Sie sind auf Seite 1von 7

Condfill.

xls

Descr: 3 Cond 15KV Shielded 220mil TC

Trade
size
1 1/2

Fill= 40%
Number of Wires
1
1

Wire Size
Wire 1 #2 AWG

Outside Diam (single) X-Sect Area(single)


2.06
3.332923

Total X sec
3.332923

Wire 2 None

Wire 3 None

Wire 4 None

Wire 5 None

Wire 6 None

Wire 7 None

Wire 8 None

Wire 9 None

Wire 10 None

2
3
4
5
6
7
8
9
10
11
12

3/4
1
1 1/4
1 1/2
2
2 1/2
3
3 1/2
4
5
6

Conduit ID
x-sect (sq
in)
0.3

40% of
conduit
area
0.12

Too Small

0.53
0.86
1.5
2.04
3.36
4.79
7.39
9.89
12.73
20
28.89

0.212
0.344
0.6
0.816
1.344
1.916
2.956
3.956
5.092
8
11.556

Too Small
Too Small
Too Small
Too Small
Too Small
Too Small
Too Small
OK
OK
OK
OK

Tray:
Single Layer uncovered traywith single OD in between:

Triangular with with 2.15 OD space

Total Wire Area= 3.33292 sq in


Recommended Conduit Size=

3 1/2 inch

Based on Okonite Okoguard/Okolon Type MV-105 15KV shielded cable


Compact stranded, 220 mil insulation

Burns & McDonnell Confidential

02/02/2016

Page 1

Condfill.xls

Descr:

Trade
size
1 1/2

Fill= 40%
Number of Wires
1
1

Wire 1 None

Wire 2 None

Wire 3 None

Wire 4 None

Wire 5 None

Wire 6 None

Wire 7 None

Wire 8 None

Wire 9 None

Wire 10 None

Wire Size

Outside Diam (single) X-Sect Area(single)


0
0

Total X sec
0

2
3
4
5
6
7
8
9
10
11
12

3/4
1
1 1/4
1 1/2
2
2 1/2
3
3 1/2
4
5
6

Conduit ID
x-sect (sq
in)
0.3

40% of
conduit
area
0.12

OK

0.53
0.86
1.5
2.04
3.36
4.79
7.39
9.89
12.73
20
28.89

0.212
0.344
0.6
0.816
1.344
1.916
2.956
3.956
5.092
8
11.556

OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK

Tray:
Single Layer uncovered traywith single OD in between:

Triangular with with 2.15 OD space

Total Wire Area=


Recommended Conduit Size=

0 sq in

#N/A

Based on Okonite Okoguard/Okolon Type MV-105 15KV shielded cable


Compact stranded, 220 mil insulation

Burns & McDonnell Confidential

02/02/2016

Page 2

Condfill.xls

Descr:

Trade
size
1 1/2

Fill=
Number of Wires
1
1

Wire Size
Wire 1 #2 AWG

30%
Outside Diam (single) X-Sect Area(single)
1.53
1.838543

Total X sec
1.838543

Wire 2 None

Wire 3 None

Wire 4 None

Wire 5 None

Wire 6 None

Wire 7 None

Wire 8 None

Wire 9 None

Wire 10 None

2
3
4
5
6
7
8
9
10
11
12

3/4
1
1 1/4
1 1/2
2
2 1/2
3
3 1/2
4
5
6

Conduit ID
x-sect (sq
in)
0.3

30% of
conduit
area
0.09

Too Small

0.53
0.86
1.5
2.04
3.36
4.79
7.39
9.89
12.73
20
28.89

0.159
0.258
0.45
0.612
1.008
1.437
2.217
2.967
3.819
6
8.667

Too Small
Too Small
Too Small
Too Small
Too Small
Too Small
OK
OK
OK
OK
OK

Total Wire Area= 1.83854 sq in


Recommended Conduit Size=

Burns & McDonnell Confidential

02/02/2016

3 inch

Page 3

Condfill.xls

Descr:

