SADRAJ
PRIMJER PROGRAMSKOG ZADATKA IZ EEP POSTROJENJA........................................ 3
1
PRORAUN ....................................................................................................................... 4
1.1
VODOVA.................................................................................................................... 4
1.2
GENERATORA.......................................................................................................... 4
1.3
TRANSFORMATORA............................................................................................... 5
2
EKVIVALENTNE SHEME ............................................................................................... 5
2.1
DIREKTNI SUSTAV ................................................................................................. 5
2.2
INVERZNI SUSTAV ............................................................................................... 10
2.3
NULTI SUSTAV ...................................................................................................... 15
3
PRORAUN STRUJA KRATKOG SPOJA .................................................................... 20
3.1
JEDNOPOLNI KRATKI SPOJ ................................................................................ 20
3.2
DVOPOLNI KRATKI SPOJ .................................................................................... 20
3.3
DVOPOLNI KRATKI SPOJ SA ZEMLJOSPOJEM ............................................... 20
3.4
TROPOLNI KRATKI SPOJ ..................................................................................... 21
4
RASPODJELA STRUJA U EKVIVALENTNIM SHEMAMA ZA ZADANO MJESTO
KS I MJERODAVNI KS .......................................................................................................... 21
5
STRUJE FAZA R, S i T.................................................................................................... 24
JEDNOPOLNI KS ................................................................................................................ 24
TROPOLNI KS ..................................................................................................................... 24
5.1
STRUJE FAZE R ...................................................................................................... 24
5.1.1
Struje vodova..................................................................................................... 24
5.1.2
Struje transformator sabirnica ........................................................................ 25
5.2
STRUJE FAZE S ...................................................................................................... 25
5.2.1
Struje vodova..................................................................................................... 25
5.2.2
Struje transformator sabirnica ........................................................................ 25
5.3
STRUJE FAZE T ...................................................................................................... 25
5.3.1
Struje vodova..................................................................................................... 25
5.3.2
Struje transformator sabirnica ........................................................................ 25
6
STRUJE GENERATORA ODNOSNO PRIMARA TRANSFORMATORA.................. 26
6.1
JEDNOPOLNI KS .................................................................................................... 26
6.2
TROPOLNI KS ......................................................................................................... 26
6.2.1
Struje generatora G1 .......................................................................................... 26
6.2.2
Struje generatora G2 .......................................................................................... 26
6.2.3
Struje generatora G3 .......................................................................................... 26
6.2.4
Struje generatora G4 .......................................................................................... 26
7
TROPOLNA SHEMA RASPODJELA STRUJA U MREI ZA VRIJEME
TROPOLNOG KRATKOG SPOJA ......................................................................................... 27

Literatura: Hrvoje Poar: Visokonaponska Rasklopna Postrojenja, Tehnika


knjiga, Zagreb, 1963.

PRIMJER PROGRAMSKOG ZADATKA IZ EEP POSTROJENJA


(PRORAUN STRUJA KRATKOG SPOJA)
ZADATAK: Proraunati struje kratkog spoja na zadanim sabirnicama
i odrediti struje u pojedinim granama za najnepovoljniji
sluaj kratkog spoja u mrei prema slici.

D
G1

LDE

T1

B
LAD

LBD
T4

G2

T2

LAC

G4

LBC

T3

G3

Za reaktancije vodova uzeti 0,4 /km.

Ostali podaci:

Element
G1, G2

G3

G4

T1, T2
T3
T4

Vodovi

Veliina
S
U
Xd
Xi
S
U
Xd
Xi
S
U
Xd
Xi
S
U1/U2
Xk
S
U1/U2
Xk
S
U1/U2
Xk
lAD
lAC
lBC
lBD
lDE

MJESTO KRATKOG SPOJA

Jedinica
MVA
kV
%
%
MVA
kV
%
%
MVA
kV
%
%
MVA
kV/kV
%
MVA
kV/kV
%
MVA
kV/kV
%
km
km
km
km
km

Primjer 0
25
10
17
4,5
70
10
28
15
35
10
38
8
25
10/110
10
70
10/110
11
35
10/110
9
60
110
85
70
70
D

