET
SET
SET
SET
OUT1
OUT2
OUT3
OUT4
EQUAL
EQUAL
EQUAL
EQUAL
TRIP1
0
0
0
87A1
DP2=
87B1
DP3=
87C1
DP4=
DP5=
DP6=
DP7=
DP8=
Trip 86BS/2BE
PH 1 ELEM
NA
PH 2 ELEM
NA
PH 3 ELEM
NA
PORT 1
PROTO=
04/10/12
MOD
64
Rev. 0
STATION:
PATNODE
DEVICE:
87BS/2BE
DATE:
LINE:
RELAY:
FID:
ENG:
3/20/2012
SPEED=
9600
PARITY=
STOP=
SLAVEID=
SER1
EQUAL
87A1,87B1,87C1
SET
SER2
EQUAL
N/A
SET
SER3
EQUAL
N/A
04/10/12
65
Rev. 0
STATION:
PATNODE
DEVICE:
87BS/2BE
DATE:
LINE:
RELAY:
FID:
ENG:
3/20/2012
APPENDIX:
CT, Breakers 2102 and 2114
04/10/12
66
Rev. 0
STATION:
PATNODE
DEVICE:
87BS/2BE
DATE:
LINE:
RELAY:
FID:
ENG:
3/20/2012
CT, Transformer
04/10/12
67
Rev. 0
STATION:
PATNODE
DEVICE:
87BS/2BE
DATE:
LINE:
RELAY:
FID:
ENG:
3/20/2012
04/10/12
68
Rev. 0
STATION:
PATNODE
DEVICE:
87BS/2BE
DATE:
LINE:
RELAY:
FID:
ENG:
3/20/2012
04/10/12
69
Rev. 0
PATNODE
50/62BFP/2102
04/10/12
70
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2102
DATE:
BKR 2102
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
DEVICE CONFIGURATION
0103 Setting Group Change Option
Disabled
Enabled
NOT USED
0112 50/51
0113 50N/51N
0127 50 1Ph
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Binary Input 1
Type
Conf.
BF initiation
SP
H
SPARE
Binary Input 2
Type
Conf.
Binary Input 3
Type
Conf.
Binary Input 4
Type
Conf.
BFI + 52a
SP
H
Low Gas Detection
SP
H
No current BF initiation
SPARE
Binary Input 5
Type
Conf.
SPARE
Binary Input 6
Type
Conf.
SPARE
Binary Input 7
Type
Conf.
SPARE
Binary Input 8
Type
04/10/12
71
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2102
DATE:
BKR 2102
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
Conf.
BF trip of bkr.
RETRIP
OUT
U
Retrip of bkr.
Type
Conf.
BF BYPASS
OUT
U
Type
Conf.
Binary Output 2
Binary Output 3
SPARE
Binary Output 4
Type
Conf.
SPARE
Binary Output 5
Type
Conf.
SPARE
Binary Output 6
Type
Conf.
SPARE
Binary Output 7
Type
Conf.
SPARE
Binary Output 8
Type
Conf.
CONFIGURATION: LEDS
LED 1
Type
Conf.
LED 2
Type
Conf.
BFI + 52a
SP
L
Type
Conf.
A ph BFT LED
OUT
L
Type
Conf.
B ph BFT LED
OUT
L
Type
Conf.
C ph BFT LED
OUT
L
Type
Conf.
LED 3
LED 4
LED 5
LED 6
04/10/12
72
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2102
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2102
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
3/20/2012
LED 7
Type
Conf.
INTERFACE: VD ADDRESSES
VD Address
SIPROTEC SYS VD Address
Proxy VD Address
SIPROTEC T103 VD Address
04/10/12
73
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2102
DATE:
BKR 2102
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
Baud Rate
Max gap
IP Address
Subnet Mask
Link Layer
Access Authorization
Access Rights
Image 1
60hz
ABC
Degr. F
Towards Bus
0201 CT Starpoint
0235A Storage
NO
OFF
Ignd(meas.)
800
800
0.10s
1.00s
0.50A
Fault Values:
CTR=
160
2000/800:5 CT
230kV Line Ratings (R102-11 Analysis to Confirm Non-Material Change for Marble River Wind Farm, Table 3-1)
04/10/12
74
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2102
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2102
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
3/20/2012
996
A,pri
6.23 A,sec
996
A,pri
6.23 A,sec
Fault Information
All fault information is based on Aspen Oneliner Case: NYISO CY11. To
model a weak system the following were taken out of service: Noble Clinton
W.F., Chateaugay W.F., Noble Ellenburg W.F., Noble Altona W.F., Marble
River W.F. Additionally, The strongest source opposite the faulted station
was removed (ie, for a Duley the strongest source at Willis was removed.
The removed element is specified next to the fault table below.
2023
2492
2889
A,pri (3I0)
A,pri
A,pri
12.64 A,sec
15.58 A,sec
18.06 A,sec
1102
894
1034
A,pri (3I0)
A,pri
A,pri
6.89 A,sec
5.59 A,sec
6.46 A,sec
ON
oo
NOT USED
oo
NOT USED
2.75
NOT USED
Set the phase fault detector at 50% of the lowest phase fault value.
Phase fault detector will be set below the current rating of the line.
Remote end protection transfer trip as well as Patnode Transformer and
230kV bus protection will initiate the low current breaker failure scheme at
Patnode. Fault contribution from Marble River Windfarm may fall below this
level and protection will rely on the low current scheme for proper operation.
Fault I (A,pri)=
EQUALS
894
2.79
TIMES
A,sec
0.5
2.75
440
A,sec
A,pri
EQUALS
oo
oo
NOT USED
oo
NOT USED
447 A,pri
RESIDUAL GROUND
04/10/12
75
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2102
DATE:
BKR 2102
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
ON
oo
NOT USED
oo
NOT USED
1.25
NOT USED
Set the ground fault detector at 20% of the line rating and check that it is
lower than expected ground fault.
Gnd fault detector setting of 40A primary is below expected Ph-gnd fault of
1034A 3I0.
Remote end protection transfer trip as well as Patnode Transformer and
230kV bus protection will initiate the low current breaker failure scheme at
Patnode. Marble River Windfarm is not a ground current source and the
protection will rely on the low current scheme for proper breaker failure
operation.
