Sie sind auf Seite 1von 25

4.

Platform / Area nomenclature Guidelines:


a. New platform or area which is similar to existing facilities should carry the same
existing facility name by adding sequence number such as CSP, CSP-1 or NRP,
NRP-1.
b. New facilities with new operation concept should carry an abbreviated name
agreed between project team and ESVT i.e. SARB, UL, GIF, GPF and TA etc
c. Area number for all new facilities will be assigned by Engineering Record officer.

5.

AVEVA PDMS
PDMS project folders, files, databases including any foreign project data, templates, reports
and all relevant document/ information associated with the project shall be submitted to
ADMA-OPCO.
The PDMS environment shall be set-up in accordance with this document.

5.1

Project Set-up
PDMS System administration of the Project set up shall be documented in detail and
submitted for ADMA-OPCO approval prior to modeling.
This shall include all team names, user names & passwords, administration
passwords, MDB/ database names/ numbers with description, design hierarchy &
naming convention with description.
All UDAs required for the project shall be documented and submitted for ADMAOPCO approval.

5.2

Model Content
The individual areas of the detailed 3D model shall be the responsibility of the
respective engineering/design disciplines. Each discipline shall define and document
the items that are to be modeled in PDMS in their respective areas.
Any exclusion to the model content is subject to written approval by ADMA-OPCO.
The following shall be modelled as a minimum.

1a.0
Rev.

Structure:
Primary and secondary and tertiary steelwork (Columns, Beams, Bracings)
Joints complete with details.
Floor, grating, plating and walls including penetration & sleeves and
fireproofing.
Jacket appurtenances, boat landing, riser fender, J-tube, Caissons, anodes
Stairs, ladders, access/ maintenance platforms, walkways, handrails and kick
plates.

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
51

Structural supports and guides for equipment, piping, trays, ducts.


Equipment handling fixtures like crane, monorail, lifting hoist, pulley/ chain
block
Installation aids i.e. lifting pad eyes/ trunnions.

Equipment:
Process and Utility equipment (to shape) shown on P&ID/ Equipment list
including within package/ skid complete with appurtenances such as nozzles,
hand hole, manway, covers, and davits
Major proprietary and ancillary items.
Saddles, supports and any fixing mechanism.
Door/ cover swing and access volume.
Installation/ handling volumes and aids i.e. lifting pad eyes/ lugs, slings...
Jacket/ insulation volume complete with aids like rings, cleats...
Reinforcement items, platform/ support cleats.
Reserved volume for withdrawal/ removal, operation/ maintenance/ access,
dropout zone, handling space etc
Future equipment (Modelled in separate Zone).

Piping:
All process, auxiliary and utility piping (including piping covered under
legend drawing), piping within package/ skid (including vendor scope).
Vessel trim, bridle complete with instrument.
Inline items, fittings, accessories, special items, valves & instruments
complete with manual/ gear/ actuated operators and space required for
operation.
Insulation, jacket as per specification.
Vent, drain, instrument tapping/ connection, utility station.
Pipe supports.
Reserved volume for operation/ maintenance, removal and handling/
retrieving tools.
Conductors/ risers.
Bolt removal envelop to ensure no captive bolts and space for torqueing/
tensioning equipment.
All future piping (Modelled in separate Zone).

Electrical and Instrumentation:


All equipment e.g. generator, transformer, switchgear, MCC, LCS
Accessories for valve actuators.
Cable trays/ ladders with support, J-Tube.

1a.0
Rev.

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
52

Electrical/ instrument panels & cabinets complete with door swing,


maintenance/ access volume, stanchion.
Junction box, Marshalling box, Distribution box, termination box
Lighting fixtures, power sockets, switches, Nav-aid
Field instruments with support/ stanchion and shade.
Radio mast/ tower.

HSE:
All equipment i.e. Firefighting, safety, Lifeboat/ raft with davit, life buoy
Deluge/ Foam skid (with piping), deluge and sprinkler system with coverage
envelop.
Fire mains, fire hydrants/ monitors, hose reel..
Primary & secondary escape route/ volume with indicators/ signage and
muster area.
F&G detection, PA system, Telecom, CCTV, beacon, sounder
Maintenance/ operation/ access volume, lay-down & material handling
volume, dropout zone, crane & lifting hoist movement area/ volume.
Hatches, access openings with protective barriers.
Safety shower, eyewash.