1 PRORAUN
1.1
VAD

VODOVA

Xd = Xi = l * Xv = 60 km * 0,4 /km = 24
X0 = 3 Xd = 3 * 24 = 72

VAC

Xd = Xi = l * Xv = 110 km * 0,4 /km = 44


X0 = 3 Xd = 3 * 44 = 132

VBC

Xd = Xi = l * Xv = 85 km * 0,4 /km = 34
X0 = 3 Xd = 3 * 34 = 102

VBD

Xd = Xi = l * Xv = 70 km * 0,4 /km = 28
X0 = 3 Xd = 3 * 28 = 84

VDE

Xd = Xi = l * Xv = 70 km * 0,4 /km = 28
X0 = 3 Xd = 3 * 28 = 84

G1

G2

1.2

GENERATORA

Xd =

X d U 2
17 (110 10 3 ) 2 V 2

= 82,28
100 S
100
25 10 6 VA

Xi =

X i U 2 4,5 (110 10 3 ) 2 V 2

= 21,78
100 S
100
25 10 6 VA

X d U 2
17 (110 10 3 ) 2 V 2
Xd =

= 82,28
100 S
100
25 10 6 VA
X i U 2 4,5 (110 10 3 ) 2 V 2
Xi =

= 21,78
100 S
100
25 10 6 VA

G3

X d U 2
28 (110 10 3 ) 2 V 2
Xd =

= 48,4
100 S
100
70 10 6 VA
X i U 2
15 (110 10 3 ) 2 V 2
Xi =

= 25,92
100 S
100
70 10 6 VA

G4

Xd =

X d U 2
38 (110 10 3 ) 2 V 2

= 131,37
100 S
100
35 10 6 VA

Xi =

X i U 2
8 (110 10 3 ) 2 V 2

= 27,65
100 S
100
35 10 6 VA

1.3

TRANSFORMATORA

T1

Xd = Xi = X0 =

X k U 2
10 (110 10 3 ) 2 V 2

= 48,4
100 S
100
25 10 6 VA

T2

Xd = Xi = X0 =

X k U 2
10 (110 10 3 ) 2 V 2

= 48,4
100 S
100
25 10 6 VA

T3

Xd = Xi = X0 =

X k U 2
11 (110 10 3 ) 2 V 2

= 19,01
100 S
100
70 10 6 VA

T4

Xd = Xi = X0 =

X k U 2
9 (110 10 3 ) 2 V 2

= 31,11
100 S
100
35 10 6 VA

2 EKVIVALENTNE SHEME
2.1

DIREKTNI SUSTAV
D

XDE

A
XG1

XT1

XAD

XDB

E
B
XT4

XG2

XT2

XAC

XG4

XCB

XT3

XG3

C
G

Slika 2.1: Ekvivalentna shema direktnog sustava


D

28
XDE

82,28
XG1

48,4

XT1

82,28
XG2

48,4
XT2

48,4
XG3

24

28

XAD

XDB

44

34

XAC

XCB

E
B

31,11
XT4

131,37
XG4

19,01
XT3

C
G

Slika 2.2 a): Ekvivalentna shema direktnog sustava s reaktancijama


5

X1 = XG1 + XT1 = 82,28 + 48,4 = 130,68


X2 = XG2 + XT2 = 82,28 + 48,4 = 130,68
X3 = XG3 + XT3 = 48,4 + 19,01 = 67,41
X4 = XG4 + XT4 = 31,11 + 131,37 = 162,48

130,68 A
X1

130,68

24

28

XAD

XDB

44

X2

162,48
X4

34

XAC

XCB

X3 67,41

Slika 2.2 b)

X 12 =

A
65,34

X1 X 2
130,68 130,68
=
= 65,34
X 1 + X 2 130,68 + 130,68
24

28

XAD

XDB
XAB

X12
XAC

44

162,48
X4

XCB

34
X3 67,41

XAC3

XCB3

Slika 2.2 c)

