Sie sind auf Seite 1von 1

Power Cable (direct burial)

Requirements

Supplier

300MM (600
MCM) 25kV
CU/XLPE/CWS/AT/
MDPE 133% IL
POWER CABLE

300MM (600
MCM) 25kV
CU/XLPE/CWS/AT/
MDPE 133% IL
POWER CABLE

provide...

please see attached...

25KV

25KV

Nominal Sectional Area

300mm2

300mm2

AC Test Voltage

provide...

64kV

Brand

Brief Description

Catalog
Voltage Rating

Continous Current Direct Burial


Continous Current Air

530+ amps
530+ amps

559 amps

725 amps

Conductor

Copper

Copper

Insulation

XLPE

XLPE

Insulation Level

133%

133%

Nominal Diameter of Copper Conductor

provide...

52 Wires by 1.25mm

Shield

provide...

Aluminum Tape Armour

Insulation Fault Current Rating

9 kA/sec

9 kA/sec

Normal Condition Temperature

90degC

90C

Short-Circuit Condition Temperature

250degC

250C

Max DC resistance @ 20degC

ohm/km

0.0581

Weight of Cable

kg/km

5,864.86

Overall Diameter

mm

57.61

Thickness of Insulation

mm

8.76

Thickness of Sheath

mm

2.52

Bending Radius

mm

please attached testing results, certifications, etc...


Note:
For Direct Burial:
1. Ground Temperature : 15C
2. For ground Thermal Resistivity : 1.2 Km/W
3. Adjacent Circuits : atleast 1.8m apart
4. Depth of Laying : 0.80mts

864.0 (15 times OD)

Das könnte Ihnen auch gefallen