Trade
size
1 1/2

Fill=
Number of Wires
6
6

Wire Size
Wire 1 500 KCM

30%
Outside Diam (single) X-Sect Area(single)
1.24
1.207631

Total X sec
7.245786

Wire 2 None

Wire 3 None

Wire 4 None

Wire 5 None

Wire 6 None

Wire 7 None

Wire 8 None

Wire 9 None

Wire 10 None

2
3
4
5
6
7
8
9
10
11
12

3/4
1
1 1/4
1 1/2
2
2 1/2
3
3 1/2
4
5
6

Conduit ID
x-sect (sq
in)
0.3

30% of
conduit
area
0.09

Too Small

0.53
0.86
1.5
2.04
3.36
4.79
7.39
9.89
12.73
20
28.89

0.159
0.258
0.45
0.612
1.008
1.437
2.217
2.967
3.819
6
8.667

Too Small
Too Small
Too Small
Too Small
Too Small
Too Small
Too Small
Too Small
Too Small
Too Small
OK

Total Wire Area= 7.24579 sq in


Recommended Conduit Size=

6 inch

Based on Okonite FMR/Okolon type TC


(EPR/Hypalon Tray cable, 45 mil jacket)

Burns & McDonnell Confidential

02/02/2016

Page 4

Condfill.xls

Description:

Trade
size
1 1/2

Fill=

40%

Outside Diameter
Wire 1 350 KCM--3Cond wGnd
1.91

Wire 2 None

Wire 3 None

Wire 4 None

Wire 5 None

Wire 6 None

Wire 7 None

Wire 8 None

Wire 9 None

Wire 10 None

Burns & McDonnell Confidential

X-Sect Area
2.865211

2
3
4
5
6
7
8
9
10
11
12

3/4
1
1 1/4
1 1/2
2
2 1/2
3
3 1/2
4
5
6

Conduit ID
x-sect (sq
in)
0.3

40% of
conduit
area
0.12

Too Small

0.53
0.86
1.5
2.04
3.36
4.79
7.39
9.89
12.73
20
28.89

0.212
0.344
0.6
0.816
1.344
1.916
2.956
3.956
5.092
8
11.556

Too Small
Too Small
Too Small
Too Small
Too Small
Too Small
OK
OK
OK
OK
OK

Total Wire Area= 2.86521

02/02/2016

Page 5

Condfill.xls

Descr:

Trade
size
1 1/2

Fill=
Number of Wires
4
4

Wire Size
Wire 1 #6

40%
Outside Diam (single) X-Sect Area(single)
0.397
0.123786

Total X sec
0.495143

Wire 2 None

Wire 3 None

Wire 4 None

Wire 5 None

Wire 6 None

Wire 7 None

Wire 8 None

Wire 9 None

Wire 10 None

2
3
4
5
6
7
8
9
10
11
12

3/4
1
1 1/4
1 1/2
2
2 1/2
3
3 1/2
4
5
6

Conduit ID
x-sect (sq
in)
0.3

40% of
conduit
area
0.12

Too Small

0.53
0.86
1.5
2.04
3.36
4.79
7.39
9.89
12.73
20.01
28.89

0.212
0.344
0.6
0.816
1.344
1.916
2.956
3.956
5.09
8.00
11.56

Too Small
Too Small
OK
OK
OK
OK
OK
OK
OK
OK
OK

Total Wire Area= 0.49514 sq in


Recommended Conduit Size=

1 1/4 inch

Based on Okonite FMR/Okolon type TC


(EPR/Hypalon Tray cable, 45 mil jacket)

Burns & McDonnell Confidential

02/02/2016

Page 6

Condfill.xls

DESCR:

Trade
size
1 1/2

Fill=

40%

Outside Diameter
0.34

X-Sect Area x number


0.726336

Wire 1 1pair #16 w shield

Wire 2 None

Wire 3 None

Wire 4 None

Wire 5 None

2
3
4
5
6
7
8
9
10
11
12

3/4
1
1 1/4
1 1/2
2
2 1/2
3
3 1/2
4
5
6

Conduit ID
x-sect (sq
in)
0.3

40% of
conduit
area
0.12

Too Small

0.53
0.86
1.5
2.04
3.36
4.79
7.39
9.89
12.73
20
28.89

0.212
0.344
0.6
0.816
1.344
1.916
2.956
3.956
5.092
8
11.556

Too Small
Too Small
Too Small
OK
OK
OK
OK
OK
OK
OK
OK

Total Wire Area= 0.72634 sq in


Recommended Conduit Size=

1 1/2 inch

Based on Rockbestos EPR/Hypalon Tray Cable

Burns & McDonnell Confidential

02/02/2016

Page 7

Das könnte Ihnen auch gefallen