X 12 = X 1 + X 2 +

X1 X 2
X3

X 13 = X 1 + X 3 +

X1 X 3
X2

X 23 = X 2 + X 3 +

X2 X3
X1

X AC 3 = X AC + X 3 +

X AC X 3 X AC X CB + X 3 X CB + X AC X 3
=
X CB
X CB

44 34 + 67,41 34 + 44 67,41
= 198,64
34
X X 3 X CB X AC + X 3 X AC + X CB X 3
= X CB + X 3 + CB
=
X AC
X AC

X AC 3 =
X CB 3

34 67,41
= 153,49
44
X X CB X AC X 3 + X CB X 3 + X AC X CB
+ AC
=
X3
X3

X CB 3 = 34 + 67,41 +
X AB = X AC + X CB
X AB = 44 + 34 +

44 34
= 100,19
67,41

24

28

XAD

65,34
X12

XDB

162,48
X4

100,19
XAB
XAC3

XCB3

198,64

153,49

Slika 2.2 d)

X 1A =

X 12 X AC 3
65,34 198,64
=
= 49,16
X 12 + X AC 3 65,34 + 198,64

X 4B =

X 4 X CB 3
162,48 153,49
=
= 78,92
X 4 + X CB 3 162,48 + 153,49
X1 =

X 12 X 13
X 12 + X 13 + X 23

X2 =

X 12 X 23
X 12 + X 13 + X 23

X3 =

X 13 X 23
X 12 + X 13 + X 23

24

28

XAD

XDB

100,19
XAB
XB

XA

XC
X1A

X4B

49,16

78,92
P

Slika 2.2 e)

XA =

X 1 A X AB
X 1 A + X AB + X 4 B

49,16 100,19
= 21,57
49,16 + 100,19 + 78,92
X 4 B X AB
XB =
X 1 A + X AB + X 4 B
XA =

78,92 100,19
= 34,63
49,16 + 100,19 + 78,92
X1A X 4 B
XC =
X 1 A + X AB + X 4 B
XB =

XC =

49,16 78,92
= 16,83
49,16 + 100,19 + 78,92

24

28

XAD

XDB

XA

XB

21,57

34,63
XC 16,83

G
P

Slika 2.2 f)

XA = XAD + XA = 24 + 21,57 = 45,57


XB = XDB + XB = 28 + 34,63 = 62,63
D
XA' 45,57

XB' 62,63

XC 16,83

G
P

Slika 2.2 g)
'

'

X AB =

XA XB
'

'

XA + XB

'

45,57 62,63
= 26,37
45,57 + 62,63

Xd = XAB + XC = 26,37 + 16,83 = 43,2


Zd = j 43,2

XAB'

43,2

26,37

Xd
XC 16,83

110
3

V
P

Slika 2.2 i)
P

Slika 2.2 h)

2.2

INVERZNI SUSTAV
D

XDE

A
XG1

XT1

XAD

XDB

E
B
XT4

XG2

XT2

XAC

XG4

XCB

XT3

XG3

C
P
Slika 2.3: Ekvivalentna shema inverznog sustava

28

D
21,78
XG1

21,78
XG2

48,4

XT1

48,4
XT2

25,92
XG3

XDE

24

28

XAD

XDB

44

34

XAC

XCB

E
B

31,11
XT4

27,65
XG4

19,01
XT3

Slika 2.3 a): Ekvivalentna shema inverznog sustava s reaktancijama


X1 = XG1 + XT1 = 21,78 + 48,4 = 70,18
X2 = XG2 + XT2 = 21,78 + 48,4 = 70,18
X3 = XG3 + XT3 = 25,92 + 19,01 = 44,93
X4 = XG4 + XT4 = 27,65 + 31,11 = 58,76

10

70,18

X1

70,18

24

28

XAD

XDB

44

X2

58,76
X4

34

XAC

XCB

X3 44,93

P
Slika 2.3 b)

X 12 =

A
35,09

X1 X 2
70,18 70,18
=
= 35,09
X 1 + X 2 70,18 + 70,18
24

28

XAD

XDB
XAB

X12
XAC

44

58,76
X4

XCB

34
X3 44,93

XAC3

XCB3

P
Slika 2.3 c)