996
1.25
TIMES
A,sec
0.2
1.25
200
A,sec
A,pri
EQUALS
oo
oo
NOT USED
oo
NOT USED
199.2 A,pri
TIME SYNCHRONIZATION
IRIG B
Source
Fault Indication
Time Format
Offset to Signal
10 Min
mm/dd/yy
CFC CHART
See CFC Chart in Appendix for Breaker Failure Logic
04/10/12
76
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2102
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2102
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
7.700
2.040
0.900
0.240
0.030
3.000
2.400
0.240
0.900
3.000
0.000
0.000
0.000
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
Used for CFC Timer setting (Adjusted to achieve ~2 cyc safety margin)
T2 relay time to operate for a differential fault
Electroswitch standard speed LOR, 15mSec operate time (Per catalog)
76J6115 Input Pickup Time = 4ms (76J6115 Manual, page 299)
76J6115 Processor Scan Time = 0.5ms (Not published, typical used)
Local circuit breaker operate time (Per bkr. nameplate)
Fault Detector MAX dropout = 40ms (7SJ6115 Manual, Page 309)
76J6115 Published operate time = 4ms (Not published, typical used)
Electroswitch standard speed LOR, 15mSec operate time (Per catalog)
Local backup circuit breaker operate time
Transfer trip channel time - By NYPA
Transfer trip aux relay operate time - By NYPA
Assumed remote backup circuit breaker operate time - By NYPA
( ENTER '0' FOR 'RBCB' IF NO REMOTE BACKUP BREAKER (OR TT))
cyc
3/20/2012
62FC=
PR =
PRX =
DB =
PS =
CB =
FD =
BF =
BFX =
LBCB =
TT =
TTX =
RBCB =
62FC must provide enough time for breaker to trip normally or retrip
5.670
cyc
04/10/12
EQUALS
EQUALS
7.700 cyc
6.000 cyc
77
128.33 msec
100.00 msec
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2102
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2102
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
3/20/2012
APPENDIX:
04/10/12
78
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2102
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2102
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
3/20/2012
04/10/12
79
Rev. 0
PATNODE
50/62BFS/2102
04/10/12
80
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2102
DATE:
BKR 2102
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
Setting Password
5 min
30 min
5 min
Enabled
1.0 s
300 s
25%
Enabled
30 min
0.020 pu
1.0 V
04/10/12
81
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2102
DATE:
BKR 2102
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
Enabled
0.0 hr
Disabled
04/10/12
82
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2102
DATE:
BKR 2102
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
Number Of Records
Trigger Mode
5
Automatic Overwrite
Trigger Position
Trigger Source
30%
Osc Trigger On (VO64)
AC Input Waveforms
32 samples/cycle
Digital Channel 1
BFI On(H7A)
Digital Channel 2
Digital Channel 3
52a On(H8A)
Digital Channel 4
Digital Channel 5
Digital Channel 6
BKR FAIL 1 T1 OP
Digital Channel 7
BKR FAIL 2 T3 OP
Digital Channel 8
BFI/BFI/ LC On (VO1)
Digital Channel 9
BF RETRIP On (VO2)
Digital Channel 10
BF TRIP On (VO3)
Digital Channel 11
BF BYPASS On (VO4)
Digital Channel 12
LC RETRIP On (VO5)
Digital Channel 13
TRIPBUS 1 OP
Digital Channel 14
TRIPBUS 2 OP
Digital Channel 15
TRIPBUS 3 OP
Digital Channel 16 - 63
OFF
Analog Channel 1
SRC1
Ia RMS
Analog Channel 2
SRC1
Ib RMS
Analog Channel 3
SRC1
Ic RMS
Analog Channel 4 - 16
OFF
Continuous
OFF
Rate
60000 msec
04/10/12
Thermal Exponential
83
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2102
DATE:
BKR 2102
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
Power Method
Thermal Exponential
Interval
15 MIN
Trigger
OFF
Enabled
Enabled
Enabled
Disabled
Enabled
Enabled
Enabled
04/10/12
84
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2102
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2102
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
50/62BFS/2102
800 A
2000/800:5 CT
5A
1A
1A
60 Hz
Phase Rotation
ABC
04/10/12
SRC 1
SOURCE 1: Phase CT
F1
SOURCE 1: Ground CT
None
SOURCE 1: Phase VT
None
SOURCE 1: Auxiliary VT
None
SOURCE 2: Name
SRC 2
SOURCE 2: Phase CT
None
SOURCE 2: Ground CT
None
SOURCE 2: Phase VT
None
SOURCE 2: Auxiliary VT
None
85
DEFAULT VALUE
ASSIGN BKR CT AS SOURCE 1
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2102
DATE:
BKR 2102
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
04/10/12
FlexLogic Entry 1
BFI On(H7A)
FlexLogic Entry 2
FlexLogic Entry 3
OR(2)
FlexLogic Entry 4
BFI/BFI LC (VO1)
FlexLogic Entry 5
FlexLogic Entry 6
LC RETRIP On (VO5)
FlexLogic Entry 7
AND(2)
FlexLogic Entry 8
BF RETRIP (VO2)
FlexLogic Entry 9
BKR FAIL 1 T1 OP
FlexLogic Entry 10
BKR FAIL 2 T3 OP
FlexLogic Entry 11
OR(2)
FlexLogic Entry 12
BF TRIP (VO3)
FlexLogic Entry 13
FlexLogic Entry 14
BF RETRIP (VO2)
FlexLogic Entry 15
AND(2)
FlexLogic Entry 16
BF BYPASS (VO4)
FlexLogic Entry 17
TRIPBUS 1 OP
FlexLogic Entry 18
FlexLogic Entry 19
TRIPBUS 2 OP
FlexLogic Entry 20
FlexLogic Entry 21
TRIPBUS 3 OP
FlexLogic Entry 22
FlexLogic Entry 23
OR(3)
FlexLogic Entry 24
86
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2102
DATE:
BKR 2102
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
FlexLogic Entry 25
FlexLogic Entry 26
52a ON(H8A)
FlexLogic Entry 27
AND(2)
FlexLogic Entry 28
LC RETRIP (V05)
SPARE
FLEXLOGIC: FLEXELEMENTS
NOT USED - LEAVE AT DEFAULT
04/10/12
87
Rev. 0
STATION:
PATNODE
LINE:
RELAY:
FID:
ENG:
BKR 2102
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
DEVICE:
50/62BFS/2102
7.700
2.040
0.900
0.000
0.030
3.000
2.400
0.240
0.900
3.000
0.000
0.000
0.000
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
DATE:
3/20/2012
62FC=
PR =
PRX =
DB =
PS =
CB =
FD =
BF =
BFX =
LBCB =
TT =
TTX =
RBCB =
62FC must provide enough time for breaker to trip normally or retrip
5.670
cyc
FAULT VALUES:
CTR=
160
2000/800:5 CT
230kV Line Ratings (R102-11 Analysis to Confirm Non-Material Change for Marble River Wind Farm, Table 3-1)
WPN1 Line Rating=
04/10/12
996
88
A,pri
6.23 A,sec
1.25 A,pu
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2102
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2102
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
996
A,pri
6.23 A,sec
1.25 A,pu
Fault Information
All fault information is based on Aspen Oneliner Case: NYISO CY11. To
model a weak system the following were taken out of service: Noble Clinton
W.F., Chateaugay W.F., Noble Ellenburg W.F., Noble Altona W.F., Marble
River W.F. Additionally, The strongest source opposite the faulted station
was removed (ie, for a Duley the strongest source at Willis was removed.
The removed element is specified next to the fault table below.
2023
2492
2889
A,pri (3I0)
A,pri
A,pri
12.64 A,sec
15.58 A,sec
18.06 A,sec
2.53 A,pu
3.12 A,pu
3.61 A,pu
1102
894
1034
A,pri (3I0)
A,pri
A,pri
6.89 A,sec
5.59 A,sec
6.46 A,sec
1.38 A,pu
1.12 A,pu
1.29 A,pu
BF1: Function
3-Pole
BF1: Mode
BF1: Source
BF1: Current Supervision
Yes
No
No seal in
BFI/BFI LC On (VO1)
OFF
BF1: Block
No blocking of BFI
0.55 pu
Set the phase fault detector at 50% of the lowest phase fault value.
Phase fault detector will be set below the current rating of the line.
Remote end protection transfer trip as well as Patnode Transformer and
230kV bus protection will initiate the low current breaker failure scheme at
Patnode. Fault contribution from Marble River Windfarm may fall below this
level and protection will rely on the low current scheme for proper operation.
