T1B 160 TMF32-630 1p F FC Cu


(170mm2)

ABB contact for Mxico

Informacion General
Extended Product Type:
Product ID:
EAN:
Catalog Description:

Long Description:

T1B 160 TMF32-630 1p F FC Cu (170mm2)


1SDA052619R1
8015644532833
C.BREAKER TMAX T1B 160 FIXED SINGLE-POLE WITH FRONT
TERMINALS FOR CABLE Cu 70mm2 AND THERMOMAGNETIC RELEASE
TMF R 32-630 A
C.BREAKER TMAX T1B 160 FIXED SINGLE-POLE WITH FRONT
TERMINALS FOR CABLE Cu 70mm2 AND THERMOMAGNETIC RELEASE
TMF R 32-630 A

Categorias

Productos
moldeada

Productos y sistemas de baja tensin

Interruptores automticos

Interruptores automticos en caja

Tmax T

Ordering
EAN:
Minimum Order Quantity:
Customs Tariff Number:

8015644532833
1 piece
85362090

Dimensions
Product Net Width:
Product Net Height:
Product Net Depth:
Product Net Weight:

25 mm
130 mm
70 mm
0.35 kg

Container Information
Package
Package
Package
Package
Package
Package

Level
Level
Level
Level
Level
Level

1
1
1
1
1
1

Units:
Width:
Height:
Length:
Gross Weight:
EAN:

1 piece
117.5 mm
35 mm
140 mm
0.426 kg
8015644532833

Environmental
RoHS Status:

Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment


after 2006-07-01

Additional Information
Electrical Durability:
IIT Publishing Status:
Mechanical Durability:
Number of Poles:

8000 cycle
120 cycles per hour
Level 0 - Information enabled
25000 cycle
240 cycles per hour
1

http://www.abb.com/SmartLinks/Default.aspx?app=9AAG1827&lc=es&cc=MX&gid=ABB1SDA052619R1&printGuid=4c92923286364abc8d6a9b772e431ffb&ipp

1/3

28/10/2014

ABB ABB1SDA052619R1

Power Loss:
Product Main Type:
Product Name:
Product Type:
Rated Current (I n ):

Per Pole 2,1 W


SACE Tmax T
Automatic Circuit Breaker
CB
160 A

Rated Impulse Withstand Voltage


(Uimp ):

8 kV

Rated Insulation Voltage (Ui):

800 V

Rated Operational Voltage:

240 V
125 V
Rated Service Short-Circuit Breaking (220V
Capacity (I cs):
(230V
(380V
(415V
(440V
Rated Ultimate Short-Circuit
(220V
Breaking Capacity (I cu ):
(230V
(380V
(415V
(440V
(500V
(125V
(250V
Rated Uninterrupted Current (I u ):
160 A

AC
DC
AC) 18 kA
AC) 18 kA
AC) 16 kA
AC) 16 kA
AC) 10 kA
AC) 2.5 kA
AC) 2.5 kA
AC) 16 kA
AC) 16 kA
AC) 10 kA
AC) 8 kA
DC) 25 kA
DC) 3 poles in series 20 kA

Release Type:
Standards:
Sub-type:
Suitable For:
Suitable for Product Class:
Terminal Connection Type:
Test Voltage at Industrial Frequency
for 1 Minute:
Test Voltage Max (Utest ):

TM
IEC947-2 (D)
T1
T1
Moulded Case Circuit Breakers
Front for Copper Cables
3000 V

Version:

Fixed

3000 V

Certificates and Declarations (Document Number)


Declaration of Conformity - CE:
RoHS Information:

1SDL000165R0001
1SDL000200R0001

Classifications
Object Classification Code:

http://www.abb.com/SmartLinks/Default.aspx?app=9AAG1827&lc=es&cc=MX&gid=ABB1SDA052619R1&printGuid=4c92923286364abc8d6a9b772e431ffb&ipp

2/3

28/10/2014

ABB ABB1SDA052619R1

http://www.abb.com/SmartLinks/Default.aspx?app=9AAG1827&lc=es&cc=MX&gid=ABB1SDA052619R1&printGuid=4c92923286364abc8d6a9b772e431ffb&ipp

3/3

Das könnte Ihnen auch gefallen