X 12 = X 1 + X 2 +

X1 X 2
X3

X 13 = X 1 + X 3 +

X1 X 3
X2

X 23 = X 2 + X 3 +

X2 X3
X1

11

X AC X 3 X AC X CB + X 3 X CB + X AC X 3
=
X CB
X CB

X AC 3 = X AC + X 3 +

44 44,93
= 147,07
34
X X 3 X CB X AC + X 3 X AC + X CB X 3
+ X 3 + CB
=
X AC
X AC

X AC 3 = 44 + 44,93 +
X CB 3 = X CB

34 44,93
= 113,68
44
X X CB X AC X 3 + X CB X 3 + X AC X CB
+ AC
=
X3
X3

X CB 3 = 34 + 44,93 +
X AB = X AC + X CB
X AB = 44 + 34 +

44 34
= 111,3
44,93

24
XAD

35,09

28
XDB

X12

58,76
X4

111,3
XAB
XAC3

XCB3

147,07

113,68

P
Slika 2.3 d)

X 1A =

X 12 X AC 3
35,09 147,07
=
= 28,33
X 12 + X AC 3 35,09 + 147,07

X 4B =

X 4 X CB 3
58,76 113,68
=
= 38,73
X 4 + X CB 3 58,76 + 113,68
X1 =

X 12 X 13
X 12 + X 13 + X 23

X2 =

X 12 X 23
X 12 + X 13 + X 23

X3 =

X 13 X 23
X 12 + X 13 + X 23

12

24

28

XAD

XDB

111,3
XAB
XB

XA

XC
X1A

X4B

28,33

38,73
P

Slika 2.3 e)

XA =

X 1 A X AB
X 1 A + X AB + X 4 B

28,3 38,73
= 17,67
28,3 + 111,3 + 38,73
X 4 B X AB
XB =
X 1 A + X AB + X 4 B
XA =

38,73 111,3
= 24,16
28,3 + 111,3 + 38,73
X 1A X 4 B
XC =
X 1 A + X AB + X 4 B
XB =

XC =

28,3 38,73
= 6,15
28,3 + 111,3 + 38,73

24

28

XAD

XDB

XA

XB

17,67

24,16
XC 6,15

Slika 2.3 f)

13

XA = XAD + XA = 24 + 17,67 = 41,67


XB = XDB + XB = 28 + 24,16 = 52,16
D
XA' 41,67

XB' 52,16

XC 6,15

Slika 2.3 g)
'

XA XB

'

X AB =

'

'

XA + XB

'

41,67 52,16
= 23,16
41,67 + 52,16

Xi = XAB + XC = 23,16 + 6,15 = 29,31


Zi = j 29,31

XAB'

23,16

29,31

Xi
XC

6,15
P

Slika 2.3 i)
P

Slika 2.3 h)

14

2.3

NULTI SUSTAV
D

XDE

XT1

XAD

XDB

XT4

XAC

XCB

XT3

C
P
Slika 2.4: Ekvivalentna shema nultog sustava

D
48,4

72

84
XDE

E
B

XT1

XAD

84
XDB

132
XAC

102
XCB

31,11
XT4

19,01
XT3

C
P
Slika 2.4 a): Ekvivalentna shema nultog sustava s reaktancijama

A
48,4

72

84

XAD

XDB
XAB

X1
XAC

132

31,11
X4

XCB

102
X3 19,01

XAC3

XCB3

P
Slika 2.4 b)

15

X 12 = X 1 + X 2 +

X1 X 2
X3

X 13 = X 1 + X 3 +

X1 X 3
X2
X2 X3
X1
X CB + X 3 X CB + X AC X 3
X CB

X 23 = X 2 + X 3 +
X AC X 3 X AC
=
X CB

X AC 3 = X AC + X 3 +

132 19,01
= 175,61
102
X X 3 X CB X AC + X 3 X AC + X CB X 3
+ X 3 + CB
=
X AC
X AC

X AC 3 = 132 + 19,01 +
X CB 3 = X CB

102 19,01
= 135,7
132
X X CB X AC X 3 + X CB X 3 + X AC X CB
+ AC
=
X3
X3

X CB 3 = 102 + 19,01 +
X AB = X AC + X CB
X AB = 132 + 102 +

132 102
= 942,25
19,01

72

XAD

48,4
X1

84
XDB

31,11
X4

942,25
XAB
XAC3

XCB3

175,61

135,7

P
Slika 2.4 c)