Fault I (A,pri)=
EQUALS
EQUALS
894
2.79
0.56
TIMES
A,sec
A,pu
0.5
0.55
440
A,pu
A,pri
EQUALS
447 A,pri
0.05 pu
Set the ground fault detector at 20% of the line rating and check that it is
04/10/12
89
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2102
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2102
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
996
1.25
0.25
TIMES
A,sec
A,pu
0.2
0.25
200
A,pu
A,pri
Yes
0.128 s
04/10/12
No
0.000 s
No
0.000 s
199.2 A,pri
EQUALS
7.700 cyc
0.128333 sec
NOT USED
REQUIRED ENTRY, NOT USED
NOT USED
REQUIRED ENTRY, NOT USED
ON
OFF
NOT USED
OFF
NOT USED
1.050 pu
1.050 pu
1.050 pu
1.050 pu
0.000 s
0.000 s
BF1: Target
Self-reset
BF1: Events
Enabled
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
90
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2102
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2102
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
Enabled
3-Pole
NOT USED
Enable function for low current BFI
Three pole tripping only
No
No
No seal in
No blocking of BFI
1.050 pu
1.050 pu
No
0.000 s
No
0.000 s
Yes
0.128 s
OFF
52a On(H8a)
04/10/12
OFF
OFF
NOT USED
REQUIRED SETTING, NOT USED
NOT USED
REQUIRED ENTRY, NOT USED
62BF, Low/NO current trip
Set same as BF1 T1
Not used
Used for breaker position supervision of low current BFI
NOT USED
1.050 pu
1.050 pu
1.050 pu
1.050 pu
0.000 s
0.000 s
BF2: Target
Self-reset
BF2: Events
Enabled
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
91
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2102
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2102
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
OFF
NOT USED
04/10/12
Enabled
OFF
NO BLOCK TRIP
0.00 s
NO PICK-UP DELAY
0.10 s
BF TRIP On (VO3)
SPARE
Disabled
OFF
Self-reset
92
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2102
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2102
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
Enabled
Enabled
OFF
NO BLOCK TRIP
0.00 s
NO PICK-UP DELAY
0.10 s
BF RETRIP ON (VO2)
SPARE
Disabled
OFF
Self-reset
Enabled
Enabled
OFF
NO BLOCK TRIP
0.00 s
NO PICK-UP DELAY
0.10 s
BF BYPASS On (VO4)
SPARE
Disabled
OFF
Self-reset
Enabled
SPARE
04/10/12
93
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2102
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2102
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
BFI
BFI INITIATE
0 ms
Enabled
BFI LOW CURR BF OC BY-PASS
0 ms
Enabled
52a
52a
0 ms
Enabled
LOW GAS
0 ms
Enabled
[M7A] - [M8C]
SPARE
BF LOW GAS
Debounce set to 0ms
04/10/12
94
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2102
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2102
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
Cont 1p 1 - Cont Ip 4
84 Vdc
Cont 1p 5 - Cont Ip 8
84 Vdc
Cont Op 1
TRIPBUS 1 OP
OFF
Enabled
Cont Op 2
TRIPBUS 2 OP
OFF
Enabled
Cont Op 3
TRIPBUS 3 OP
OFF
Enabled
[H4] - [H6]
SPARE
[M1] - [M6]
SPARE
Enabled
BF RETRIP
Enabled
Virtual Output 3 ID
BF TRIP
Enabled
Virtual Output 4 ID
Virtual Output 4 Events
Virtual Output 5
Virtual Output 5 Events
04/10/12
BFI/BFI LC
BF BYPASS
Enabled
LC RETRIP
Enabled
95
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2102
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2102
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
SPARE
Virtual Output 64 ID
Osc Trigger
Enabled
Virtual Output 65 - 96
SPARE
INPUTS/OUTPUTS: RESETTING
NOT USED - LEAVE AT DEFAULT
INPUTS/OUTPUTS: TELEPROTECTION
NOT USED - LEAVE AT DEFAULT
04/10/12
96
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2102
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2102
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
APPENDIX:
Flex Logic Diagram for C60
04/10/12
97
Rev. 0
PATNODE
50/62BFP/2108
04/10/12
98
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2108
DATE:
BKR 2108
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
DEVICE CONFIGURATION
0103 Setting Group Change Option
Disabled
Enabled
NOT USED
0112 50/51
0113 50N/51N
0127 50 1Ph
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Binary Input 1
Type
Conf.
BF initiation
SP
H
SPARE
Binary Input 2
Type
Conf.
Binary Input 3
Type
Conf.
Binary Input 4
Type
Conf.
BFI + 52a
SP
H
Low Gas Detection
SP
H
No current BF initiation
SPARE
Binary Input 5
Type
Conf.
SPARE
Binary Input 6
Type
Conf.
SPARE
Binary Input 7
Type
Conf.
SPARE
Binary Input 8
Type
04/10/12
99
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2108
DATE:
BKR 2108
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
Conf.
BF trip of bkr.
RETRIP
OUT
U
Retrip of bkr.
Type
Conf.
BF BYPASS
OUT
U
Type
Conf.
Binary Output 2
Binary Output 3
SPARE
Binary Output 4
Type
Conf.
SPARE
Binary Output 5
Type
Conf.
SPARE
Binary Output 6
Type
Conf.
SPARE
Binary Output 7
Type
Conf.
SPARE
Binary Output 8
Type
Conf.
CONFIGURATION: LEDS
LED 1
Type
Conf.
LED 2
Type
Conf.
BFI + 52a
SP
L
Type
Conf.
A ph BFT LED
OUT
L
Type
Conf.
B ph BFT LED
OUT
L
Type
Conf.
C ph BFT LED
OUT
L
Type
Conf.
LED 3
LED 4
LED 5
LED 6
04/10/12
100
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2108
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2108
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
3/20/2012
LED 7
Type
Conf.
INTERFACE: VD ADDRESSES
VD Address
SIPROTEC SYS VD Address
Proxy VD Address
SIPROTEC T103 VD Address
04/10/12
101
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2108
DATE:
BKR 2108
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
Baud Rate
Max gap
IP Address
Subnet Mask
Link Layer
Access Authorization
Access Rights
Image 1
60hz
ABC
Degr. F
Towards Bus
0201 CT Starpoint
0235A Storage
NO
OFF
Ignd(meas.)
800
800
0.10s
1.00s
0.50A
Fault Values:
CTR=
160
2000/800:5 CT
230kV Line Ratings (R102-11 Analysis to Confirm Non-Material Change for Marble River Wind Farm, Table 3-1)
04/10/12
102
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2108
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2108
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
3/20/2012
996
A,pri
6.23 A,sec
996
A,pri
6.23 A,sec
Fault Information
All fault information is based on Aspen Oneliner Case: NYISO CY11. To
model a weak system the following were taken out of service: Noble Clinton
W.F., Chateaugay W.F., Noble Ellenburg W.F., Noble Altona W.F., Marble
River W.F. Additionally, The strongest source opposite the faulted station
was removed (ie, for a Duley the strongest source at Willis was removed.
The removed element is specified next to the fault table below.
2023
2492
2889
A,pri (3I0)
A,pri
A,pri
12.64 A,sec
15.58 A,sec
18.06 A,sec
1102
894
1034
A,pri (3I0)
A,pri
A,pri
6.89 A,sec
5.59 A,sec
6.46 A,sec
ON
oo
NOT USED
oo
NOT USED
2.75
NOT USED
Set the phase fault detector at 50% of the lowest phase fault value.
