Beruflich Dokumente
Kultur Dokumente
Lecture - 05
Analysis and Design of Two-way Slab
System without Beams
(Flat Plates and Flat Slabs)
By: Prof Dr. Qaisar Ali
Civil Engineering Department
UET Peshawar
www.drqaisarali.com
Session I
Topics Addressed
Background
Introduction to Direct Design Method (DDM)
Frame Analysis Steps using Direct Design Method (DDM)
Example 1
Two Way Slabs (Other Requirements of ACI)
Example 2
Example 3
Summary of Direct Design Method (DDM)
Background
In previous lectures, a 90 60 Hall was analyzed as a
one-way slab system as shown below.
Option 02
Option 01
Prof. Dr. Qaisar Ali
Background
Also, in previous lecture, the slab of 100 60
commercial building was analyzed as slab with beams
using Moment coefficient method.
Background
In the same 100 60 commercial building, if there are
shallow or no beams, Moment Coefficient Method cannot
be used.
Direct Design Method (DDM) can be used for such cases.
Introduction to DDM
Direct Design Method (DDM) is one of the method for
flexural analysis of two-way slabs with or without beams.
DDM is relatively difficult for slabs with beams or walls
therefore we will use it only for slabs without beams.
Introduction to DDM
In DDM, frames rather than panels are analyzed.
Exterior Frame
Interior Frame
Interior Frame
Exterior Frame
Introduction to DDM
For complete analysis of slab system frames, are
analyzed in E-W and N-S directions.
E-W Frames
10
Introduction to DDM
For complete analysis of slab system frames, are
analyzed in E-W and N-S directions.
N-S Frames
11
Introduction to DDM
Limitations
12
Introduction to DDM
Limitations (ACI 13.6.1):
Uniformly distributed loading (L/D 2)
l1
2l1 /3
l1
l2
Rectangular slab
panels (2 or less:1)
Column offset
l2 /10
13
Steps In DDM
Step 01: Sizes
ACI table 9.5 (a) and (c) are used for finding the slab thickness.
14
Steps In DDM
Step 02: Loads
The slab load is calculated in usual manner.
15
Steps In DDM
Step 03: Analysis
Panel Centerline
Interior Frame
Col Centerline
Panel Centerline
l1
l2
According to ACI 13.6.2.3: Where the transverse span of panels on either side of the
centerline of supports varies, l2 shall be taken as the average of adjacent transverse spans.
Prof. Dr. Qaisar Ali
16
Steps In DDM
Step 03: Analysis
h2/2
Exterior Frame
l2
l1
17
Steps In DDM
Step 03: Analysis
l2
Half Column strip
CS/2
CS/2
M.S/2
C.S
M.S/2
18
Steps In DDM
Step 03: Analysis
l2
Half Column Strip
5
5
5
10
5
ln
l1
l2/4 = 20/4 = 5
Prof. Dr. Qaisar Ali
19
Steps In DDM
Step 03: Analysis
CS
l2
MS
ln
l1
20
10
Steps In DDM
Step 03: Analysis
Step III: Calculate Static Moment (Mo) for interior span of frame.
Span of frame
wu l2 ln2
Mo =
Mo
8
ln
l2
21
Steps In DDM
Step 03: Analysis
Step IV: Longitudinal Distribution of Static Moment (Mo).
M+
M = 0.65Mo
M + = 0.35Mo
22
11
Steps In DDM
Step 03: Analysis
Step V: Lateral Distribution to column and middle strips.
M = 0.65Mo
0.60M +
0.75M
M + = 0.35Mo
0.75M
23
Steps In DDM
Step 03: Analysis
Step III: Calculate Static Moment (Mo) for exterior span of frame.
25'-0"
Mo =
25'-0"
wu l2 ln2
25'-0"
25'-0"
Span of frame
20'-0"
Mo
ln
l2
20'-0"
20'-0"
24
12
Steps In DDM
Step 03: Analysis
Step IV: Longitudinal distribution of static moment (Mo).
Mext = 0.26Mo
M ext+ = 0.52Mo
Mext
+
Mext
Mint
Mint- = 0.70Mo
25
Steps In DDM
Step 03: Analysis
Step V: Lateral Distribution to column and middle strips.