HVAC:
All equipment e.g. Chiller, Air handling unit, Compressor unit, Window
AC
All piping (i.e. chilled water, refrigeration) with inline items, accessories,
instruments, valves, actuators
Ductwork with accessories, dampers, actuators, grilles..
Support for equipment, ductwork, piping.
Duct and pipe insulation.
Reserved space/ volume for maintenance, handling..

Architectural and Civil:


Foundations for structure & support, sleepers, piles, etc ..
Building detailing doors and windows.

1a.0
Rev.

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
53

5.3

Database and Naming


The project shall be split into Multiple Databases (MDBs) based on Area for Das
Island and Platform for Offshore. Area number shall be MDB Name. e.g.:
MDB Name
08.3
201

MDB Description
Das - Zakum Separator Area
ZWSC - Riser Platform

Each discipline shall be allocated databases based on the PDMS activity.


Databases numbers shall be obtained from ADMA-OPCO. Database file number shall
be same as database number. Sequential numbers shall be used without skipping except
for temporary DBs (which are to be deleted upon as built) which shall use end of the
range, to maintain continuity of the numbers.
Naming format of all administrative elements and databases with description to have
a suitable convention.
Details of the naming convention and coding explanations used to be submitted to
ADMA-OPCO for approval.
An example database name and description is given below for information only:
DB Name: 201+DES+PIPE+01

e.g. 201DESPIPE01
= Serial Number (Incremental for same DB name)
= Discipline Code
= Database Type Code
= Area number / MDB name
DB Description: Piping Design DB for ZWSC - Riser Platform
Database Type Code
Data Base Type

1a.0
Rev.

Code

Data Base Type

Code

Design (DESI)

DES

Dictionary (DICT)

DIC

Draft (PADD)

DRA

ISODRAFT (ISOD)

ISO

Catalogue (CATA)

CAT

Schematic (SCHE)

SCH

Properties (PROP)

PRO

Engineering (ENGI)

ENG

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
54

Discipline Code
Discipline

Description

Codes

Structure (offshore topside)*

Structural Discipline

STRU

Structure (offshore Jacket)*

Structural Discipline

JCKT

Civil

Civil

CIVL

Architecture

Architecture

ARCH

Support

Support

SUPP

Equipment

Mechanical Discipline

EQUI

Piping

Mechanical Discipline

PIPE

Instrumentation

Instrumentation Discipline

INST

Electrical

Electrical Discipline

ELEC

HVAC

HVAC

HVAC

Safety

HSE discipline

HSE

General

General Purpose

GEN

Catalogue

PDMS Administration Discipline

CATA

* Discipline code STRU & JCKT for offshore and STRU for onshore shall be used.
5.4

Catalogues and Specifications Naming


All items shall be named in accordance with the catalogues component naming convention as
supplied with PDMS. There shall be project specific catalogue databases for components
and/or data items that are created for the project.
Catalogues and Specifications (e.g. Piping, Structural, etc.) shall be developed to ADMAOPCO standards and any deviations are to be noted and submitted to ADMA-OPCO for
approval.

5.5

PDMS Design Hierarchy


PDMS Design Sites and Zones shall be named (as illustrated below) in a manner such that
they can be easily identified and organised against plant area and discipline. Sites and Zones
shall have their description and purpose attributes set to reflect their intended use. Naming
format with description shall be submitted for ADMA-OPCO approval.

1a.0
Rev.

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
55

Site Naming
Sites shall be created and named in line with the respective DB for all disciplines with
the Datum Point and Purpose set for it. Site naming shall be in the following format:
Site Name:
=XXXPIPE
Where PIPE
=Discipline Code
XXX
=Area number/ MDB name
e.g.: Site name for Piping in area 201 (ZWSC Riser Platform) shall be /201PIPE.

Zone Naming
Zone naming will vary as per the discipline need. All zones created shall be named
appropriately and to follow the explained convention. For offshore Zone naming is
generally deck based and for Onshore it is based on type.

Pipe Zone Naming


All pipes shall be modelled in proper zone which is based on process service code. The
zone name shall be as follows:
/201PIPE/NNNN

e.g. /201PIPE/CO
Process Service Code
Site Name (Area Number/ MDB name +
Discipline Code)
e.g.: Pipe having service code CO shall be created in zone /201PIPE/CO.
Detailed hierarchy as follows:
Site > /201PIPE
Zone> /201PIPE/CO
Zone> /201PIPE/LO
Zone> /201PIPE/PW

> /CO-16-AC0NA0-1234AD
> /CO-18-AC0NA0-2345AD
> /CO-20-AC0NA0-3456AD

Equipment Zone Naming


All mechanical equipment (with proper origin) shall be modelled under equipment zone.
For offshore zones shall be deck based. Where equipment crosses into multiple decks it
shall be modelled under deck on which it rests. The zone naming shall be as follows:
For Onshore
08.3EQUI/NNNN

1a.0
Rev.

e.g.

