Sie sind auf Seite 1von 1

Final Detail Report - Lindi

Appendix 5-1

7 Towns Urban Upgrading Project


Ng'apa Well fields - Calculation on boreholes, collector pipes and required pumps for ground water
Ng'apa
Static levels
BH DWL
Well field
WTP

m
20
56.05
44.7

Assumed Borehole Draw Down Water Level


masl
masl

Range 15 - 35m

Eight new boreholes from Ng'apa well field to Water Treatment Plant
Design for transmissions and pumps for boreholes at Ng'apa well field
New BH

Ground Pipe Node - Node /


Level borehole - node
(m)

Flow (l/s)

Diameter mm
assuming 1
m/s velocity

Actual
selected
diameter DN
(mm)

Pipe Length
(m)

Hydraulic
Friction Head
Gradient m/m
(m)

Required
Head to
balancing
tank (m)

Required
pump power
(kW)

Remarks

LDBH 8

56.05

LDBH8 - Node AA

22.22

168

150

1318

0.0120

15.816

56.756

17.67

Submersible pump

LDBH 3

56.05

LDBH3 - Node AA

22.22

168

150

403

0.0120

4.836

45.776

14.25

Submersible pump

Node AA - Node BB

44.44

238

250

924

0.0035

3.234

LDBH1 - Node BB

22.22

168

150

231

0.0120

2.772

Node BB - Node CC

66.66

291

250

1100

0.0075

8.250

LDBH2 - Node CC

22.22

168

150

550

0.0120

6.600

Node CC - Node DD

88.88

336

300

880

0.0053

4.664

LDBH4 - Node DD

22.22

168

150

50

0.0120

0.600

Node DD - Node EE

111.1

376

350

500

0.0043

2.150

LDBH7 - Node EE

22.22

168

150

1220

0.0120

14.640

Node EE - Node FF

133.3

412

350

120

0.0061

0.732

LDBH6 - Node FF

22.22

168

150

420

0.0120

5.040

Node FF - Node GG

155.5

445

400

650

0.0042

2.730

56.05

LDBH5 - Node GG

22.22

168

150

300

0.0120

3.600

44.7

Node GG - WTP

177.7

475

400

1950

0.0054

10.530

Pipeline
LDBH 1

56.05

Pipeline
LDBH 2

56.05

Pipeline
LDBH 4

LD BH7

56.05

56.05

Pipeline
LDBH6

56.05

Pipeline
LDBH 5

Combined collector main


40.478

12.60

Submersible pump
Combined collector main

36.056

11.23

Submersible pump
Combined collector main

24.792

7.72

Submersible pump
Combined transmission line

37.282

11.61

Submersible pump
Combined collector main

26.950

8.39

Submersible pump
Combined collector main

22.780

7.09

Submersible pump
Combined collector main to WTP

Design Assumptions:
C Value for Hazen Williams formula is 130 for HDPE & PVC; and 120 for Steel and Ductile Iron pipes
For pressure transmission main material selected is HDPE or uPVC for pipe diameter less or equal to DN 300 and Steel or DI for bigger sizes
Assumed Pump efficiency is 70%

Poyry Environment GmbH - Donconsult Ltd

Page 5-1-1