Phase fault detector will be set below the current rating of the line.
Remote end protection transfer trip as well as Patnode Transformer and
230kV bus protection will initiate the low current breaker failure scheme at
Patnode. Fault contribution from Marble River Windfarm may fall below this
level and protection will rely on the low current scheme for proper operation.
Fault I (A,pri)=
EQUALS
894
2.79
TIMES
A,sec
0.5
2.75
440
A,sec
A,pri
EQUALS
oo
oo
NOT USED
oo
NOT USED
447 A,pri
RESIDUAL GROUND
04/10/12
103
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2108
DATE:
BKR 2108
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
ON
oo
NOT USED
oo
NOT USED
1.25
NOT USED
Set the ground fault detector at 20% of the line rating and check that it is
lower than expected ground fault.
Gnd fault detector setting of 40A primary is below expected Ph-gnd fault of
1034A 3I0.
Remote end protection transfer trip as well as Patnode Transformer and
230kV bus protection will initiate the low current breaker failure scheme at
Patnode. Marble River Windfarm is not a ground current source and the
protection will rely on the low current scheme for proper breaker failure
operation.
996
1.25
TIMES
A,sec
0.2
1.25
200
A,sec
A,pri
EQUALS
oo
oo
NOT USED
oo
NOT USED
199.2 A,pri
TIME SYNCHRONIZATION
IRIG B
Source
Fault Indication
Time Format
Offset to Signal
10 Min
mm/dd/yy
CFC CHART
See CFC Chart in Appendix for Breaker Failure Logic
04/10/12
104
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2108
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2108
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
7.700
2.040
0.900
0.240
0.030
3.000
2.400
0.240
0.900
3.000
0.000
0.000
0.000
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
Used for CFC Timer setting (Adjusted to achieve ~2 cyc safety margin)
T2 relay time to operate for a differential fault
Electroswitch standard speed LOR, 15mSec operate time (Per catalog)
76J6115 Input Pickup Time = 4ms (76J6115 Manual, page 299)
76J6115 Processor Scan Time = 0.5ms (Not published, typical used)
Local circuit breaker operate time (Per bkr. nameplate)
Fault Detector MAX dropout = 40ms (7SJ6115 Manual, Page 309)
76J6115 Published operate time = 4ms (Not published, typical used)
Electroswitch standard speed LOR, 15mSec operate time (Per catalog)
Local backup circuit breaker operate time
Transfer trip channel time - By NYPA
Transfer trip aux relay operate time - By NYPA
Assumed remote backup circuit breaker operate time - By NYPA
( ENTER '0' FOR 'RBCB' IF NO REMOTE BACKUP BREAKER (OR TT))
cyc
3/20/2012
62FC=
PR =
PRX =
DB =
PS =
CB =
FD =
BF =
BFX =
LBCB =
TT =
TTX =
RBCB =
62FC must provide enough time for breaker to trip normally or retrip
5.670
cyc
04/10/12
EQUALS
EQUALS
7.700 cyc
6.000 cyc
105
128.33 msec
100.00 msec
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2108
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2108
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
3/20/2012
APPENDIX:
04/10/12
106
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2108
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2108
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
3/20/2012
04/10/12
107
Rev. 0
PATNODE
50/62BFS/2108
04/10/12
108
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2108
DATE:
BKR 2108
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
Setting Password
5 min
30 min
5 min
Enabled
1.0 s
300 s
25%
Enabled
30 min
0.020 pu
1.0 V
04/10/12
109
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2108
DATE:
BKR 2108
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
Enabled
0.0 hr
Disabled
04/10/12
110
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2108
DATE:
BKR 2108
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
Number Of Records
Trigger Mode
5
Automatic Overwrite
Trigger Position
Trigger Source
30%
Osc Trigger On (VO64)
AC Input Waveforms
32 samples/cycle
Digital Channel 1
BFI On(H7A)
Digital Channel 2
Digital Channel 3
52a On(H8A)
Digital Channel 4
Digital Channel 5
Digital Channel 6
BKR FAIL 1 T1 OP
Digital Channel 7
BKR FAIL 2 T3 OP
Digital Channel 8
BFI/BFI/ LC On (VO1)
Digital Channel 9
BF RETRIP On (VO2)
Digital Channel 10
BF TRIP On (VO3)
Digital Channel 11
BF BYPASS On (VO4)
Digital Channel 12
LC RETRIP On (VO5)
Digital Channel 13
TRIPBUS 1 OP
Digital Channel 14
TRIPBUS 2 OP
Digital Channel 15
TRIPBUS 3 OP
Digital Channel 16 - 63
OFF
Analog Channel 1
SRC1
Ia RMS
Analog Channel 2
SRC1
Ib RMS
Analog Channel 3
SRC1
Ic RMS
Analog Channel 4 - 16
OFF
Continuous
OFF
Rate
60000 msec
04/10/12
Thermal Exponential
111
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2108
DATE:
BKR 2108
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
Power Method
Thermal Exponential
Interval
15 MIN
Trigger
OFF
Enabled
Enabled
Enabled
Disabled
Enabled
Enabled
Enabled
04/10/12
112
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2108
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2108
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
50/62BFS/2108
800 A
2000/800:5 CT
5A
1A
1A
60 Hz
Phase Rotation
ABC
04/10/12
SRC 1
SOURCE 1: Phase CT
F1
SOURCE 1: Ground CT
None
SOURCE 1: Phase VT
None
SOURCE 1: Auxiliary VT
None
SOURCE 2: Name
SRC 2
SOURCE 2: Phase CT
None
SOURCE 2: Ground CT
None
SOURCE 2: Phase VT
None
SOURCE 2: Auxiliary VT
None
113
DEFAULT VALUE
ASSIGN BKR CT AS SOURCE 1
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2108
DATE:
BKR 2108
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
04/10/12
FlexLogic Entry 1
BFI On(H7A)
FlexLogic Entry 2
FlexLogic Entry 3
OR(2)
FlexLogic Entry 4
BFI/BFI LC (VO1)
FlexLogic Entry 5
FlexLogic Entry 6
LC RETRIP On (VO5)
FlexLogic Entry 7
AND(2)
FlexLogic Entry 8
BF RETRIP (VO2)
FlexLogic Entry 9
BKR FAIL 1 T1 OP
FlexLogic Entry 10
BKR FAIL 2 T3 OP
FlexLogic Entry 11
OR(2)
FlexLogic Entry 12
BF TRIP (VO3)
FlexLogic Entry 13
FlexLogic Entry 14
BF RETRIP (VO2)
FlexLogic Entry 15
AND(2)
FlexLogic Entry 16
BF BYPASS (VO4)
FlexLogic Entry 17
TRIPBUS 1 OP
FlexLogic Entry 18
FlexLogic Entry 19
TRIPBUS 2 OP
FlexLogic Entry 20
FlexLogic Entry 21
TRIPBUS 3 OP
FlexLogic Entry 22
FlexLogic Entry 23
OR(3)
FlexLogic Entry 24
114
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2108
DATE:
BKR 2108
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
FlexLogic Entry 25
FlexLogic Entry 26
52a ON(H8A)
FlexLogic Entry 27
AND(2)
FlexLogic Entry 28
LC RETRIP (V05)
SPARE
FLEXLOGIC: FLEXELEMENTS
NOT USED - LEAVE AT DEFAULT
04/10/12
115
Rev. 0
STATION:
PATNODE
LINE:
RELAY:
FID:
ENG:
BKR 2108
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
DEVICE:
50/62BFS/2108
7.700
2.040
0.900
0.000
0.030
3.000
2.400
0.240
0.900
3.000
0.000
0.000
0.000
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
DATE:
3/20/2012
62FC=
PR =
PRX =
DB =
PS =
CB =
FD =
BF =
BFX =
LBCB =
TT =
TTX =
RBCB =
62FC must provide enough time for breaker to trip normally or retrip
5.670
cyc
FAULT VALUES:
CTR=
160
2000/800:5 CT
230kV Line Ratings (R102-11 Analysis to Confirm Non-Material Change for Marble River Wind Farm, Table 3-1)
WPN1 Line Rating=
04/10/12
996
116
A,pri
6.23 A,sec
1.25 A,pu
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2108
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2108
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
996
A,pri
6.23 A,sec
1.25 A,pu
Fault Information
All fault information is based on Aspen Oneliner Case: NYISO CY11. To
model a weak system the following were taken out of service: Noble Clinton
W.F., Chateaugay W.F., Noble Ellenburg W.F., Noble Altona W.F., Marble
River W.F. Additionally, The strongest source opposite the faulted station
was removed (ie, for a Duley the strongest source at Willis was removed.