/08.3EQUI/Static
Equipment type: Static/ Rotating
Site Name (Area Number/ MDB name +
Discipline Code)

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
56

For Offshore
201EQUI/NNNN

e.g.

/201EQUI/Deck name
Deck name (where necessary)
Site Name (Area Number/ MDB name +
Discipline Code)

Future equipment shall be created in separate zone as follows:


/201EQUI/FUTURE

e.g.

/201EQUI/FUTURE

Site Name (Area Number/ MDB name + Discipline Code)


Detailed hierarchy as follows:
/201EQUI/DECK NAME
/201EQUI/PACKAGE:

For modelling Mechanical equipment.


For modelling Mechanical package unit.

Detailed Hierarchy as follows:


Site > /201EQUI
Zone> /201EQUI/MAINDECK
Zone> /201EQUI/PACKAGE
/EQUI> /201-C-1234
NOZZ> /201-C-1234/N1
/EQUI> /201-P-1234
NOZZ> /201-C-1234/N2
/EQUI> /201-T-1234
SUBE> /201-C-1234/Platform-Clips
/EQUI> /201-V-1234
SUBE> /201-C-1234/Ladder-Clips
SUBE> /201-C-1234/Supp-Clips
SUBE> /201-C-1234/Earthing-Boss
SUBE> /201-C-1234/Name-Plate
SUBE> /201-C-1234/Fixed-Saddle
SUBE> /201-C-1234/Sliding-Saddle
SUBE> /201-C-1234/Davit-XXX (Each davit to be SUBE and named appropriately)
SUBE> /201-C-1234/Boot
SUBE> /201-C-1234/Rein-Pad
SUBE> /201-C-1234/Insulation
SUBE> /201-C-1234/Access-Way/ Platform
SUBE> /201-C-1234/Reserved-Volume
SUBE> /201-C-1234/Reserved-Volume: Area /volume required/ reserved for operation and
maintenance of the equipment.

Nozzle Naming
Nozzle names shall be equipment tag/nozzle number. e.g. /201-C-1234/N1

1a.0
Rev.

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
57

Civil/Structure Zones:
Zone naming for Civil/ Structure for Offshore shall be deck based and as follows:
For Onshore Zone naming, sub division shown under deck shall be used (e.g.:
STRUCTURE, LAD-STAIR, HANDRAIL ).

/201STRU/HELI DECK
/201STRU/VALVE ACCESS DECK
/201STRU/MAIN DECK
/201STRU/CELLAR DECK
Detailed Hierarchy as follows:
Site > /201STRU
Zone> /201STRU/MAIN DECK
structure.

Deck Code shall be used at /STRU> level and below


/STRU>MDK/STRUCTURE For modelling main
/STRU>MDK/LAD-STAIR
/STRU>MDK/HANDRAIL
/STRU>MDK/GRATING
/STRU>MDK/SUPPORT

For modelling ladder &


staircase.
For modelling handrail.
For modelling grating
/flooring.
For modelling all
supports.

/FRMW>MDK/COLUMN
/FRMW>MDK/BEAM
/FRMW>MDK/BRACING
Access/ Maintenance platforms shall be created at /STRU> level and named appropriately.
All sections (SCTN) under framework shall be properly tagged.
Items like stiffeners shall be clubbed together and created under sub-framework and tagged
appropriately (as per the structure they belong to).
Deck Codes:

1a.0
Rev.

Deck/ Area Level

Code Deck/ Area Level

Code

Heli Deck

HED

MZD

Mezzanine Deck

Above Weather Deck AWD Valve Access Deck

VAD

Weather Deck

WED Sub Cellar Deck

SCD

Solar Panel Deck

SPD

SDK

Main Deck

MDK Jacket Walkway and Boat Landing

Cellar Deck

CDK

Sump Deck

BLL

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
58

Similar convention shall be followed for Jacket.

Electrical Zones
Zone naming for Electrical shall be as follows:

/201ELEC/CABLE_TRAY-HI:
/201ELEC/CABLE_TRAY-LO:
/201ELEC/EQUI-Deck Name:

For modelling Electrical high voltage cable tray.


