Specification of the Earth Fault Indicators — with Battery Powered 1. The Remote indication ( 2 contact request(NO}) to DMS must be Fleeting Contact (Pulse type) having approximately 500 ms pulse width. 2. Trip settings of the EFI as 25A, SOA,80A & 100A, 3, Manual reset by Test/Reset button. 4, LED indication with red color and Flag to operate when the EF detected Fault. 5. Auto reset after pre-selected time (1/2/4 Hrs. range).(for LED indication with and Flag) 6. Power Supply ~ Internal Lithium Battery (Battery capacity - 10 years (more than 1000 flash hours) and also the battery should be available in market and able to change it without effect the EFI efficiency. 7. One extra LED with one Extra contact(NO} required so when the battery load decreased to 5%, the battery LED (Different Color than the original LED of EF!) will start to blank and the contact will close 8. Feature for reset by 230VAC (for future when aux supply available) 9. Sensor CT with Cable. 10. Response delay (ms}- Selectable 40/60/80/160 (ms). 11. The proposed EFI shall operate in non-air-conditioned environment. 12, Warrantee for 10 years. e Rejected EFI: Type Manufacture Country 1_|EFI.06 _[CEDLT [Italy 2_|OMEG1 Bowden UK 3. |OMEG 2 Bowden UK 4 |Sensorform BLZ __| Suparule Ireland e¢ Recommended EFI: Type Manufacture Country 1 |EASLR EMG Germany 2_ | EARTH 4.0 HORSTMANN | Germany