BORL SRU BLOCK

COMPLIANCE REPORT TO EIL COMMENTS


-*21

Document Number

Document Title

VPTL NO 6743/PLL/SRU/257

DATED 11-06-2008

S No.
A

-SRU Block-BORL-BINA

COMMENTS / OBSERVATION
REFER DOC NO.
1. 6743-PEIN06-28-6102-A-508 REV0
2. 6743-PEIN06-29-6102-L-519 REV0
1. 6743-PEIN06-29-6102-L-517 REV0
2. 6743-PEIN06-29-6102-L-203 REV0
1. DESIGN CALCULATION FOR VESSEL
FOUNDATION (VESSEL NO 29-VV-00003), (VESSEL NO 29-VV-00-0015),
(VESSEL NO 29-VV-00-004 . GA AND
RCC DETAILS OF FOUNDATIONS. HI108.
2. ITEM NO. (29-EE-00-15A/B, 29-EE-0019A/B, 29-EE-00-11) GA AND RCC
DETAILS OF FOUNDATIONS.
3. ITEM NO. (27-EE-00-105A/B, 27-EE-00101A/B, 29-EE-00-009) GA AND RCC
DETAILS OF FOUNDATIONS.

1. 6743-PEIN06-29-6102-A-017 REV0
2. 6743-PEIN06-29-6102-A-506 REV0
1.DESIGN CALCULATION FOR LEAN
AMINE WATER COOLER (27-EE-00-105A/B),
LEAN/RICH AMINE EXCHANGER (27-EE00-101A/B ) & BFW HEATER (29-EE-00-009)
FOUNDATIONS.
1.DESIGN CALCULATION FOR LEAN
AMINE WATER EXCHANGER (27-EE-0015A/B), LEAN/RICH AMINE TRIM COOLER
(27-EE-00-19A/B ) & BLOW DOWN COOLER
(29-EE-00-11) FOUNDATIONS.

RESOLUTION/ ACTION

BORL SRU BLOCK


COMPLIANCE REPORT TO EIL COMMENTS
S No.

COMMENTS / OBSERVATION

RESOLUTION/ ACTION

ALWAYS FURNISH DESIGN & DRAWING Noted


TOGETHER IN SAME TRASMITTAL FOR
SYSTEMATIC REVIEW .PLEASE NOTE
DRAWING CANNOT BE REVIEWED IN
ABSENCE OF DESIGN CALCULATION .
IN FUTURE IN CASE DESIGN AND
DRAWING
ARE
NOT
SUBMITTED
TOGETHER THEN DOCUMENT WILL BE
RETURNED WITHOUT REVIEW

CONTRACTOR TO ENSURE AND CONFIRM


THAT ALL LEVEL SHOWN IN DRAWING
ARE AS PER APPROVED DRAWINGS.

Ensured

COORDINATES NEED TO BE VARIFIED AT OK, added in notes also.


SITE FROM APPROVED EQUIPMENT
LAYOUT DRAWING BEFORE TAKING UP
CONSTRUCTION ACTIVITIES.

REMOVE HOLD.

ADD DETAILS OF SLIDING PLATE AND Sliding plate will be supplied by vendor and it
SHOW IN DETAIL OF PEDESTAL FOR
Will rest above the grout
SLIDING SUPPORT.

ANNEXURE A DOES NOT INCLUDE Sorry for inconvenience caused.


PROPERTIES OF OCTAGONAL SHAPE
Shall be added in next submission.
FOUNDATION/PEDESTAL . REFER PAGE 7
OF DOC. NO. 6743-PEIN06-28-6102-A-508
REV0

CHECK BEARING PRESSURE UNDER Shall be added in next submission


HYDROSTATICTEST LOAD+25% WIND

FOR OCTAGONAL PEDESTAL PROVIDE


NUMBER OF BARS IN MULTIPLE OF 8 AS
EACH BAR IS REQUIRED IN EACH
CORNER OF OCTAGONAL , IN PLACE

Removed

Same above

Page 2 of 3

BORL SRU BLOCK


COMPLIANCE REPORT TO EIL COMMENTS
S No.

COMMENTS / OBSERVATION

RESOLUTION/ ACTION

SPECIFYING SPACING.

CHECK DESIGN OF FOUNDATION FOR 27- OK


EE-AS-105A/B AT THE TIME OF REMOVING
HOLD. REFER DOC.
NO. 6743PEIN06-29-6102-L-203
REV
0.
IT IS SUGGESTED THAT CONSTRUCTION
ACTIVITY SHOULD BE TAKEN ONLY
AFTER REMOVING HOLD.

10

PLEASE CLARIFY LOADING SHOWN IN It is for single exchanger.


MECHANICAL
DATA
SHEET
FOR
EXCHANGER IN SERIES IS FOR SINGLE
EXCHANGERS, IF REQUIRED DESIGN MAY
BE MODIFIED ACCORDINGLY

11

ADD SUMMARY FOR STRUCTURAL Refer detail drawing


MEMBER SIZE AND REINFORCEMENT
PROVODED AREA AS WELL AS NUMBER
OF BARS IN DOC. NO. 6743-PEIN06-29-6102A-017 REV0 & 6743-PEIN06-29-6102-A-506
REV0

12

AT THE TIME OF REMOVING HOLD OR AT Agreed


LATER STAGE , ANY CHANGE IN MEMBER
SIZE IS REQUIRED DUE TO CHANGE IN
DATA SHEET OR LOADING OR DUE TO
CHANGE IN DESIGN IT WILL BE SOLE
RESPONSIBILITY OF CONTRACTOR TO
PROVIDE THE SAME WITH NO COST AND
TIME IMPLICATION TO THE CLIENT.

13

THIS DOCUMENT HAS BEEN REVIEWED IN OK


CODE 2.

Page 3 of 3