The removed element is specified next to the fault table below.
2023
2492
2889
A,pri (3I0)
A,pri
A,pri
12.64 A,sec
15.58 A,sec
18.06 A,sec
2.53 A,pu
3.12 A,pu
3.61 A,pu
1102
894
1034
A,pri (3I0)
A,pri
A,pri
6.89 A,sec
5.59 A,sec
6.46 A,sec
1.38 A,pu
1.12 A,pu
1.29 A,pu
BF1: Function
3-Pole
BF1: Mode
BF1: Source
BF1: Current Supervision
Yes
No
No seal in
BFI/BFI LC On (VO1)
OFF
BF1: Block
No blocking of BFI
0.55 pu
Set the phase fault detector at 50% of the lowest phase fault value.
Phase fault detector will be set below the current rating of the line.
Remote end protection transfer trip as well as Patnode Transformer and
230kV bus protection will initiate the low current breaker failure scheme at
Patnode. Fault contribution from Marble River Windfarm may fall below this
level and protection will rely on the low current scheme for proper operation.
Fault I (A,pri)=
EQUALS
EQUALS
894
2.79
0.56
TIMES
A,sec
A,pu
0.5
0.55
440
A,pu
A,pri
EQUALS
447 A,pri
0.25pu
Set the ground fault detector at 20% of the line rating and check that it is
04/10/12
117
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2108
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2108
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
996
1.25
0.25
TIMES
A,sec
A,pu
0.2
0.25
200
A,pu
A,pri
Yes
0.128 s
04/10/12
No
0.000 s
No
0.000 s
199.2 A,pri
EQUALS
7.700 cyc
0.128333 sec
NOT USED
REQUIRED ENTRY, NOT USED
NOT USED
REQUIRED ENTRY, NOT USED
ON
OFF
NOT USED
OFF
NOT USED
1.050 pu
1.050 pu
1.050 pu
1.050 pu
0.000 s
0.000 s
BF1: Target
Self-reset
BF1: Events
Enabled
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
118
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2108
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2108
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
Enabled
3-Pole
NOT USED
Enable function for low current BFI
Three pole tripping only
No
No
No seal in
No blocking of BFI
1.050 pu
1.050 pu
No
0.000 s
No
0.000 s
Yes
0.128 s
OFF
52a On(H8a)
04/10/12
OFF
OFF
NOT USED
REQUIRED SETTING, NOT USED
NOT USED
REQUIRED ENTRY, NOT USED
62BF, Low/NO current trip
Set same as BF1 T1
Not used
Used for breaker position supervision of low current BFI
NOT USED
1.050 pu
1.050 pu
1.050 pu
1.050 pu
0.000 s
0.000 s
BF2: Target
Self-reset
BF2: Events
Enabled
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
119
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2108
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2108
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
OFF
NOT USED
04/10/12
Enabled
OFF
NO BLOCK TRIP
0.00 s
NO PICK-UP DELAY
0.10 s
BF TRIP On (VO3)
SPARE
Disabled
OFF
Self-reset
120
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2108
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2108
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
Enabled
Enabled
OFF
NO BLOCK TRIP
0.00 s
NO PICK-UP DELAY
0.10 s
BF RETRIP ON (VO2)
SPARE
Disabled
OFF
Self-reset
Enabled
Enabled
OFF
NO BLOCK TRIP
0.00 s
NO PICK-UP DELAY
0.10 s
BF BYPASS On (VO4)
SPARE
Disabled
OFF
Self-reset
Enabled
SPARE
04/10/12
121
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2108
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2108
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
BFI
BFI INITIATE
0 ms
Enabled
BFI LOW CURR BF OC BY-PASS
0 ms
Enabled
52a
52a
0 ms
Enabled
LOW GAS
0 ms
Enabled
[M7A] - [M8C]
SPARE
BF LOW GAS
Debounce set to 0ms
04/10/12
122
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2108
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2108
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
Cont 1p 1 - Cont Ip 4
84 Vdc
Cont 1p 5 - Cont Ip 8
84 Vdc
Cont Op 1
TRIPBUS 1 OP
OFF
Enabled
Cont Op 2
TRIPBUS 2 OP
OFF
Enabled
Cont Op 3
TRIPBUS 3 OP
OFF
Enabled
[H4] - [H6]
SPARE
[M1] - [M6]
SPARE
Enabled
BF RETRIP
Enabled
Virtual Output 3 ID
BF TRIP
Enabled
Virtual Output 4 ID
Virtual Output 4 Events
Virtual Output 5
Virtual Output 5 Events
04/10/12
BFI/BFI LC
BF BYPASS
Enabled
LC RETRIP
Enabled
123
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2108
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2108
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
SPARE
Virtual Output 64 ID
Osc Trigger
Enabled
Virtual Output 65 - 96
SPARE
INPUTS/OUTPUTS: RESETTING
NOT USED - LEAVE AT DEFAULT
INPUTS/OUTPUTS: TELEPROTECTION
NOT USED - LEAVE AT DEFAULT
04/10/12
124
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2108
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2108
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
APPENDIX:
Flex Logic Diagram for C60
04/10/12
125
Rev. 0
PATNODE
50/62BFP/2114
04/10/12
126
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2114
DATE:
BKR 2114
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
DEVICE CONFIGURATION
0103 Setting Group Change Option
Disabled
Enabled
NOT USED
0112 50/51
0113 50N/51N
0127 50 1Ph
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Disabled
NOT USED
Binary Input 1
Type
Conf.
BF initiation
SP
H
SPARE
Binary Input 2
Type
Conf.
Binary Input 3
Type
Conf.
Binary Input 4
Type
Conf.
BFI + 52a
SP
H
Low Gas Detection
SP
H
No current BF initiation
SPARE
Binary Input 5
Type
Conf.
SPARE
Binary Input 6
Type
Conf.
SPARE
Binary Input 7
Type
Conf.
SPARE
Binary Input 8
Type
04/10/12
127
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2114
DATE:
BKR 2114
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
Conf.
BF trip of bkr.
RETRIP
OUT
U
Retrip of bkr.
Type
Conf.
BF BYPASS
OUT
U
Type
Conf.