For modelling Electrical low voltage cable tray.
For modelling Electrical equipment (Transformer,
Panels, DB, Bus duct etc.) based on deck for
offshore and one zone for onshore.

/201ELEC/SMALL-POWER-EQUIP:

For modelling Electrical lighting fixture & poles


etc.
For modelling Electrical heat tracing equipment.

/201ELEC/EHT-SYSTEM:
Detailed Hierarchy as follows:
Site > /201ELEC
Zone> /201ELEC/CABLE_TRAY-HI
Zone> /201ELEC/CABLE_TRAY-LO
Zone> /201ELEC/EQUI-Deck Name

/PIPE> CABLE_TRAY-HI-150
/PIPE> CABLE_TRAY-HI-200
/PIPE> CABLE_TRAY-HI-300
/PIPE> CABLE_TRAY-HI-400

/STRU> DBs
/STRU> RTU
/STRU> PANELS
/STRU> TRANSFORMER
/STRU> SWITCH-GEAR
All equipment shall be created with proper origin.

Instrument Zones

Zone naming for Instrument shall be as follows:


/201INST/F&G:
/201INST/EQUI:
/201INST/TEL-EQUIP:
/201INST/MANIFOLD:
/201INST/CABLE-TRAY:
/201INST/V-BOTTLE:

For modelling fire and gas detector.


For modelling instrument equipment.
For modelling telecom equipment, CCTV, PA system.
For modelling instrument air manifold.
For modelling instrument cable tray.
For modelling Volume bottle.

Detailed Hierarchy as follows:


Site > /201INST
Zone> /201INST/CABLE-TRAY
1a.0
Rev.

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
59

Zone> /201INST/EQUI
Zone> /201INST/CABLE-TRAY
Zone> /201INST/EQUI
/PIPE> CABLE_TRAY-150
/PIPE> CABLE_TRAY-200
/PIPE> CABLE_TRAY-300
/STRU> JBOX
/STRU> MBOX
/STRU> LOC-PANEL
/STRU> ANA-PANEL
/STRU> STANCHIONS
All equipment shall be created with proper origin.

Safety Zones

Zone naming for HSE shall be as follows:


/201HSE/EQUI:
/201HSE/ESCAPE-ROUTE:
/201HSE/LAYDOWN:
/201HSE/ACCESS:

For modelling firefighting & safety equipment.


For modelling escape routes.
For modelling laydown area.
For modelling access and maintenance volume.

Detailed Hierarchy as follows:


Site > /201HSE
Zone> /201HSE/EQUI

/EQUI> Lifeboat-001(assigned tag shall be used)


/EQUI> Lifebouy-001
All equipment shall be created with proper origin.

Support Zones:

/201SUPP/PIPE
/201SUPP/ELEC
/201SUPP/INST
/201SUPP/HVAC
Detailed Hierarchy as follows:
Site > /201SUPP
Zone> /201SUPP/PIPE

/STRU>MDK/SUPP
/STRU>VAD/SUPP
/STRU>CDK/SUPP
Deck Code shall be used at /STRU> level and below for offshore.

1a.0
Rev.

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
60

Equipment Origin:
All equipment shall have a logical origin which can aid in its placement. Following are
examples of origin for some equipment.

1a.0
Rev.

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
61

VERTICAL VESSEL/ COLUMN/ CYCLONE

SHELL & TUBE EXCHANGER

ELEVATION

PLAN

CENTRELINE OF EXCHANGER &


INLET/ OUTLET NOZZLES
REBOILER

T/L

ELEVATION
CENTRELINE OF TUBE BUNDLE
& CENTRELINE OF TUBE INLET

ELEVATION
CENTRELINE OF EQUIPMENT & BOTTOM TAN LINE

PLAN

FIN-FAN COOLERS &


CONDENSERS

S.S

HORIZONTAL VESSEL
F.S

PLATE EXCHANGER

PLAN

T/L

PLAN

CL

CL

ISO VIEW
CENTRELINE & FLANGE FACE
OF LOWER RIGHT HAND NOZZLE

1a.0
Rev.

ELEVATION
CENTRELINE OF EQUIPMENT &
TAN LINE NEAR FIXED SUPPORT

ELEVATION
CENTRELINE & FLANGE FACE
OF INLET NOZZLE

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
62

HORIZONTAL PUMP, BLOWER


& FAN, HORZ. ROTARY
EQUIPMENT & DRIVER

POSITIVE
DISPLACEMENT PUMP

VERTICAL PUMP

PLAN

DISCH.

