IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 60, NO. 12, DECEMBER 2013
I. I NTRODUCTION
HE INCREASING use of nonlinear loads such as adjustable speed drives, electric arc welders, and switching
power supplies causes large amounts of harmonic currents
inject into distribution systems. These harmonic currents are
responsible for voltage distortion, increasing power losses and
heat on networks and transformers, and causing operational
failure of electronic equipment. Due to these problems, harmonic restriction standards such as IEEE-519 or IEC 61000-3-2
have been published to demand those harmonic currents injected into utility networks to be below the specified values
[1], [2]. In order to improve the power quality of distribution
networks as well as to meet these restriction standards, two
main solutions have been introduced: LC passive filters and
active power filters (APFs) [3][5].
LC passive filters are traditionally utilized to compensate the
harmonic currents since they are simple and low-cost solution.
However, they are often large and heavy. Furthermore, the
compensation capability of a passive filter is typically fixed
Manuscript received May 1, 2012; revised August 20, 2012; accepted
October 16, 2012. Date of publication December 10, 2012; date of current
version June 21, 2013. This work was supported by the 2013 Research Fund
of the University of Ulsan.
The authors are with the School of Electrical Engineering, University of Ulsan, Ulsan 680-749, Korea (e-mail: hhlee@mail.ulsan.ac.kr;
trinhquocnam2010@gmail.com).
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org.
Digital Object Identifier 10.1109/TIE.2012.2229677
Fig. 1.
TRINH AND LEE: CURRENT CONTROL STRATEGY FOR THREE-PHASE SHUNT ACTIVE POWER FILTERS
increasing of the switching frequency and consequently introduces higher switching loss on the APF.
In recent years, several high-performance current controllers
have been developed for APFs to achieve good control
performance [15][18]. In these control schemes, the current
controllers are employed in the fundamental reference frame,
consisting of a proportional controller plus multiple sinusoidal
signal integrators [15], a PI controller plus a series of resonant
controllers [16], [17], or vector PI (VPI) controllers [18]. In
fact, the VPI controller introduced in [18] is an alternative
version of resonant controller that has superior and robust characteristics when compensating high-order harmonic currents.
These control schemes are capable of providing good control
performances thanks to high-performance current controllers.
However, as illustrated in Fig. 1, the performance of the APF
relies on not only the current controller but also the harmonic
currents detector. The harmonic detector aims to extract the
harmonic components presented in the load currents whose output becomes the reference filter current for the APF. Thus, the
performance of this process critically impacts on the accuracy
of the APF. The harmonic detector is typically employed by using filters such as high-pass, low-pass, adaptive filters [8][13],
or through complex mathematical functions [14]. However, by
using these filters, it is difficult to achieve both fast response and
good steady-state harmonic tracking performance because of a
compromise: if the filters are designed to achieve good steadystate performance, their response becomes slow and vice-versa.
As a result, the use of a harmonic detector in the control scheme
may have an adverse effect on both the accuracy and response
of an APF.
In order to avoid the use of harmonic detectors, indirect current control schemes have been introduced in [19][24] where
the supply currents (iS,abc ) are directly measured and regulated
to be sinusoidal. In [19], [20], [22], hysteresis controller was
used in the current control loop to force the supply current to
be sinusoidal. However, as mentioned earlier, this method has a
drawback, i.e., the variation of the switching frequency, so that
the supply current regularly contains many switching noises.
Meanwhile, the PI controller and the proportional controller are
utilized in [21] and [23], respectively. They obviously have a
limitation on the control bandwidth and are unable to accurately
regulate high-frequency signals such as harmonic currents.
Consequently, it is hard to achieve a good performance of
the supply currents. In [24], authors demonstrated that indirect
control method is able to provide better performances compared
to direct one since it can prevent inaccurate tracking performances of the harmonic detector. Nevertheless, in this control
scheme, two sets of current sensors are required. In addition, the
reference supply current is given based on the supply voltage
which is assumed to be a pure sinusoidal waveform. Thus, the
performance of the supply current is degraded when the supply
voltage is distorted.
Adopting the advantage of indirect current control schemes,
i.e., the absence of a harmonic detector, this paper proposes an
advanced control strategy to enhance the APF performance. In
the proposed control scheme, the supply currents are directly
measured and regulated to be sinusoidal by an effective harmonic compensator, which is developed based on a PI plus
5401
5402
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 60, NO. 12, DECEMBER 2013
Fig. 2. Structure of the proposed control scheme for three-phase shunt APF.
GPR =
Kph +
h=1,5,7,11,13...
2Krh s
s2 + (hs )2
(1)
where Kph and Krh are the proportional and resonant gains of
the resonant controller, respectively, h is the order of harmonic
currents, and s is the fundamental frequency of the supply
voltage.
However, as shown in (1), each resonant controller has a
responsibility to regulate only one harmonic component. Thus,
the controller complexity and computational burden are significantly increased if large numbers of harmonic currents are
required to be compensated.