Mext- = 0.26Mo
M ext+ = 0.52Mo
1.00Mext
0.75Mint
0.60Mext
+
Mint- = 0.70Mo
26
13
Steps In DDM
Step 03: Analysis
Step V: Lateral Distribution to column and middle strips.
Mext- = 0.26Mo
Mext+ = 0.52Mo
Mint- = 0.70Mo
0.60M+
1.00Mext
0.75Mint
0.60Mext
0.75M
0.75M
+
M- = 0.65Mo
M+ = 0.35Mo
27
Example 1
Example 1:
Analyze the flat plate shown below using DDM. The slab supports a
live load of 144 psf. All columns are 14 square. Take fc = 4 ksi and fy
= 60 ksi.
25
25
25
25
20
20
20
28
14
Example 1
Step 01: Sizes
ACI table 9.5 (c) is used for finding flat plate and flat slab
thickness.
29
Example 1
Step 01: Sizes
Take hf = 10
30
15
Example 1
Step 02: Loads
31
Example 1
Step 03: Frame Analysis (E-W Interior Frame)
Step I: Marking E-W Interior Frame.
25'-0"
25'-0"
25'-0"
25'-0"
20'-0"
Panel Centerline
Interior Frame
l2
Col Centerline
Panel Centerline
l1
20'-0"
20'-0"
32
16
Example 1
Step 03: Frame Analysis (E-W Interior Frame)
Step II: Marking column and middle strips.
a) Marking Column Strip
25'-0"
25'-0"
25'-0"
25'-0"
b) Middle Strip
l2
Half Column strip
20'-0"
5
5
5
10
5
20'-0"
ln
l2/4 = 20/4 = 5
l1
20'-0"
33
Example 1
Step 03: Frame Analysis (E-W Interior Frame)
Step III: Static Moment (Mo) calculation.
25
25
25
25
Mo = wul2ln2/8
= 540 ft-kip
20
Mo = 540 ft-k
Mo = 540 ft-k
l2
20
ln =23.83
l1
20
34
17
Example 1
Step 03: Frame Analysis (E-W Interior Frame)
Step IV: Longitudinal distribution of Static Moment (Mo).
25
25
25
25
20
M+
Mext+
Mext
Mint- M
M
20
20
35
Example 1
Step 03: Frame Analysis (E-W Interior Frame)
Step IV: Longitudinal distribution of Static Moment (Mo).
25
25
281
189
25
25
20
140
378
351
351
20
20
36
18
Example 1
Step 03: Frame Analysis (E-W Interior Frame)
Step V: Lateral distribution to column and middle strips.
25
25
25
25
20
0.75Mint 0.75M
1.00Mext
0.60Mext
0.75M
0.60M+
M = 0.65Mo = 351
M + = 0.35Mo = 189
20
20
37
Example 1
Step 03: Frame Analysis (E-W Interior Frame)
Step V: Lateral distribution to column and middle strips.
25
25
0.75Mint 0.75M
140
0.75M
0.60M+
20
25
20
0.60Mext
M = 0.65Mo = 351
M + = 0.35Mo = 189
25
20
38
19
Example 1
Step 03: Frame Analysis (E-W Interior Frame)
Step V: Lateral distribution to column and middle strips.
25
25
25
25
20
0.75Mint 0.75M
140
169
0.75M
113
M = 0.65Mo = 351
M + = 0.35Mo = 189
20
20
39
Example 1
Step 03: Frame Analysis (E-W Interior Frame)
Step V: Lateral distribution to column and middle strips.
25
25
25
20
284
140
168
263
263
113
M = 0.65Mo = 351
M + = 0.35Mo = 189
20
75 % of Mint- goes to
column strip and
remaining to middle strip
25
20
40
20
Example 1
Step 03: Frame Analysis (E-W Interior Frame)
Step V: Lateral distribution to column and middle strips.
