Sie sind auf Seite 1von 1

A State Sequencer Module is used for testing the logic of the undervoltage function.

Therefore, several different network faults (three phase, two phase and single phase)
for all phases are simulated (see Table 2,) while all other release criteria are fulfilled.
Between each simulated fault, a prefault with nominal voltages is simulated. As
Figure 3 shows, the Q->& U< protection may only trip if all three line to line voltages
.are below the set threshold Vmin
This only applies to the last simulated fault (3ph (L1L2L3) < Vmin), thus the
.protection function may only trip during this state

Das könnte Ihnen auch gefallen