In fact, each pair of h = 6n 1 harmonic currents behave as
h = 6n harmonic currents in the fundamental reference frame.
Thus, it is possible to perform a resonant controller tuned at h =
6n multiples of s in this reference frame to regulate a pair of
h = 6n 1 harmonic currents. The transfer function of the PI
controller plus resonant controllers in the s-domain is given as
GPI-R = Kp1 +
Ki1
+
s
h=6,12,18...
Kph +
s2
2Krh s
(2)
+ (hs )2
where Kp1 and Ki1 are the proportional and integrator gains of
the PI controller, respectively, h = 6n is the order of harmonics
in the fundamental reference frame with n = 1, 2, 3 . . ..
In (2), the aim of the PI controller is to regulate the fundamental current whereas resonant controllers are used to control
TRINH AND LEE: CURRENT CONTROL STRATEGY FOR THREE-PHASE SHUNT ACTIVE POWER FILTERS
5403
Ki1
+
s
+2Krh
Kph
h=6,12,18...
s cos(hs N Ts ) hs sin(hs N Ts )
s2 + (hs )2
(3)
h=6,12,18...
Kph s2 + Krh s
.
s2 + (hs )2
(4)
Ki1
Kph s2 + Krh s
+
2 2
.
s
s + (hs )2
(5)
h=6...30
1
.
sLF + RF
(6)
5404
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 60, NO. 12, DECEMBER 2013
Fig. 7. Closed-loop Bode diagrams of the VPI controllers with Kph = 0.5,
Kph = 2, and Kph = 5.
controller. Thus, the use of VPI controllers significantly improves the stability margin and accuracy of the proposed current
controller.
The complete proposed current control scheme using the
PI-VPI controller is shown in Fig. 6. Since the proposed current
controller is designed in the fundamental reference frame, the
measured supply current iS, first must be transformed from
the stationary to the fundamental reference frame iS,dq . The
proposed current controller is then executed to regulate this
current follow its reference iS,dq . The outputs of the current
and the feedforward supply voltage term vS,dq
controllers vF,dq
are added together and then transformed in the stationary
reference frame through an inverse rotational transformation to
GC =
=
GPI-VPI GLF
1 + GPI-VPI GLF
h=6...30
(Kp1 + 2Kph )s3 + (Ki1 + 2Krh )s2 + Kp1 (hs )2 s + Ki1 (hs )2
LF s4 + (Kp1 + 2Kph + RF )s3 + (Ki1 + 2Krh + LF (hs )2 ) s2 + (RF + Kp1 )(hs )2 s + +Ki1 (hs )2
GC =
h=6...30
LF
s3
(7)
(8)
TRINH AND LEE: CURRENT CONTROL STRATEGY FOR THREE-PHASE SHUNT ACTIVE POWER FILTERS
5405
(hs Ts )4
(hs Ts )6
(hs Ts )2
+
+. . . .
2
24
720
(10)
(11)
Vdc )
(12)
iSd = Kpdc +
(Vdc
s
where Kpdc and Kidc are the proportional and integrator gains
5406
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 60, NO. 12, DECEMBER 2013
Fig. 10.
v +
v
vF a =
2 F
2 F
vF b = 2vF
(13)
where vF a and vF b are the control signals for leg a and b of the
four-switch APF, respectively.
D. Supply Voltage PLL
TRINH AND LEE: CURRENT CONTROL STRATEGY FOR THREE-PHASE SHUNT ACTIVE POWER FILTERS
5407
V. E XPERIMENTAL R ESULTS
An overview of the experimental system built in the laboratory is shown in Fig. 11. The system consists of a 1.5-kVA shunt
APF and a 3-kVA nonlinear load with the parameters listed in
Table I. The control algorithm was implemented using a 32-bit
fixed point DSP (TMS320F2812 by Texas Instruments), with a
150-MHz clock frequency. The control sampling and switching
frequencies are set at 10 kHz. The current controller is designed
with one PI controller and five VPI controllers, capable of compensating all of the harmonic currents up to the 31st harmonic
(1860 Hz). The gains of the controllers were individually tuned,
as listed in Table II. The supply voltage is generated by a
6-kVA Programmable AC Power Source (Chroma 61704) that
is able to produce either ideal sinusoidal or distorted supply
voltage sources to investigate the performance of the proposed
control strategy. Two types of nonlinear loads were used in the
experimental tests, i.e., the RL and RLC loads connected to the
power supply through a diode rectifier as shown in Fig. 9.
First, before evaluating the performance of the proposed
APF, we have investigated the existing APF with the PI current
controller by using the current control scheme in [21] because it
uses the indirect current control method and its control scheme
is similar to the proposed control strategy except the PI current
5408
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 60, NO. 12, DECEMBER 2013
Fig. 15.
load.