25
25
25
20
0
112/2
94/2
283
140
88/2
112/2
76/2
88/2
263
263
168
M = 0.65Mo = 351
M + = 0.35Mo = 189
25
113
94/2
88/2
76/2
88/2
20
20
41
Example 1
Step 03: Frame Analysis (E-W Interior Frame)
Step V: Lateral distribution to column and middle strips.
25
25
25
25
20
112/2
11.2
9.4
94/2
283
28.3
140
14.0
168
16.8
88/2
8.8
76/2
7.6
8.8
88/2
263
26.3
263
26.3
11.3
113
10 column strip
5 half middle strip
20
20
42
21
Example 1
Step 03: Frame Analysis (E-W Exterior Frame)
Exterior Frame
l2
l1
43
Example 1
Step 03: Frame Analysis (E-W Exterior Frame)
CS
l2
MS
44
22
Example 1
Step 03: Frame Analysis (E-W Exterior Frame)
Step III: Calculation of static moment, Mo
25
Mo =
25
wul2ln2/8
= 285.68 ft-kip
Mo = 285.68 ft-k
25
25
Mo = 285.68 ft-k
20
l2 =10.58
ln =23.83
20
20
45
Example 1
Step 03: Frame Analysis (E-W Exterior Frame)
Step IV: Longitudinal distribution to column and middle strips.
25
Mo = 285.68 ft-kip
Mext- = 0.26Mo = 74
Mext+ = 0.52Mo = 148
Mint- = 0.70Mo = 200
25
25
M+
Mext+
Mext
25
Mint-
20
l2 =10.58
20
M - = 0.65Mo = 186
M + = 0.35Mo = 100
20
46
23
Example 1
Step 03: Frame Analysis (E-W Exterior Frame)
Step IV: Longitudinal distribution to column and middle strips.
25
Mo = 285.68 ft-kip
Mext- = 0.26Mo = 74
Mext+ = 0.52Mo = 148
Mint- = 0.70Mo = 200
25
148
74
25
25
100
200
186
186
20
l2 =10.58
20
M - = 0.65Mo = 186
M + = 0.35Mo = 100
20
47
Example 1
Step 03: Frame Analysis (E-W Exterior Frame)
Step V: Lateral distribution to column and middle strips.
25
Mo = 285.68 ft-kip
1.00Mext
0.60Mext+
25
0.75Mint
0.75M
0.60M+
25
25
0.75M
20
Mext- = 0.26Mo = 74
Mext+ = 0.52Mo = 148
Mint- = 0.70Mo = 200
l2 =10.58
20
M - = 0.65Mo = 186
M + = 0.35Mo = 100
20
48
24
Example 1
Step 03: Frame Analysis (E-W Exterior Frame)
Step V: Lateral distribution to column and middle strips.
25
Mo = 285.68 ft-kip
25
25
74
89
150
140
60
140
59
50
46
40
46
25
20
Mext- = 0.26Mo = 74
Mext+ = 0.52Mo = 148
Mint- = 0.70Mo = 200
l2 =10.58
20
M - = 0.65Mo = 186
M + = 0.35Mo = 100
20
49
Example 1
Step 03: Frame Analysis (E-W Exterior Frame)
Step V: Lateral distribution to column and middle strips (per strip width)
25
Mo = 285.68 ft-kip
25
25
13.26
15.94
26.8
25.1
10.75
25.1
11.87
10
9.2
9.2
Mext- = 0.26Mo = 74
Mext+ = 0.52Mo = 148
Mint- = 0.70Mo = 200
25
CS
MS
20
l2 =10.58
20
M - = 0.65Mo = 186
M + = 0.35Mo = 100
l2 = (20) + (14/12) = 10.58
20
50
25
Example 1
Step 03: Frame Analysis (N-S Interior Frame)
Column Strip and Middle strip Moments
25
Mo = 421.5 ft-kip
Mext- = 0.26Mo = 110
Mext+ = 0.52Mo = 219
Mint- = 0.70Mo = 295
M - = 0.65Mo = 274
M + = 0.35Mo = 148
74/2
25
110
131
88/2
25
20
221
206