PLAN

CL

ELEVATION
CENTRELINE OF PUMP
& DISCHARGE NOZZLE

COMPRESSOR PACKAGE

PLAN

ELEVATION
CENTRELINE OF PUMP
& DISCHARGE NOZZLE

ISO VIEW
CENTRELINE & FACE
OF SUCTION FLANGE

SKID/PACKAGE

PRINTED CIRCUIT
EXCHANGER

PLAN

EL

ELEVATION
CENTRELINE OF EQUIPMENT & BOTTOM
OF BASE AT SOUTH OR WEST END

1a.0
Rev.

ISO VIEW
BOTTOM OF BASE AT
SOUTH WEST CORNER

ELEVATION
CENTRELINE OF EQUIPMENT
& TUBE INLET

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
63

PIG LAUNCHER
& RECEIVER

RECTANGULAR STORAGE
TANK OR VESSEL

PLAN

PLAN

PLAN

ISO VIEW
BOTTOM OF BASE AT
SOUTH WEST CORNER

ISO VIEW
CENTRELINE OF EQUIPMENT
& INLET NOZZLE

ISO VIEW
CENTRELINE AT FACE OF
FACE OF FLANGE

STORAGE TANK

VERTICAL SUBMERGED
PUMP

FILTER/ STRAINER

LIFEBOAT & DAVIT

ISO VIEW
MID WAY BETWEEN
SUPPORTS & TOP OF STEEL

PUMP

CRANE

MOTOR
CENTRELINE &
BOTTOM OF BASE PLATE

ISO VIEW
CENTRELINE OF PUMP
& DISCHARGE NOZZLE

For E&I Cabinets/ Panels -

1a.0
Rev.

ISO VIEW
BASE OF PEDESTAL

Centre bottom of back side/ panel.

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
64

5.6

Tagged Items
All tagged items shall be named as per their Tag ID as given on P&IDs, plot-plans,
datasheets, lists, etc. and as per specified tagging philosophy. Any deviations shall be
documented and submitted to ADMA-OPCO for approval. This applies to but is not limited
to:
a.
b.
c.
d.
e.
f.

Equipment
Nozzles
Pipes
In-line piping items, i.e. Orifice Plates, Instruments, Valves, Filters, etc.
Steelwork i.e. columns, beams, stair, ladder, access platform etc.
Electrical & Instrument Cable Tray, Equipment, i.e. Junction Boxes, Control Panels,
etc.
g. Supports

5.7

Pipe Supports
AVEVA Multi-Discipline Supports (MDS) software shall be used for the 3D design of all
Pipe work supports in PDMS.
The catalogue, specification, design and drawing databases for VPD-MDS that are used on
the project complete with any modifications shall be submitted to ADMA-OPCO as part of
the project deliverable.
Support numbering shall comply with ADMA-OPCO numbering procedure.
E.g. 201-PS-00001
= Sequence Number
= Pipe Support
= Area number/ MDB name
PS = Pipe Support
TS = Cable Tray Support
SPS = Special Support

5.8

Colours
Colours specified in the following table which is basic identification colour (first band
colour) specified in ADMA-OPCO painting manual MNL-01 shall be used for PDMS model,
draft and review model.

1a.0
Rev.

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
65

1.0 - STRUCTURE
SL.
No
.

3D Model Item

ADMA Basic Colour

PDMS
Colour
Name

PDMS
DRAFT
Colour

Auto
Cad
Colour

1.1

STRUCTURE - JACKET

BLACK

15

1.2

STRUCTURE - DECK

IVORY

185

1.3

STEEL GRATING

BLACK

15

1.4

GRP - GRATING

YELLOW

31

1.6

PLATING

LIGHT
GREY

CYAN

56

PDMS
Review
Colour

255,255,
240

2.0 MECHANICAL

2.1

EQUIPMENT - NEW

2.3

EQUIPMENT (FUTURE)
PIPING (FUTURE)

STEEL BLUE

67

165

2.3

HANDLING EQUIPMENT,
WAYS/VOLUMES

DARKSLATE

46

117

1a.0
Rev.