X 1A =

X 4B =

X 1 X AC 3
48,4 175,61
=
= 37,94
X 1 + X AC 3 48,4 + 175,61
X 4 X CB 3
31,11 135,7
=
= 25,3
X 4 + X CB 3 31,11 + 135,7

16

72

84

XAD

XDB

942,25
XAB
XB

XA

XC
X1A

X4B

37,94

25,3
P

Slika 2.4 d)

XA =

37,94 942,25
= 35,53
37,94 + 942,25 + 25,3
X 4 B X AB
XB =
X 1 A + X AB + X 4 B

X 12 X 13
X1 =
X 12 + X 13 + X 23
X2 =

X 12 X 23
X 12 + X 13 + X 23

X3 =

X 13 X 23
X 12 + X 13 + X 23

XA =

25,3 942,25
= 23,7
37,94 + 942,25 + 25,3
X 1A X 4 B
XC =
X 1 A + X AB + X 4 B
XB =

XC =

X 1 A X AB
X 1 A + X AB + X 4 B

72

37,94 25,3
= 0,95
37,94 + 942,25 + 25,3

84

XAD

XDB

XA

XB

35,53

23,7
XC 0,95

Slika 2.4 e)
17

XA = XAD + XA = 72 + 35,53 = 107,53


XB = XDB + XB = 84 + 23,7 = 107,7
D
XA' 107,53

XB' 107,7

XC 0,95

Slika 2.4 f)
'

'

X AB =

XA XB
'

'
'

107,53 107,7
= 53,8
107,53 + 107,7

XA + XB
X0 = XAB + XC = 53,8 + 0,95 = 54,75
Z0 = j 54,75
D

54,75

X0
XAB'

53,8
P

XC

0,95

Slika 2.4 h)

Slika 2.4 g)

X i 29,31
=
= 0,53 < 1 mjerodavan je tropolni kratki spoj
X 0 54,75

18

Slika 2.5: Podruja omjera = Zi/Zd i = Zi/Z0 u kojima se pojavljuju najvee struje za
razliite vrste kratkog spoja

19

3 PRORAUN STRUJA KRATKOG SPOJA


3.1

JEDNOPOLNI KRATKI SPOJ


I&R
I&S

110
3
190,52
3E& d
3
=
= j1,497 kA
=
=
Z& d + Z&i + Z& 0 j 43,2 + j 29,31 + j 54,75 j127,26
= I& = 0
T

1
E& d
I&d = I&i = I&0 = I&R =
3
Z& d + Z&i + Z& 0

3.2

DVOPOLNI KRATKI SPOJ


I&R = 0

I&S + I&T = 0

110
3
&
3 Ed
110
3
I&S = I&T =
=
=
= j1,517 kA
&
&
Z d + Z i j 43,2 + j 29,31 j 72,51

I&S = I&d a 2 a
I&d = I&i =
3.3

E& d
;
Z& d + Z& i

I&T = I&d a a 2

I&0 = 0

DVOPOLNI KRATKI SPOJ SA ZEMLJOSPOJEM

I&R = 0

3Z& i + j 3 (Z& i + 2 Z& 0 )


1
3 j 29,31 + j 3 ( j 29,31 + 2 j 54,75)
110
=

=
I&S = E& d
2
Z& d Z& i + Z& i Z& 0 + Z& d Z& 0 2 3 j 43,2 j 29,31 + j 29,31 j 54,75 + j 43,2 j 54,75
7634,48 j 2792,13
j87,93 240,426
I&S = 31,754
=
= 1,45 + j 0,53 =
1266,19 1604,72 2365,2
5236,11
I& = 1,54 20,07 o kA
S

3Z& i j 3 (Z& i + 2 Z& 0 )


1
3 j 29,31 j 3 ( j 29,31 + 2 j 54,75)
110
=
=

I&T = E& d
2
Z& d Z& i + Z& i Z& 0 + Z& d Z& 0 2 3 j 43,2 j 29,31 + j 29,31 j 54,75 + j 43,2 j 54,75
j87,93 + 240,426
7634,48 j 2792,13
I&T = 31,754
=
= 1,45 + j 0,53 =
1266,19 1604,72 2365,2
5236,11
I& = 1,5420,07 o kA
T