59/2
25
69/2
20
88.8
206
69/2
20
l2 =25
51
Example 1
Step 03: Frame Analysis (N-S Interior Frame)
Column Strip and Middle strip Moments (Per Strip Width)
25
Mo = 421.5 ft-kip
Mext- = 0.26Mo = 110
Mext+ = 0.52Mo = 219
Mint- = 0.70Mo = 295
M - = 0.65Mo = 274
M + = 0.35Mo = 148
4.9
25
11.0
13.1
5.8
20
4.6
20
8.88
20.6
4.6
l2 =25
25
22.1
20.6
3.9
25
20
52
26
Example 1
Step 03: Frame Analysis (N-S Exterior Frame)
Column Strip and Middle strip Moments
25
Mo = 220.5 ft-kip
Mext = 0.26Mo = 58
Mext+ = 0.52Mo = 114
Mint = 0.70Mo = 154
M = 0.65Mo = 143
M + = 0.35Mo = 77
58
69
45
115.5
25
25
25
20
38.5
107.3 35.75
46.2
20
30.8
107.3 35.75
l2 =13.08
20
l2 = (25) + (14/12)
= 13.08
Prof. Dr. Qaisar Ali
53
Example 1
Step 03: Frame Analysis (N-S Exterior Frame)
Column Strip and Middle strip Moments (Per Strip Width)
25
25
25
25
Mo = 220.5 ft-kip
Mext = 0.26Mo = 58
Mext+ = 0.50Mo = 110
Mint = 0.70Mo = 154
M = 0.65Mo = 143
M + = 0.35Mo = 77
Column Strip Width
= (20/4) + (14/12)
= 5.58
MS = 13.08 5.58
= 7.5
10.4
20
12.32 6
20.69
5.13
19.2
4.76
8.27
4.12
19.2
4.76
20
20
l2 =13.08
54
27
Example 1
Step 03: Frame Analysis (E-W Direction Moments)
25
13.26
0
25
15.94
26.8
25.1
10.75
25.1
11.87
10
9.2
9.2
9.4
28.3
14.0
25
20
7.6
26.3
26.3
16.8
0
25
11.3
8.8
11.2
8.8
20
20
55
Example 1
Step 03: Frame Analysis (N-S Direction Moments)
25
10.4
00
11.0
8.8
13.1
8.8
5.13 4.9
22.1
12.32 6
20.69
25
19.2
4.76
4.6
20.6
8.27
4.12
3.9
8.88
19.2
4.76
4.6
20.6
25
25
20
4.6
20
4.6
20
56
28
Example 1
Step 04: Design (E-W Direction)
25
13.26
0
25
15.94
26.8
25.1
10.75
25.1
11.87
10
9.2
9.2
9.4
25
20
7.6
28.3
14.0
26.3
26.3
16.8
0
25
11.3
8.8
11.2
8.8
20
20
57
Example 1
Step 04: Design (E-W Direction)
25
B
25
25
C
A
A
C
C
A = #5 @ 4 c/c
B = #5 @ 8 c/c
C = #5 @ 12 c/c
20
B
C
25
20
20
58
29
Example 1
Step 04: Design (N-S Direction)
25
B
25
4.9
3.9
25
25
20
A = #5 @ 6 c/c
B = #5 @ 9 c/c
C = #5 @ 12 c/c
D = #5 @ 15 c/c
20
20
59
60
30
Slab
3/4
Support
61
62
31
Reinforcement
placement:
However
in
the
case
of
flat
63
Splicing: ACI 13.3.8.5 requires that all bottom bars within the
column strip in each direction be continuous or spliced with length
equal to 1.0 ld, (For development length see ACI 12.2.3 or Nelson
13th Ed, page 172 chapter 5 or mechanical or welded splices)
ld = 47 db
64
32
65
66
33
Reinforcement
should
be
provided
at
l /5
l /5
required
for
maximum
positive
67
Example 2
Homework: Analysis results of the slab shown below using DDM are
presented next. The slab supports a live load of 60 psf. Superimposed
dead load is equal to 40 psf. All columns are 14 square. Take fc = 3 ksi
and fy = 40 ksi.