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
66

3.0 ELECTRICAL
SL.
No.

3D Model Item

PDMS
Colour
Name

ADMA Basic Colour

PDMS
DRAFT
Colour

Auto
Cad
Colour

3.1

ELECTRICAL HIGH
VOLTAGE CABLE TRAYS

RED

11

3.2

LOW VOLTAGE CABLE


TRAY

MAGENTA

71

3.3

ELECTRICAL EQUIPMENT
(CONTROL PANELS)

LIGHT
GREY

140

30

PDMS
Review
Colour

4.0 INSTRUMENTATION
4.1

INSTRUMENTATION TRAY
/ LADDER

ORANGE

4.2

INSTRUMENT EQUIPMENT
(CONTROL PANELS)

LIGHT
GREY

5.0 HSE

AND

YELLOW WITH BLACK DIRECTIONAL


ARROWS AT 5 METER INTERVALS & AT
CHANGE OF DIRECTION.

5.1

SAFETY PATH

5.2

FIRST AID EQUIPMENT

DARKSLATE

167

127

5.3

SAFETY NET SUPPORTS

RED

11

5.4

FIRE FIGHTING FACILITIES

RED

11

1a.0
Rev.

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
67

6.0 PIPING
SL.
No.

3D Model Item

PDMS
Colour
Name

ADMA Basic Colour

PDMS
DRAFT
Colour

Auto
Cad
Colour

6.1

CRUDE OIL (LIVE)

BROWN

26

6.2

CRUDE OIL (STABILIZED)

BROWN

26

6.3

CRUDE OIL (EXPORT)

BROWN

26

6.4

SEPARATED OIL

BROWN

26

6.5

RECOVERED OIL

BROWN

26

6.6

SOUR GAS (WET)

SALMON

322

21

6.7

SOUR GAS (DRY)

SALMON

322

21

SALMON

322

21

SALMON

322

21

6.8
6.9

SWEET GAS (WET)


< 100 PPM H2S
SWEET GAS (DRY)
< 100 PPM H2S

6.10

FLARE GAS

SALMON

322

21

6.11

CONDENSATE

SALMON

322

21

6.12

GAS CONDENSATE

SALMON

322

21

6.13

FUEL GAS

SALMON

322

21

6.14

RELIEF VENT

SPRING
GREEN

127

110

6.15

PROPANE

SALMON

322

21

6.16

PILOT GAS TO FLARE

SALMON

322

21

6.17

REBOILER VENT GAS

SALMON

322

21

6.18

GAS TO ATMOSPHERE

SALMON

322

21

6.19
6.20

HALON
INERGEN

STEEL BLUE
STEEL BLUE

160
160

142
142

6.21

VACUUM

STEEL BLUE

160

142

6.22

NITROGEN

STEEL BLUE

160

142

6.23

OXYGEN

STEEL BLUE

160

142

6.24

INSTRUMENT AIR

STEEL BLUE

160

142

6.25

INDUSTRIAL AIR

STEEL BLUE

160

142

6.26

CHLORINE GAS

STEEL BLUE

160

142

6.27

CARBON DIOXIDE

STEEL BLUE

160

142

6.28

FIRE WATER

RED

11

6.29

FOAM (FIRE FIGHTING)

RED

11

1a.0
Rev.

PDMS
Review
Colour

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
68

SL.
No.

3D Model Item

ADMA Basic Colour

PDMS
PDMS
DRAFT
Colour Name
Colour

Auto
Cad
Colour

6.30

ACID

MAUVE

12

204

6.31

CAUSTIC SODA

MAUVE

12

204

6.32

STEAM

LIGHT GREY

6.33

STEM CONDENSATE

LIGHT GREY

6.34

BUNKER FUEL

BLACK

15

6.35

AVIATION FUEL

BLACK

15

6.36

FURNACE FUEL

BLACK

15

6.37

KEROSINE

BLACK

15

6.38

GASOLINE

BLACK

15

6.39

DEISEL OIL

BLACK

15

6.40

LUBE OIL

BLACK

15

6.41

HYDRAULIC OIL

BLACK

15

6.42

SEA WATER

FOREST GREEN

101

84

6.43

HOT WATER

FOREST GREEN

101

84

6.44

SOUR WATER

FOREST GREEN

101

84

6.45

COOLING WATER

FOREST GREEN

101

84

6.46

UTILITY WATER

FOREST GREEN

101

84

6.47

POTABLE WATER

FOREST GREEN

101

84

6.48

BALLAST WATER

FOREST GREEN

101

84

6.49

INJECTION SEA WATER

FOREST GREEN

101

84

6.50

BOILER FEED WATER

FOREST GREEN

101

84

6.51

EFFLUENT WATER

FOREST GREEN

101

84

6.52

DEOXYGENATED SEA
WATER

FOREST GREEN

101

84

1a.0
Rev.

