SR. NO.

NTPC COMMENTS

CB DOCTOR RESPONSE

G.A. OF CENTRIFUGAL FAN

Dampers shall be made out of 18SWG (min) MS sheets

NOTED & INCORPORATED

Location- Near PH-1 ( ventilation for tunnel of conv 1 A/B)

NOTED & INCORPORATED

indicate size of the ID

INCORPORATED

Indicate critical speed of fan

NOTED & INCORPORATED

is it @20C

NOTED & INCORPORATED

Indicate thickness of these items

NOTED & INCORPORATED

Indicate type of bearing

NOTED & INCORPORATED


Centrifugal fans are belt driven with
different pulley sizes at motor & fan so
motor RPM and fan rpm will be
different.

Indicate Motor RPM. The motor RPM should be so


selected such that there is no mismatch in the fan RPM
mentioned in the GA.

IS12615, IE2 motor

NOTED & INCORPORATED

10

provide canopy over motor

NOTED & INCORPORATED

11

casing drain with valve shall be provided

NOTED & INCORPORATED

12

Attach technical datasheet of fan too

ALL FAN TECCHINAL DETAIL


PROVIDE IN THE DRAWING

13

Add in note :
1. The casing shall be rigidly reinforced and supported by
structural angles.
2. Split casing shall be provided.
3. Inspection & testing shall be as per approved QAP
4.Painting shall be as per painting schedule

NOTED & INCORPORATED

14

Include efficiency curve also

NOTED & INCORPORATED

15

Indicate the temp at which the performance curves are


given, is it 20C or 50C

Performance curves are at 50 deg c


same has been incorporated.

16

Plz check the orientation of outlet duct as per the location


of supply air shaft. Chk as per drg no 9573-155-PVM-B016

CHECKED

17

GA of supply fan for VSF 6- 134530m3/hr is not included.

NOTED & INCORPORATED