25
25
25
25
20
20
20
68
34
Example 2
Calculation summary
Slab thickness hf = 10
69
Example 2
E-W Direction Moments (units: kip-ft)
25
57.4
0
25
68.9
116
107.6
46.4
107.6
45.9
38.6
35.9
30.9
35.9
36.5
219
108.6
43.4
25
20
29.2
204
204
130
0
25
88
33.9
33.9
20
20
70
35
Example 2
E-W Direction Moments (units: kip-ft/ft)
Moments per strip width
25
10.3
0
25
12.3
20.8
19.3
8.3
19.3
9.2
7.7
7.2
6.2
7.2
7.3
21.9
10.9
25
20
5.8
20.4
20.4
13.0
0
25
8.8
6.8
8.7
6.8
20
20
71
Example 2
N-S Direction moments (units: kip-ft)
25
44.3
53.2
89.5
84.7
35.5
101
33.9
29.8 4.9
28.5
171
83.1
27.7
35.8
23.9
83.1
27.7
00
25
159
22.8
3.9
25
20
26.5
20
68.4
159
25
26.5
20
72
36
Example 2
N-S Direction moments (units: kip-ft/ft)
Moments per strip width
25
7.9
9.5
4.7
16.0
4.0
14.9
3.7
6.4
3.2
14.9
3.7
25
00
8.5
10.1
4.5
4.9
3.8
25
25
20
17.1
15.9
3.0
3.9
3.5
20
6.8
15.9
3.5
20
73
Example 3
Homework: Analysis results of the slab shown below using DDM are
presented next. The slab supports a live load of 60 psf. Superimposed
dead load is equal to 40 psf. All columns are 12 square. Take fc = 3 ksi
and fy = 40 ksi.
20
20
20
20
15
15
15
74
37
Example 3
Calculation summary
Slab thickness hf = 8
75
Example 3
E-W Direction Moments (units: kip-ft)
20
24.8
0
20
29.7
50
46.5
20
46.5
19.8
16.7
15.5
13.3
15.5
15.6
93.8
46.5
18.6
20
15
12.5
87.1
87.1
55.8
0
20
37.5
14.5
14.5
15
15
76
38
Example 3
E-W Direction Moments (units: kip-ft/ft)
Moments per strip width
20
5.8
0
20
7.0
11.8
10.9
4.7
10.9
5.3
4.5
4.1
3.6
4.1
4.2
12.5
6.2
20
15
3.3
11.6
11.6
7.4
0
20
5.0
3.9
5.0
3.9
15
15
77
Example 3
N-S Direction moments (units: kip-ft)
20
17.7
21.2
35.7
33.6
14.1
40.4
13.5
11.9 4.9
11.3
67.9
33.1
11.0
14.3
9.5
33.1
11.0
00
20
63.1
9.1
3.9
20
15
10.5
15
27.2
63.1
20
10.5
15
78
39
Example 3
N-S Direction moments (units: kip-ft/ft)
Moments per strip width
20
17.7
21.2
35.7
4.5
2.26
5.4
2.2
1.90 4.9
1.8
9.5
33.1
1.77
14.3
1.52
33.1
1.77
00
20
8.4
1.4
3.9
20
20
1.7
15
3.6
8.4
15
1.7
15
79
Decide about sizes of slab and columns. The slab depth can
be calculated from ACI table 9.5 (c).
80
40
81
Session II
82
41
Topics Addressed
Introduction
Various Design Options
Design Example
83
Introduction
These are the most common types of two-way slab system, which are commonly
used in multi-story construction.
They render low story heights and have easy construction and formwork.
84
42
Introduction
Behavior
When two-way slabs are directly supported by columns, shear near the column
(punching shear) is of critical importance.
Therefore, in addition to flexure, flat plates shall also be designed for two way
shear (punch out shear) stresses.
85
Introduction
Punching shear occurs at column support points in flat plates and flat slabs.
