Generator Details:
Generator Voltage (VL) (L-L)
Maximum Over Voltage
Frequency

Generator Transformer Details:


Transformer Primary Voltage
Transformer Secondary Voltage

Capacitance Per Phase:


Generator Winding Capacitance / Phase
Generator Connection Capacitance / Phase
Generator Transformer Capacitance / Phase
Generator Transformer Connection Capacitance / Phase
Transformer Cable Capacitance / Phase
Surge Arrestor Capacitance / Phase
Other Capacitance / Phase
Total Zero Sequence Capacitance (C):
Total Zero Sequence Capacitance Reactance to Ground (Xc):

Neutral Earthing Transformer Size:


Primary Voltage of the Grounding Transformer (Vp)
Secondary Voltage of the Grounding Transformer (Vs)
Turns Ratio of the Grounding Transformer (N)
Neutral Earthing Transformer % Reactance (X%)
Neutral Earthing Transformer Reactance in PU (Xpu)
Neutral Earthing Transformer Base KV (Bv)

on Size of NGR/ Neutral Earthing Transformer (NGR/NET)

11
14.3
50

KV
KV
Hz

11
6.6

KV
KV

0.22
0.001
0.006
0
0.0003
0.25
0.47730
6672.35

Farad
Farad
Farad
Farad
Farad
Farad
Farad
Farad
/Phase

11

KV

6.9

Volt

1594.20
4%
0.04
0.24

0.04
PU
KV

l Earthing Transformer (NGR/NET)


:Calculate Size of NGR/Neutral Earthing Transformer:
Phase to Neutral Voltage (Vp1)
% of Force field condition for Neutral Earthing Transformer
Phase to Neutral Voltage under Force Field Condition (Vf)
Capacitive charging current/phase (Ic)
Total Capacitive charging current (It)
Rating of Neutral Earthing Transformer (Pr)
Neutral Earthing Transformer overloading factor
Size of Neutral Earthing Transformer (P)
Residual Capacitive reactance (Xct)
Required Resistance value at secondary side (Rsec)
Required Grounding Resistor value at primary side (Rp)
Neutral Earthing Transformer Secondary Current
Neutral Earthing Transformer Secondary Resistor Current (for 30 Seconds)
Neutral Earthing Transformer Reactance Base(Base X):
Neutral Earthing Transformer Reactance (X)
Neutral Earthing Transformer X/R Ratio
Fault current through Neutral (single line to ground fault) (If)

:Results:
Rating of Neutral Earthing Transformer (P)
Short time Rating of Neutral Earthing Transformer
Ratio of Neutral Earthing Transformer
Neutral Earthing Transformer Secondary Current
Required Grounding Resistor value at primary side (Rp)

Required Resistance at secondary side (Rsec)


Neutral Earthing Transformer Secondary Resistor Current (for 30 Seconds)

6.35
30%
8.26

KV
1.3
KV

VL/1.732

1.24

Amp

3.71
40.83

Amp
KVA

Ic=Vf / Xc
It=3xIc
Pr=VpxIt

Vf=Vp1x 1,3

2.6
16
2224.12
0.001
2224.12
2276.15
7693.38
3.67
0.15
167.63

KVA

Amp
Amp

P=Pr/ 2,6
Xct=Xc / 3
Rsec=Xct / (NxN)
Rp=Xct

2.86

Amp

If=Vp1/Rp

16

KVA

41
11000 /6,9
2276.15
2224.12

0.00
7693.38

KVA
Volt
Amp

Amp

X=Xpu x Base X