I&R = I&d + I&i + I&0 = 0


E& d (Z& i + Z& 0 )
I&d =
Z& d Z& i + Z& i Z& 0 + Z& d Z& 0
E& d Z& 0
I&i =
Z& Z& + Z& Z& + Z& Z&
d

I&0 =
0

E& d Z& i
Z& d Z& i + Z& i Z& 0 + Z& d Z& 0

20

3.4

TROPOLNI KRATKI SPOJ


I&R

110
&
E
3
= d =
= j1,47 = 1,47 90 o kA
&
j 43,2
Zd
= I& a 2 = 1,47 90 o 1240 o = 1,47150 o kA

I&S
R
&I = I& a = 1,47 90 o 1120 o = 1,4730 o kA
T
R
&I + I& + I& = 0
R

E&
I&d = I&R = d
Z& d

I&i = 0

1
I&0 = (I&R + I&S + I&T ) = 0
3

4 RASPODJELA STRUJA U EKVIVALENTNIM SHEMAMA ZA


ZADANO MJESTO KS I MJERODAVNI KS
Mjesto kratkog spoja(KS) je sabirnica D, a mjerodavni KS je tropolni kratki spoj.

j43,2

j26,37

d
G

110
3

d = -j1,47kA

d = -j1,47kA

j16,83

d = -j1,47kA
G

Slika 4.1

Slika 4.2
Za tropolni KS vrijedi:

110
E&
I&R = d = 3 = j1,47 = 1,47 90 o kA
j 43,2
Z& d
2
I&S = I&R a = 1,47 90 o 1240 o = 1,47150 o kA
I& = I& a = 1,47 90 o 1120 o = 1,4730 o kA
T

I&R + I&S + I&T = 0


E&
I&d = I&R = d = j1,47kA
Z&
d

I&i = 0

1
I&0 = I&R + I&S + I&T = 0
3

21

I&1 = j1,47kA

D
j45,57

Sa strujnim djelilom dobiju se druge dvije struje :


j 62,63
I&2 = I&1
= j 0,85kA
j 45,57 + j 62,63
I& = I& I& = j1,47 + j 0,85 = j 0,62kA

j62,63

3
1

ili

j16,83

U AD = I&1 Z& AD = j1,47 j 26,37 = 38,76kV


U
38,76kV
I&2 = AD' =
= j 0,85kA
j 45,57
ZA

G
P

U
38,76kV
I&3 = AD' =
= j 0,62kA
j 62,63
ZB

Slika 4.2 a)

U1 A = I&1 Z& C + I&2 Z& A


D

j24

j28

AD

DB

j21,57

C
1A

j49,16

U 4 B = 24,74 + 21,47 = 46,21kV


U = I& Z& + I& Z&
AB

U
43,075kV
I&5 = 1 A =
= j 0,876kA
&
Z1 A
j 49,16

j78,92

j 0,03 j 0,59 = j 0,62kA


I&5 I&4 = I&2

U
46,21kV
I&6 = 4 B =
= j 0,586kA
&
Z4B
j 78,92
U
3,136kV
I&4 = AB =
= j 0,031kA
Z& AB
j100,19

j24

j28

AD

j 0,88 j 0,59 = j1,47kA


I&4 + I&6 = I&3

4B

Slika 4.2 b)

U AB = ( j1,47 ) j 21,57 + ( j 0,62) j 34,63

U AB = 18,33 + 21,47 = 3,136kV

Pr ovjera dobivenih rezultata :


I& + I& = I&

j16,83

U 4 B = j1,47 j16,83 + ( j 0,62) j34,63

j34,63

U1 A = 24,74 + 18,33 = 43,075kV


U = I& Z& + I& Z&

AB
A

U1 A = j1,47 j16,83 + ( j 0,85) j 21,57

4B

j100,19

DB

j100,19

AB

j 0,88 + j 0,03 = j 0,85kA


1

1A

j49,16

4B

j78,92
P

Slika 4.2 c)