Binary Output 2
Binary Output 3
SPARE
Binary Output 4
Type
Conf.
SPARE
Binary Output 5
Type
Conf.
SPARE
Binary Output 6
Type
Conf.
SPARE
Binary Output 7
Type
Conf.
SPARE
Binary Output 8
Type
Conf.
CONFIGURATION: LEDS
LED 1
Type
Conf.
LED 2
Type
Conf.
BFI + 52a
SP
L
Type
Conf.
A ph BFT LED
OUT
L
Type
Conf.
B ph BFT LED
OUT
L
Type
Conf.
C ph BFT LED
OUT
L
Type
Conf.
LED 3
LED 4
LED 5
LED 6
04/10/12
128
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2114
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2114
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
3/20/2012
LED 7
Type
Conf.
INTERFACE: VD ADDRESSES
VD Address
SIPROTEC SYS VD Address
Proxy VD Address
SIPROTEC T103 VD Address
04/10/12
129
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2114
DATE:
BKR 2114
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
Baud Rate
Max gap
IP Address
Subnet Mask
Link Layer
Access Authorization
Access Rights
Image 1
60hz
ABC
Degr. F
Towards Bus
0201 CT Starpoint
0235A Storage
NO
OFF
Ignd(meas.)
800
800
0.10s
1.00s
0.50A
Fault Values:
CTR=
160
2000/800:5 CT
230kV Line Ratings (R102-11 Analysis to Confirm Non-Material Change for Marble River Wind Farm, Table 3-1)
04/10/12
130
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2114
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2114
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
3/20/2012
996
A,pri
6.23 A,sec
996
A,pri
6.23 A,sec
Fault Information
All fault information is based on Aspen Oneliner Case: NYISO CY11. To
model a weak system the following were taken out of service: Noble Clinton
W.F., Chateaugay W.F., Noble Ellenburg W.F., Noble Altona W.F., Marble
River W.F. Additionally, The strongest source opposite the faulted station
was removed (ie, for a Duley the strongest source at Willis was removed.
The removed element is specified next to the fault table below.
2023
2492
2889
A,pri (3I0)
A,pri
A,pri
12.64 A,sec
15.58 A,sec
18.06 A,sec
1102
894
1034
A,pri (3I0)
A,pri
A,pri
6.89 A,sec
5.59 A,sec
6.46 A,sec
ON
oo
NOT USED
oo
NOT USED
2.75
NOT USED
Set the phase fault detector at 50% of the lowest phase fault value.
Phase fault detector will be set below the current rating of the line.
Remote end protection transfer trip as well as Patnode Transformer and
230kV bus protection will initiate the low current breaker failure scheme at
Patnode. Fault contribution from Marble River Windfarm may fall below this
level and protection will rely on the low current scheme for proper operation.
Fault I (A,pri)=
EQUALS
894
2.79
TIMES
A,sec
0.5
2.75
440
A,sec
A,pri
EQUALS
oo
oo
NOT USED
oo
NOT USED
447 A,pri
RESIDUAL GROUND
04/10/12
131
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2114
DATE:
BKR 2114
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
ON
oo
NOT USED
oo
NOT USED
1.25
NOT USED
Set the ground fault detector at 20% of the line rating and check that it is
lower than expected ground fault.
Gnd fault detector setting of 40A primary is below expected Ph-gnd fault of
1034A 3I0.
Remote end protection transfer trip as well as Patnode Transformer and
230kV bus protection will initiate the low current breaker failure scheme at
Patnode. Marble River Windfarm is not a ground current source and the
protection will rely on the low current scheme for proper breaker failure
operation.
996
1.25
TIMES
A,sec
0.2
1.25
200
A,sec
A,pri
EQUALS
oo
oo
NOT USED
oo
NOT USED
199.2 A,pri
TIME SYNCHRONIZATION
IRIG B
Source
Fault Indication
Time Format
Offset to Signal
10 Min
mm/dd/yy
CFC CHART
See CFC Chart in Appendix for Breaker Failure Logic
04/10/12
132
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2114
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2114
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
7.700
2.040
0.900
0.240
0.030
3.000
2.400
0.240
0.900
3.000
0.000
0.000
0.000
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
Used for CFC Timer setting (Adjusted to achieve ~2 cyc safety margin)
T2 relay time to operate for a differential fault
Electroswitch standard speed LOR, 15mSec operate time (Per catalog)
76J6115 Input Pickup Time = 4ms (76J6115 Manual, page 299)
76J6115 Processor Scan Time = 0.5ms (Not published, typical used)
Local circuit breaker operate time (Per bkr. nameplate)
Fault Detector MAX dropout = 40ms (7SJ6115 Manual, Page 309)
76J6115 Published operate time = 4ms (Not published, typical used)
Electroswitch standard speed LOR, 15mSec operate time (Per catalog)
Local backup circuit breaker operate time
Transfer trip channel time - By NYPA
Transfer trip aux relay operate time - By NYPA
Assumed remote backup circuit breaker operate time - By NYPA
( ENTER '0' FOR 'RBCB' IF NO REMOTE BACKUP BREAKER (OR TT))
cyc
3/20/2012
62FC=
PR =
PRX =
DB =
PS =
CB =
FD =
BF =
BFX =
LBCB =
TT =
TTX =
RBCB =
62FC must provide enough time for breaker to trip normally or retrip
5.670
cyc
04/10/12
EQUALS
EQUALS
7.700 cyc
6.000 cyc
133
128.33 msec
100.00 msec
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2114
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2114
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
3/20/2012
APPENDIX:
04/10/12
134
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFP/2114
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2114
7SJ6115-4DC11-1FA1
V04.71.04
JK/TRC
3/20/2012
04/10/12
135
Rev. 0
PATNODE
50/62BFS/2114
04/10/12
136
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2114
DATE:
BKR 2114
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
Setting Password
5 min
30 min
5 min
Enabled
1.0 s
300 s
25%
Enabled
30 min
0.020 pu
1.0 V
04/10/12
137
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2114
DATE:
BKR 2114
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
Enabled
0.0 hr
Disabled
04/10/12
138
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2114
DATE:
BKR 2114
