Sie sind auf Seite 1von 1

HARIDWAR INFRASTRUCTURE LTD

DIKCHU HEP

No of Units
Sl No

Description

Rating in Kw

Units per
Machine

Total Units
for Power
House

Total Installed
Load
in kW

Start up Load
Emergency Load on DG Set
in Kw

LP AIR COMPRESSOR FOR SHAFT SEAL (UNIT-1 & 2)

15.00

1.00

2.00

30.00

15.00

15.00

3
7

DRAINAGE PUMP (Main & stand by)


Fire pump(Main & standby)
PRIMARY CKT. COOLING WATER PUMP
(Main,stand by & Common)
Secondary CKT. COOLING WATER PUMP
(Main,stand by & Common)
BACK WASH FILTER FOR SHAFT SEAL(Main & Stand
by)
CYCLONE SEPARATOR FOR SHAFT SEAL(Main &
Stand by)
PRIMARY CKT. DUPLEX FILTER (unit -1 & 2)
PRIMARY CKT. HEAT EX. I/L
MOTORIZED VALVE (Main,stand by & Common)
Secondary CKT. HEAT EX. I/L
MOTORIZED VALVE (Main,stand by & Common)
Secondary CKT. HEAT EX. I/L
MOTORIZED VALVE (Main,stand by & Common)
CYCLONE SEPARATOR CKT.
MOTORIZED VALVE-1 FOR UNIT-1
SHAFT SEAL PUMP(Main & Standby)
HEAD COVER PUMPS 1,2 (Main & stand by)
GOVERNING/MIV PUMP
GOVERNING/MIV JOCKEY PUMP
HIGH PRESSURE OIL INJECTION PUMP
OIL MIST EXH. SYSTEM
CARBON / BRAKE DUST EX. SYSTEM-1&2 ( Main &
stand by)

30.00
40.00

1.00
1.00

2.00
2.00

59.99
80.00

30.00
40.00

30.00
40.00

45.00

1.00

3.00

135.00

45.00

45.00

75.00

1.00

3.00

225.01

75.00

75.00

2.00

2.00

4.00

8.00

4.00

4.00

1.50

2.00

4.00

6.00

3.00

3.00

1.00

1.00

2.00

2.00

1.00

1.00

0.25

1.00

3.00

0.76

0.25

0.25

0.25

1.00

3.00

0.76

0.25

0.25

0.25

1.00

3.00

0.76

0.25

0.25

0.25

2.00

4.00

1.01

0.51

0.51

9.30
3.70
37.00
5.50
7.50
0.37

2.00
2.00
2.00
1.00
1.00
1.00

2.00
2.00
2.00
1.00
2.00
2.00

18.59
7.40
74.00
5.50
14.99
0.75

9.30
3.70
37.00
2.75
7.50
0.37

9.30
3.70
37.00
2.75
7.50
0.37

0.37

2.00

2.00

0.75

0.37

0.37

25

GENERATOR BRAKING SYSTEM(Main & Stand by)

5.50

2.00

2.00

11.00

5.50

5.50

26

MLDB

175.00

1.00

1.00

175.00

43.75

43.75

28
29
39

220V Battery Charger(1 & 2)


Inverter system(isolation transformer 1 &2)
SPACE HEATERS FOR GENERATOR
Total

32.00
25.00
11.00

1.00
1.00
1.00

2.00
2.00
1.00

64.01
50.00
11.00
2194.14

32.00
25.00
11.00
771.50
1341.676247

32.00
25.00
11.00
392.50
682.5770785

8
9
10
11
12
13
14
15
16
17
18
19
20
21
23
24

Installed load

CURRENT
2743
KVA

Start up load

436

KVA

Considering 5% margin for Installed load

2880

kVA

458

kVA

Considering 5% margin for start up load

Remarks

Considered only one pump


Considered only one pump
Considered only one pump
Considered only one pump

1/4th of the illumination is


considered

Considered power factor as


0.9

Only Unit start up conidtion is


taken, GSU TRF no load
charging is not considered