Fig. 16. Dynamic responses of proposed control scheme under RLC load
variations: (a) load applied (b) load changed.
condition is rare in practical networks. The non-sinusoidal supply voltage condition in practical networks may adversely affect
the control performance of the APF. To verify the effectiveness
of the proposed control algorithm under such conditions, experiments were carried out where the supply voltage was injected
with fifth and seventh harmonic components of 10% and 5%
magnitudes of the fundamental component, respectively. The
results are illustrated in Fig. 17. As shown in Fig. 17, the
harmonic compensation performance of the APF is not deteriorated by the distorted supply condition where the supply
TRINH AND LEE: CURRENT CONTROL STRATEGY FOR THREE-PHASE SHUNT ACTIVE POWER FILTERS
current was also close to sinusoidal and similar with the results
shown in Figs. 13 and 15 where an ideal sinusoidal supply
voltage is given. There are only small increases in THD factors,
approximately 1.84% and 1.93% for the cases of nonlinear RL
and RLC loads, respectively.
The effectiveness of the proposed control strategy with the
six-switch APF was validated through the results shown in
Figs. 1317. In addition, experimental tests with the four-switch
APF are also carried out to completely verify the feasibility
of the proposed control scheme with the four-switch APF
where the steady-state performance under the nonlinear RL
load and nonlinear RLC load are shown in Fig. 18(a) and (b),
respectively. In Fig. 18(a), the capacitor voltages, VC1 and VC2 ,
were charged with the same value, i.e., 210 V, which is half
of dc-link voltage, thus guaranteeing the balanced and robust
operation of the proposed topology. There were very small
variations in capacitor voltages, but it did not have a critical
impact on the supply current performance, where the supply
current was close to sinusoidal with a low THD factor of approximately 1.77%. Therefore, the experimental results verified
that the four-switch APF is able to achieve good performance
similar to that with the six-switch APF shown in Fig. 13 even
though a fewer power switching devices is used. Similarly, the
effectiveness of the four-switch APF was also confirmed under
the nonlinear RLC load as shown in Fig. 18(b).
In addition, experimental tests for the four-switch APF under
a distorted supply voltage condition are also carried out, and the
obtained THD results are given in Table III. Table III shows a
summary of the THD factors of the supply current achieved by
5409
Fig. 18. Steady-state performances of the four-switch APF with (a) RL load
and (b) RLC load.
5410
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 60, NO. 12, DECEMBER 2013
TABLE III
C OMPARISON OF THE THD FACTORS
[19]
[20]
[21]
[22]
[23]
[24]
[25]
[26]
[27]
[28]
filters, IEEE Trans. Power Electron., vol. 22, no. 5, pp. 18261835,
Sep. 2007.
B. N. Singh, A. Chandra, and K. Al-Haddad, Performance comparison
of two current control techniques applied to an active filter, in Proc. 8th
ICHQP, Athens, Greece, Oct. 1416, 1998, vol. 1, pp. 133138.
J. W. Dixon, J. M. Contardo, and L. A. Moran, A fuzzy-controlled
active front-end rectifier with current harmonic filtering characteristics
and minimum sensing variables, IEEE Trans. Power Electron., vol. 14,
no. 4, pp. 724729, Jul. 1999.
M. Singh, V. Khadkikar, and A. Chandra, Grid synchronization with
harmonics and reactive power compensation capability of a permanent
magnet synchronous generator-based variable speed wind energy conversion system, IET Power Electron., vol. 4, no. 1, pp. 122130, Jan. 2011.
A. Szromba, Energy controlled shunt active power filters, Int. J. Comput. Math. Elect. Electron. Eng., vol. 26, no. 4, pp. 11421160, Jan. 2007.
E. Teresa and J. A. Pomilio, Shunt active power filter synthesizing resistive load, IEEE Trans. Power Electron., vol. 17, no. 2, pp. 273278,
Mar. 2002.
B. N. Singh, B. Singh, A. Chandra, P. Rastgoufard, and K. Al-Haddad,
An improved control algorithm for active filters, IEEE Trans. Power
Del., vol. 22, no. 2, pp. 10091020, Apr. 2007.
A. G. Yepes, F. D. Freijedo, J. Doval-Gandoy, O. Lopez, J. Malvar, and
P. Fernandez-Comesana, Effects of discretization methods on the performance of resonant controllers, IEEE Trans. Power Electron., vol. 25,
no. 7, pp. 16921712, Jul. 2010.
A. G. Yepes, F. D. Freijedo, O. Lopez, J. Malvar, and J. Doval-Gandoy,
High-performance digital resonant controllers implemented with two
integrators, IEEE Trans. Power Electron., vol. 26, no. 2, pp. 16921712,
Feb. 2011.
F. Blaabjerg, D. Neacsu, and J. K. Pedersen, Adaptive SVM to compensate DC-Link voltage ripple for four-switch three-phase, IEEE Trans.
Power Electron., vol. 14, no. 4, pp. 743752, Jul. 1999.
M. B. de R. Corra, C. B. Jacobina, E. R. C. da Silva, and A. M. N.
Lima, A general PWM strategy for four-switch three phase inverter,
IEEE Trans. Power Electron., vol. 21, no. 6, pp. 16181627, Nov. 2006.