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
Number Of Records
Trigger Mode
5
Automatic Overwrite
Trigger Position
Trigger Source
30%
Osc Trigger On (VO64)
AC Input Waveforms
32 samples/cycle
Digital Channel 1
BFI On(H7A)
Digital Channel 2
Digital Channel 3
52a On(H8A)
Digital Channel 4
Digital Channel 5
Digital Channel 6
BKR FAIL 1 T1 OP
Digital Channel 7
BKR FAIL 2 T3 OP
Digital Channel 8
BFI/BFI/ LC On (VO1)
Digital Channel 9
BF RETRIP On (VO2)
Digital Channel 10
BF TRIP On (VO3)
Digital Channel 11
BF BYPASS On (VO4)
Digital Channel 12
LC RETRIP On (VO5)
Digital Channel 13
TRIPBUS 1 OP
Digital Channel 14
TRIPBUS 2 OP
Digital Channel 15
TRIPBUS 3 OP
Digital Channel 16 - 63
OFF
Analog Channel 1
SRC1
Ia RMS
Analog Channel 2
SRC1
Ib RMS
Analog Channel 3
SRC1
Ic RMS
Analog Channel 4 - 16
OFF
Continuous
OFF
Rate
60000 msec
04/10/12
Thermal Exponential
139
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2114
DATE:
BKR 2114
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
Power Method
Thermal Exponential
Interval
15 MIN
Trigger
OFF
Enabled
Enabled
Enabled
Disabled
Enabled
Enabled
Enabled
04/10/12
140
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2114
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2114
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
50/62BFS/2114
800 A
2000/800:5 CT
5A
1A
1A
60 Hz
Phase Rotation
ABC
04/10/12
SRC 1
SOURCE 1: Phase CT
F1
SOURCE 1: Ground CT
None
SOURCE 1: Phase VT
None
SOURCE 1: Auxiliary VT
None
SOURCE 2: Name
SRC 2
SOURCE 2: Phase CT
None
SOURCE 2: Ground CT
None
SOURCE 2: Phase VT
None
SOURCE 2: Auxiliary VT
None
141
DEFAULT VALUE
ASSIGN BKR CT AS SOURCE 1
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2114
DATE:
BKR 2114
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
04/10/12
FlexLogic Entry 1
BFI On(H7A)
FlexLogic Entry 2
FlexLogic Entry 3
OR(2)
FlexLogic Entry 4
BFI/BFI LC (VO1)
FlexLogic Entry 5
FlexLogic Entry 6
LC RETRIP On (VO5)
FlexLogic Entry 7
AND(2)
FlexLogic Entry 8
BF RETRIP (VO2)
FlexLogic Entry 9
BKR FAIL 1 T1 OP
FlexLogic Entry 10
BKR FAIL 2 T3 OP
FlexLogic Entry 11
OR(2)
FlexLogic Entry 12
BF TRIP (VO3)
FlexLogic Entry 13
FlexLogic Entry 14
BF RETRIP (VO2)
FlexLogic Entry 15
AND(2)
FlexLogic Entry 16
BF BYPASS (VO4)
FlexLogic Entry 17
TRIPBUS 1 OP
FlexLogic Entry 18
FlexLogic Entry 19
TRIPBUS 2 OP
FlexLogic Entry 20
FlexLogic Entry 21
TRIPBUS 3 OP
FlexLogic Entry 22
FlexLogic Entry 23
OR(3)
FlexLogic Entry 24
142
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2114
DATE:
BKR 2114
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
LINE:
RELAY:
FID:
ENG:
3/20/2012
FlexLogic Entry 25
FlexLogic Entry 26
52a ON(H8A)
FlexLogic Entry 27
AND(2)
FlexLogic Entry 28
LC RETRIP (V05)
SPARE
FLEXLOGIC: FLEXELEMENTS
NOT USED - LEAVE AT DEFAULT
04/10/12
143
Rev. 0
STATION:
PATNODE
LINE:
RELAY:
FID:
ENG:
BKR 2114
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
DEVICE:
50/62BFS/2114
7.700
2.040
0.900
0.000
0.030
3.000
2.400
0.240
0.900
3.000
0.000
0.000
0.000
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
cyc
DATE:
3/20/2012
62FC=
PR =
PRX =
DB =
PS =
CB =
FD =
BF =
BFX =
LBCB =
TT =
TTX =
RBCB =
62FC must provide enough time for breaker to trip normally or retrip
5.670
cyc
FAULT VALUES:
CTR=
160
2000/800:5 CT
230kV Line Ratings (R102-11 Analysis to Confirm Non-Material Change for Marble River Wind Farm, Table 3-1)
WPN1 Line Rating=
04/10/12
996
144
A,pri
6.23 A,sec
1.25 A,pu
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2114
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2114
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
996
A,pri
6.23 A,sec
1.25 A,pu
Fault Information
All fault information is based on Aspen Oneliner Case: NYISO CY11. To
model a weak system the following were taken out of service: Noble Clinton
W.F., Chateaugay W.F., Noble Ellenburg W.F., Noble Altona W.F., Marble
River W.F. Additionally, The strongest source opposite the faulted station
was removed (ie, for a Duley the strongest source at Willis was removed.
The removed element is specified next to the fault table below.
2023
2492
2889
A,pri (3I0)
A,pri
A,pri
12.64 A,sec
15.58 A,sec
18.06 A,sec
2.53 A,pu
3.12 A,pu
3.61 A,pu
1102
894
1034
A,pri (3I0)
A,pri
A,pri
6.89 A,sec
5.59 A,sec
6.46 A,sec
1.38 A,pu
1.12 A,pu
1.29 A,pu
BF1: Function
3-Pole
BF1: Mode
BF1: Source
BF1: Current Supervision
Yes
No
No seal in
BFI/BFI LC On (VO1)
OFF
BF1: Block
No blocking of BFI
0.55 pu
Set the phase fault detector at 50% of the lowest phase fault value.
Phase fault detector will be set below the current rating of the line.
Remote end protection transfer trip as well as Patnode Transformer and
230kV bus protection will initiate the low current breaker failure scheme at
Patnode. Fault contribution from Marble River Windfarm may fall below this
level and protection will rely on the low current scheme for proper operation.
Fault I (A,pri)=
EQUALS
EQUALS
894
2.79
0.56
TIMES
A,sec
A,pu
0.5
0.55
440
A,pu
A,pri
EQUALS
447 A,pri
0.05 pu
Set the ground fault detector at 20% of the line rating and check that it is
04/10/12
145
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2114
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2114
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
996
1.25
0.25
TIMES
A,sec
A,pu
0.2
0.25
200
A,pu
A,pri
Yes
0.128 s
04/10/12
No
0.000 s
No
0.000 s
199.2 A,pri
EQUALS
7.700 cyc
0.128333 sec
NOT USED
REQUIRED ENTRY, NOT USED
NOT USED
REQUIRED ENTRY, NOT USED
ON
OFF
NOT USED
OFF
NOT USED
1.050 pu
1.050 pu
1.050 pu
1.050 pu
0.000 s
0.000 s
BF1: Target
Self-reset
BF1: Events
Enabled
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
146
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2114
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2114
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
Enabled
3-Pole
NOT USED
Enable function for low current BFI