22

A
j65,34

12

j24

DB

j162,48
4

j100,19

52

j28

AD

AB

AC3

61

51

j198,64

62

CB3

j153,49

Slika 4.2 d)

j162,48
= j 0,586kA 0,514 = j 0,301kA
j153,49 + j162,48
j153,49
= I&6
= I&6 I&61 = j 0,586kA ( j 0,301kA) = j 0,285kA
j153,49 + j162,48
j 65,34
= I&5
= j 0,876kA 0,247 = j 0,217 kA
j 65,34 + j198,64
j198,64
= I&5
= I&5 I&51 = j 0,876kA ( j 0,217 kA) = j 0,659kA
j 65,34 + j198,64

I&61 = I&6
I&62
I&51
I&52

j130,68 A
1

j130,68

G2

j24

j28

AD

DB

G1

AB
AC

4
B

j44

j162,48

CB

j34

62

3 j67,41
AC3
51

61

CB3

Slika 4.2 e)

I&A = I&51 I&4 = j 0,217kA ( j 0,031kA) = j 0,186kA


I&B = I&61 + I&4 = j 0,301kA + ( j 0,031kA) = j 0,332kA
I&C = I&51 + I&61 = j 0,217 kA + ( j 0,301kA) = j 0,332kA
I&
j 0,659kA
I&G1 = 52 =
= j 0,329kA
2
2
I&
j 0,659kA
I&G 2 = I&G1 = 52 =
= j 0,329kA
2
2

23

1 = -j1,47 kA

2 = -j0,85 kA

3 = -j0,62 kA

A = -j0,19 kA

B = -j0,33 kA

62 = -j0,29 kA

G1 = -j0,33 kA

G2 = -j0,33 kA

C = -j0,52 kA

P
Slika 4.3: Jednopolna shema sustava

Provjera rezultata:

I&1 = I&G1 + I&G 2 + I&C + I&62 = j 0,33kA j 0,33kA j 0,52kA j 0,29kA = j1,47kA
I&1 = I&2 + I&3 = j 0,85kA j 0,62kA = j1,47kA

5 STRUJE FAZA R, S i T
JEDNOPOLNI KS

I&R = 3 I&d
I&S = I&T = 0
TROPOLNI KS
I&R = I&d
I&S = I&R a 2
I& = I& a
T

5.1

STRUJE FAZE R

5.1.1 Struje vodova


I&

AC

I&B C
I&

A D

= I&A = j 0,19kA = 0,19 90o kA


= I&B = j 0,33kA = 0,33 90o kA
= I& = j 0,85kA = 0,85 90o kA
2

I&B D = I&3 = j 0,62kA = 0,62 90o kA

24

5.1.2 Struje transformator sabirnica


I&
= I& = j 0,33kA = 0,33 90 o kA
T 1 A

G1

I&T 2 A = I&G 2 = j 0,33kA = 0,33 90 o kA


I&T 3C = I&C = j 0,52kA = 0,52 90 o kA
I&
= I& = j 0,29kA = 0,29 90 o kA
T 4 B

5.2

62

STRUJE FAZE S

5.2.1 Struje vodova


I&AC = a 2 I&R = 1240o 0,19 90o kA = 0,19150o kA
I& = a 2 I& = 1240o 0,33 90o kA = 0,33150o kA
B C

I&A D = a 2 I&R = 1240o 0,85 90o kA = 0,85150o kA


I&B D = a 2 I&R = 1240o 0,62 90o kA = 0,62150o kA
5.2.2 Struje transformator sabirnica
I&
= a 2 I& = 1240o 0,33 90o kA = 0,33150o kA
T 1 A

I&T 2 A = a 2 I&R = 1240o 0,33 90o kA = 0,33150o kA


I&T 3C = a 2 I&R = 1240o 0,52 90o kA = 0,52150o kA
I&T 4 B = a 2 I&R = 1240o 0,29 90o kA = 0,29150o kA
5.3

STRUJE FAZE T

5.3.1 Struje vodova


I&AC = a I&R = 1120o 0,19 90o kA = 0,1930o kA
I& = a I& = 1120o 0,33 90o kA = 0,3330o kA
B C

I&A D = a I&R = 1120o 0,85 90o kA = 0,8530o kA


I&B D = a I&R = 1120o 0,62 90o kA = 0,6230o kA
5.3.2 Struje transformator sabirnica
I&
= a I& = 1120o 0,33 90o kA = 0,3330o kA
T 1 A