PDMS
Review
Colour

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
69

5.9

Draft Drawings Rules, Libraries, etc


All 2D Drawing Production Administration elements, e.g. Rules, Libraries,
Templates, etc. shall be named and documented accordingly and submitted to
ADMA-OPCO for approval.

5.10

Draft Drawing Databases Structure


Drawing databases shall be created in a structured manner to reflect the design areas
and disciplines, consideration given to maximize drawing production.
Drawings and Sheets shall be named/ numbered in accordance with ADMA-OPCO
document/ drawing numbering procedure.
All dimensioning & annotation shall be done in draft and shall be intelligent. The
extent of annotation and quality of the drawing shall be as specified in CP-00 Part-3.
Modifying/ editing drawings outside PDMS shall not be accepted.
Zone based layers shall be created and all items within the zone shall be placed in the
same layer.
The 2D drawing representation within PDMS shall adhere to ADMA-OPCO
standards and be subject to ADMA-OPCO approval.
All drawings shall be fully updated to reflect the as-built 3D plant model upon
completion of the project and prior to hand over.
DWG and DXF format copy of all 2D project drawings produced within PDMS to be
provided to ADMA-OPCO.

Draft Naming Convention


Drawing Type Code
Drawing Type

Drawing Type Code

Section Discipline*

Plot Plan

DWG

General Arrangement Drawings

GAD

Section & Elevation Drawings

DWG

Miscellaneous Drawings

MIS

* Refer section discipline above

1a.0
Rev.

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
70

Department Naming

Department Name = Discipline Code + Area Code + Platform Deck Code*


Example:Discipline Code

Area Code

Platform Deck Code*

Department Name

PIPE

XXX

MDK (Main Deck)

/PIPEXXX-MDK

Registry Naming

Registry Name = Discipline Code + Area Code + Platform Deck Code* + Drawing Type Code
Example:Discipline
Code

Area
Code

Platform Deck
Code*

Drawing
Type Code

Registry Name

PIPE

XXX

MDK (Main
Deck)

GAD

/PIPEXXX-MDKGAD

* Platform Deck Code applicable to offshore only. For onshore use Elevations/ platform levels
where required.

Sheet Naming

Example:-

5.11

Project
Code

Area
Code

Section /
Discipline Type

Drawing
Number

ADXXX

XXX

20010

Draft Text and Colours

Text font, sizes & colour


The text font (with width factor 0.85), size and colour specified in the table below shall be
used for all engineering drawings and shall be in uppercase only. Exception to this shall be
ADMA Border template where provided fonts and colours shall be retained. Prior approval
shall be obtained for any deviation.

1a.0
Rev.

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
71

Drawing Size
Drawing Item
Text Height
Text Font
Text Colour
Text Height
Text Font
Headings
Text Colour
Dimension Line
Projection Line
Leader Line
LABEL frame
Note line
General
Text

A0

A1

A2

A3

A4

3 mm
Romans
White
5 mm
Romand
White
Red
Red
Red
Red
White

3 / 2.5 mm
Romans
White
5 mm
Romand
White
Red
Red
Red
Red
White

2.5 mm
Romans
White
4 mm
Romand
White
Red
Red
Red
Red
White

2 mm
Romans
White
3.5 mm
Romand
White
Red
Red
Red
Red
White

2 mm
Romans
White
3.5 mm
Romand
White
Red
Red
Red
Red
White

Drawing items colour coding and line thickness


Drawing item

Drawing Type

Piping Drawing

Equipment Drawing
Structural Drawing
Cable Tray Layout

5.12

Pipes
Refer colour
table
Thick lines

Structure

Grey

Grey

Thin line
Grey
Thin line

Thin line
Magenta
Thick line

Equipment
Refer colour
table
Thin line
Refer colour
table
Thick line
Grey
Thin line

Grey

Grey

Grey

Grey
Thin line

Cable tray

Other discipline

Grey

Grey

Thin line

Thin line

Grey

Grey

Thin line
Grey
Thin line
Refer colour
table

Thin line
Grey
Thin line
Grey

Piping Isometric Production and Control


Only complete lines with acceptable clash and data consistency to be submitted for isometric
generation.
Isometric option file(s) shall be created per MDB (Platform/ Plant/ Area) and shall be
configured to reflect ADMA-OPCO standards.
All process information/ parameters, test, heat treatment & painting requirement,
insulation/tracing type & thickness, support location/ type with tag, reference to piping GA &
P&ID, stress analysis requirement/ reference and detailing where required shall be provided
in isometric along with BOM.
Isometric drawing number shall reflect tag given in the design hierarchy which is the line tag
as specified in `CP-00 Part-2 process and utility line tagging format.