Three pole tripping only
No
No
No seal in
No blocking of BFI
1.050 pu
1.050 pu
No
0.000 s
No
0.000 s
Yes
0.128 s
OFF
52a On(H8a)
04/10/12
OFF
OFF
NOT USED
REQUIRED SETTING, NOT USED
NOT USED
REQUIRED ENTRY, NOT USED
62BF, Low/NO current trip
Set same as BF1 T1
Not used
Used for breaker position supervision of low current BFI
NOT USED
1.050 pu
1.050 pu
1.050 pu
1.050 pu
0.000 s
0.000 s
BF2: Target
Self-reset
BF2: Events
Enabled
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
OFF
NOT USED
147
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2114
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2114
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
OFF
NOT USED
04/10/12
Enabled
OFF
NO BLOCK TRIP
0.00 s
NO PICK-UP DELAY
0.10 s
BF TRIP On (VO3)
SPARE
Disabled
OFF
Self-reset
148
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2114
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2114
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
Enabled
Enabled
OFF
NO BLOCK TRIP
0.00 s
NO PICK-UP DELAY
0.10 s
BF RETRIP ON (VO2)
SPARE
Disabled
OFF
Self-reset
Enabled
Enabled
OFF
NO BLOCK TRIP
0.00 s
NO PICK-UP DELAY
0.10 s
BF BYPASS On (VO4)
SPARE
Disabled
OFF
Self-reset
Enabled
SPARE
04/10/12
149
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2114
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2114
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
BFI
BFI INITIATE
0 ms
Enabled
BFI LOW CURR BF OC BY-PASS
0 ms
Enabled
52a
52a
0 ms
Enabled
LOW GAS
0 ms
Enabled
[M7A] - [M8C]
SPARE
BF LOW GAS
Debounce set to 0ms
04/10/12
150
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2114
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2114
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
Cont 1p 1 - Cont Ip 4
84 Vdc
Cont 1p 5 - Cont Ip 8
84 Vdc
Cont Op 1
TRIPBUS 1 OP
OFF
Enabled
Cont Op 2
TRIPBUS 2 OP
OFF
Enabled
Cont Op 3
TRIPBUS 3 OP
OFF
Enabled
[H4] - [H6]
SPARE
[M1] - [M6]
SPARE
Enabled
BF RETRIP
Enabled
Virtual Output 3 ID
BF TRIP
Enabled
Virtual Output 4 ID
Virtual Output 4 Events
Virtual Output 5
Virtual Output 5 Events
04/10/12
BFI/BFI LC
BF BYPASS
Enabled
LC RETRIP
Enabled
151
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2114
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2114
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
SPARE
Virtual Output 64 ID
Osc Trigger
Enabled
Virtual Output 65 - 96
SPARE
INPUTS/OUTPUTS: RESETTING
NOT USED - LEAVE AT DEFAULT
INPUTS/OUTPUTS: TELEPROTECTION
NOT USED - LEAVE AT DEFAULT
04/10/12
152
Rev. 0
STATION:
PATNODE
DEVICE:
50/62BFS/2114
DATE:
LINE:
RELAY:
FID:
ENG:
BKR 2114
C60-N03-VFH-F8F-H6P-M6M-R7A
5.5x
JK/TRC
3/20/2012
APPENDIX:
Flex Logic Diagram for C60
04/10/12
153
Rev. 0
04/10/12
154
Rev. 0
WILLIS230kV
10s withHB/DL
2302
2314
15s withSync
WPN1
20s withSync
79RS/WPN1 inPos.3
15s withSync
10s withLL/DB
79RS/PND1 inPos.4
15s withSync
2102
2108
2114
PATNODE 230kV
PND1
20s withSync
15s withSync
2102
2108
2114
DP1
DULEY 230kV
Notes:
ReclosingatWillisandDuley areoutsideofTRCscopeofwork
SequenceandtimesprovidedbyNYPA
NormalsystemoperationistoreclosefromWesttoEast(WillistoPatnode toDuley)
79RS switchescanbeoperatedtochangereclosingsequence
04/10/12
155
Rev. 0
STATION:
PATNODE
DEVICE:
25/27/2102
DATE:
LINE:
RELAY:
FID:
ENG:
2102
MLJ100-5-B010-G-00-C
NA
JK/TRC
4/5/2012
FUNCTION
SETTINGS
0-1 Frequency
60
Hz
15
Volts
1-2 Angle
30
Degrees
30
mHZ
10
10.1
ON
40
Volts
98
Volts
10
Volts
98
Volts
10
Volts
ON
OFF
ON
ON
25
dL
Factory Default
9.6
Factory Default
04/10/12
Factory Default
156
Rev. 0
STATION:
PATNODE
DEVICE:
25/27/2102
DATE:
LINE:
RELAY:
FID:
ENG:
2102
MLJ100-5-B010-G-00-C
NA
JK/TRC
4/5/2012
JUMPER SETTINGS
JUMPERS ON MAIN BOARD
-ALL JUMPERS AT FACTORY DEFAULT
04/10/12
157
Rev. 0
STATION:
PATNODE
DEVICE:
25/27/2108
DATE:
LINE:
RELAY:
FID:
ENG:
2108
MLJ100-5-B010-G-00-C
NA
JK/TRC
4/5/2012
FUNCTION
SETTINGS
0-1 Frequency
60
Hz
15
Volts
1-2 Angle
30
Degrees
30
mHZ
10.1
ON
40
Volts
98
Volts
10
Volts
98
Volts
10
Volts
ON
OFF
ON
ON
25
dB
Factory Default
9.6
Factory Default
04/10/12
Factory Default
158
Rev. 0
STATION:
PATNODE
DEVICE:
25/27/2108
DATE:
LINE:
RELAY:
FID:
ENG:
2108
MLJ100-5-B010-G-00-C
NA
JK/TRC
4/5/2012
JUMPER SETTINGS
JUMPERS ON MAIN BOARD
-ALL JUMPERS AT FACTORY DEFAULT
04/10/12
159
Rev. 0
STATION:
PATNODE
DEVICE:
25/27/2114
DATE:
LINE:
RELAY:
FID:
ENG:
2114
MLJ100-5-B010-G-00-C
NA
JK/TRC
4/5/2012
FUNCTION
SETTINGS
0-1 Frequency
60
Hz
15
Volts
1-2 Angle
30
Degrees
30
mHZ
10.1
ON
40
Volts
98
Volts
10
Volts
98
Volts
10
Volts
ON
OFF
ON
ON
25
dL
Factory Default
9.6
Factory Default
04/10/12
Factory Default
160
Rev. 0
STATION:
PATNODE
DEVICE:
25/27/2114
DATE:
LINE:
RELAY:
FID:
ENG:
2114
MLJ100-5-B010-G-00-C
NA
JK/TRC
4/5/2012
JUMPER SETTINGS
JUMPERS ON MAIN BOARD
-ALL JUMPERS AT FACTORY DEFAULT
04/10/12
161
Rev. 0
STATION:
PATNODE
DEVICE:
79/2102
DATE:
LINE:
RELAY:
FID:
ENG:
2102
BE1-79M-B8C-A6J-C0L0F
NA
JK/TRC
4/5/2012
SETTINGS
Reclose 1
15.0
Reclose 2
NOT USED
Reclose 3
NOT USED
Reset
20
Reclose Fail
Max Cycle
180
Inst Trip 1
BLOCK
Inst Trip 2
BLOCK
Inst Trip 3
BLOCK
Inst Trip 4
BLOCK
Inst Trip 5
BLOCK
04/10/12
162
Rev. 0
STATION:
PATNODE
DEVICE:
79/2108
DATE:
LINE:
RELAY:
FID:
ENG:
2108
BE1-79M-B8C-A6J-C0L0F
NA
JK/TRC
4/5/2012
SETTINGS
Reclose 1
10.0
Reclose 2
NOT USED
Reclose 3
NOT USED
Reset
20
Reclose Fail
Max Cycle
180
Inst Trip 1
BLOCK
Inst Trip 2
BLOCK
Inst Trip 3
BLOCK
Inst Trip 4
BLOCK
Inst Trip 5
BLOCK
04/10/12
163
Rev. 0
STATION:
PATNODE
DEVICE:
79/2114
DATE:
LINE:
RELAY:
FID:
ENG:
2114
BE1-79M-B8C-A6J-C0L0F
NA
JK/TRC
4/5/2012
SETTINGS
Reclose 1
15.0
Reclose 2
NOT USED
Reclose 3
NOT USED
Reset
20
Reclose Fail
Max Cycle
180
Inst Trip 1
BLOCK
Inst Trip 2
BLOCK
Inst Trip 3
BLOCK
Inst Trip 4
BLOCK
Inst Trip 5
BLOCK
04/10/12
164
Rev. 0
APPENDIX 1:
BREAKER FAILURE
LOGIC DIAGRAM
04/10/12
165
Rev. 0
04/10/12
166
Rev. 0