Shear crack
Punch Out
86
43
Introduction
87
Introduction
Shear
crack
Beam
d
88
44
Introduction
Column
Critical perimeter
Slab
Tributary Area, At
d/2
d/2
89
Introduction
c1,S
d/2
c1,L
d/2
bo = 2(c1,S + d) + 2(c1,L + d)
Prof. Dr. Qaisar Ali
90
45
Introduction
c1,S
d/2
c1,L
d/2
91
Introduction
c1,L
d/2
c1,S
d/2
92
46
Introduction
Punching Shear Demand (Vu): For Square Column
l2
l1
93
Introduction
Vn = Vc + Vs
Vc is least of:
4 (fc)bod
(2 + 4/c) (fc)bod
94
47
When Vc < Vu, then we need to increase the punching shear capacity of the
slab.
Punching shear capacity of the flat plates can be increased by either of the
following ways:
i.
Increasing d ,depth of slab: This can be done by increasing the slab depth as a
whole or in the vicinity of column (Drop Panel)
ii.
Increasing bo, critical shear perimeter: This can be done by increasing column size
as a whole or by increasing size of column head (Column capital)
iii.
95
Integral beams
Bent Bars
Shear heads
Shear studs
96
48
97
Column Capital:
ACI 13.1.2 requires the column capital should be oriented no greater than 450 to the axis of the
column.
ACI 6.4.6 requires that the capital concrete be placed at the same time as the slab concrete. As a
result, the floor forming becomes considerably more complicated and expensive.
The increased perimeter can be computed by equating Vu to Vc and simplifying the resulting
equation for b0
98
49
ACI 11.11.3 requires the slab effective depth d to be at least 6 in., but not
less than 16 times the diameter of the shear reinforcement.
When bent bars and integral beams are to be used, ACI 11.11.3 reduces
Vc by 2
99
Vertical stirrups
Vertical Stirrups
Horizontal Bars
100
50
Vertical stirrups
Critical
Perimeter, bo
Prof. Dr. Qaisar Ali
Critical Perimeter, bo
(lv c/2)
lv
R
X = (lv c/2)
X = (lv c/2)
bo = 4R + 4c
102
51
Critical Perimeter,
bo
(lv c/2)
bo = 4R + 4c ........ (1)
R = (X 2 + X 2 ) = (2) X
X = (lv c/2)
X = (lv c/2)
103
Design Example
Step 01: Calculate Punching Shear Demand, Vu
Critical Perimeter, bo :
bo = 4(c + d)
= 4(14 + 8.5) = 90
20
25
= 496.5 ft2
104
52
Design Example
Calculation of Punching shear capacity (Vc):
20
Vc is least of:
4 fc bod = 145 k
25
(2 + 4 / c) fc bod = 216 k
{(s d/bo +2} fc bod = 208 k
Therefore,
105
Design Example
Design for shear (Option 01): Drop panels
In drop panels, the slab thickness in the vicinity of the columns is increased to
increase the shear capacity (Vc = 4 (fc)bod) of concrete.
and
106
53
Design Example
Design for shear (Option 01): Drop panels
Equate Vu to Vc:
Vu = Vc
189 = 0.75 4 (fc) 90 d
d = 11.07
25/6 = 4.25
20/6 = 3.5
7
8.5
107
Design Example
Design for shear (Option 02): Column Capitals
Equate Vu to Vc:
Vu = Vc
189 = 0.75 4 (fc) bo 8.5
bo = 117.20
Now,
bo = 4 (c + d)
117.20 = 4(c + 8.5)
Simplification gives,
c = 20.8 21
108
54
Design Example
Design for shear (Option 02): Column Capitals
capital
14
column
109
Design Example
Design for shear (Option 03): Integral Beams (Vertical Stirrups)
Vc = 145 kips
110
55
Design Example
Design for shear (Option 03): Integral Beams (Horizontal Bars)
Four #5 bars are to be provided in each direction to hold the stirrups. We know
minimum bo = 117.10
Hence the horizontal bars need to be extended beyond the center of the column up to
at least 20 (We will use 24)
111
Design Example
Design for shear (Option 03): Integral Beams details.
d/2
face.
#3 Stirrups @ 3 c/c
2
4 #5 bars to hold stirrups
4
Prof. Dr. Qaisar Ali
112
56
References
ACI 318
Design of Concrete Structures by Nilson, Darwin and Dolan
ACI Design Handbook
113
The End
114
57