I&T 2 A = a I&R = 1120o 0,33 90o kA = 0,3330o kA


I&T 3C = a I&R = 1120o 0,52 90o kA = 0,5230o kA
I&T 4 B = a I&R = 1120o 0,29 90o kA = 0,2930o kA

25

6 STRUJE GENERATORA ODNOSNO PRIMARA


TRANSFORMATORA
6.1

JEDNOPOLNI KS

1
I&d = I&R
3

I&R'' = 0,886 I&d + j 0,5I&d


I&S'' = I&T'' = 0
6.2

TROPOLNI KS
I&R'' = 0,886 I&d + j 0,5 I&d
I&S'' = 0,886 I&d + j 0,5 I&d
I&'' = jI&
T

I&d = I&R

6.2.1 Struje generatora G1


I&R'' G1 = 0,886 ( j 0,33) + j 0,5 ( j 0,33) = j 0,286 + 0,165 = 0,165 + j 0,286kA
I&S'' G1 = 0,886 ( j 0,33) + j 0,5 ( j 0,33) = j 0,286 + 0,165 = 0,165 j 0,286kA
I& '' = j ( j 0,33) = 0,33kA
T G1

6.2.2 Struje generatora G2


I&R'' G 2 = 0,886 ( j 0,33) + j 0,5 ( j 0,33) = j 0,286 + 0,165 = 0,165 + j 0,286kA
I&S'' G 2 = 0,886 ( j 0,33) + j 0,5 ( j 0,33) = j 0,286 + 0,165 = 0,165 j 0,286kA
I& ''
= j ( j 0,33) = 0,33kA
T G 2

6.2.3 Struje generatora G3


I&R'' G 3 = 0,886 ( j 0,52 ) + j 0,5 ( j 0,52 ) = j 0,45 + 0,26 = 0,26 + j 0,45kA
I&S'' G 3 = 0,886 ( j 0,52 ) + j 0,5 ( j 0,52 ) = j 0,45 + 0,26 = 0,26 j 0,45kA
I& ''
= j ( j 0,52 ) = 0,52kA
T G 3

6.2.4 Struje generatora G4


I&R'' G 4 = 0,886 ( j 0,29 ) + j 0,5 ( j 0,29 ) = j 0,25 + 0,145 = 0,145 + j 0,25kA
I&S'' G 4 = 0,886 ( j 0,29 ) + j 0,5 ( j 0,29 ) = j 0,25 + 0,145 = 0,145 j 0,25kA
I& ''
= j ( j 0,29 ) = 0,29kA
T G 4

Red.br.

KS

Zd()

Zi()

Z0()

j 43,2

j 29,31

j 54,75

Zi /Z0
- vrsta
KS
0,53 3pks

Id (kA)

1pKS
(IR-kA)

2pKS
(IS-kA)

2pzKS
(IS-kA)

3pKS
(IR-kA)

-j 1,47

-j 1,497

-j 1,517

1,45+j0,53

-j 1,47

Za struje sabirnica mora vrijediti I K.Z.:

I&
i =1

=0

26

7 TROPOLNA SHEMA RASPODJELA STRUJA U MREI ZA VRIJEME TROPOLNOG KRATKOG SPOJA

D
-j1,47

-1,03 +j1,05
0,23 +j1,45

0,165+j0,286

-j0,33

-j0,85

-j0,62

0,165-j0,286

-0,23+j0,24

-0,59+j0,61

-0,43+j0,44

-0,33

0,03+j0,19

0,13+j0,84

0,10+j0,61

0,165+j0,286

-j0,33

-j0,19

-j0,33

0,165-j0,286

-0,23+j0,24

-0,13+j0,14

-0,23+j0,24

-0,33

0,03+j0,19

0,03+j0,19

0,05+j0,33

0,26+j0,45

-j0,52

0,26-j0,45

-0,36+j0,37

-0,52

0,08+j0,51

0,145+j0,25

0,145+j0,25

-0,2+j0,21

0,145-j0,25

0,04+j0,29

-0,29

Slika 7.1: Tropolna shema struja u mrei za vrijeme tropolnog KS