1a.0
Rev.

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
72

As-Built Isometrics in DXF and PDF format to be delivered to ADMA-OPCO


Please Note: Annotation/ editing of Isometrics outside of PDMS is not permitted unless
approved in advance by ADMA-OPCO.
5.13

Reports
All reports and PDMS report templates generated for and used on the project shall be
submitted to ADMA-OPCO. Reports shall be in MS Excel format.

5.14

Data Consistency Checking (Reports)


A final report showing all Pipes to be free of inconsistent data shall be delivered upon project
completion.
A final report showing all Structural items logically connected shall be delivered upon
project completion.

5.15

Clash Checking (Reports)


A final report showing clash free design and approved clashes shall be delivered upon project
completion.

5.16

Database Integrity (Dice Checking Report)


A final report showing all databases clean of errors shall be delivered upon completion of the
project.

5.17

Miscellaneous
All PDMS database sessions shall be merged prior to submission.

5.18

Project Data
ADMA-OPCO may at any time request complete PDMS Project Data and/ or access to
PDMS Project Data during Project execution.

5.19

Project Review
For periodic/ milestone and as-built review of the 3D PDMS model, latest colour review
model with status file of the 3D PDMS model shall be provided.
Review model (RVM & RVS) shall be made available to ADMA prior to periodic/ milestone
reviews.
Colours specified in the table shall be used for review model.

1a.0
Rev.

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
73

5.20

Aveva P&ID
The As-built AVEVA P&ID drawings along with all related database and project files shall
be submitted to ADMA-OPCO upon project completion
P&ID representation shall be in accordance with ADMA-OPCO standards.
Symbols created for the project shall have a suitable naming convention and shall be
submitted to ADMA for approval.
Information detailing layer, line type, text font/ height, colour etc... for P&ID and PFD shall
be submitted to ADMA for approval.

5.21

Milestone Requirements
At project milestones the following shall be delivered to ADMA-OPCO;
a. P&IDs with .MON files
b. P&ID Reports generated reports

5.22

Project Completion
Upon project completion the following shall be delivered to ADMA-OPCO;
a.
b.
c.
d.
e.
f.
g.

6.

Project Set up & configuration


Project Symbols
Drawing Border Templates
P&IDs with .MON files
P&ID Reports MS Access database
P&ID Reports generated reports
Documented list of settings made to configure the VPE P&ID project.

END OF PROJECT DELIVERABLES:


At the end of the project, ADMA-OPCOs, Engineering Services Team shall receive the
following deliverables from the Contractor/Consultant through ADMA-OPCOs Project
Team Leader:-

6.1

One complete set of following Documents and Dossiers:


a. Main index of project completion dossiers/drawings (Deliverable List)
b. Engineering dossier consisting of all Specification, Calculation, Analysis, Data
sheets in its Native format
c. Certification Dossier

1a.0
Rev.

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
74

6.2

As-Built drawing folder in native files as applicable

6.3

Drawing List

6.4

Process:
a. PFDs
b. P & IDs

6.5

Mechanical
a. Plot Plans
b. Piping General Arrangement
c. Vendor/ package GAs (separate drawing for each package)
d. Sections & Details
e. Piping Isometric with BOM
f. Equipment Drawings (separate drawing for each equipment)
g. Line List
h. Valve List
i. Equipment List
j. MTO
k. Equipment and Valve Data Sheet (separate data sheet for each equipment and actuated/
safety valve).

6.6

Pipelines Drawing:
a. Profile & Alignment Sheets
b. Riser Details

6.7

Civil/Structural Drawing:
a. Site Layout, Plot Plan
b. General Arrangement
c. Architectural Drawings
d. Reinforced Concrete Detail

1a.0
Rev.

04-2012 Issued For Implementation.

Date

Description / Text Affected


Codes Of Practices For Plant Design - Part-1: Documentation & Archiving

ADMA-OPCO
SF / General / 002 Rev.0 sheet 1 of 1

CP-00 Part-1

PAGE
75