THREE-PHASE-ENCLOSURE

SF6 - GAS -INSULATED SUBSTATIONS (GIS)


72.5 170kV

IGP-18089-B ( 1/8 )

With the application of TMT&D GIS, you gain,


World class high performance equipment
The GIS is fully assembled and tested in the factory.
Minimum shipping split is provided thanks to the
compactness of the equipment.

Low construction cost


Minimum land space
Minimum civil work
Minimum construction period

Easy maintenance
Virtually maintenance free - no routine
maintenance needed

Adaptability to fully digitalized system


Electronic type current/voltage transformers
can be equipped

IGP-18089-B ( 2/8 )

TYPE GMKDGIS
Ratings ( Based on IEC 517 )
Rated voltage

(kV)

Rated current

(A)

1000/1250/1600/2000/2500/3150

(kA)

20/25/31.5/40/50

Rated short-time withstand current


Rated insulation
level

100

123

145

140

185

230

275

325

Rated lightning impulse withstand voltage (kV, peak)

325

450

550

650

750

(MPa . at 20)

0.5

(kA)

Rated lnterrupting current

20/25/31.5/40/50

(Cycle)

Rated lnterrupting time

0.6

3 to 5

Operating mechanism

Spring

Disconnector

Operating mechanism

Motor

Earthing switch

Operating mechanism

Manual/Spring

Surge arrester

Rated voltage (1)

(kV)

Rated discharge current

(kA)

Voltage (potential) Primary/secondary/tertiary voltage


transformer
Secondary/tertiary output (per phase)

(kV/V/V)

60/72

84/102

96/120

120/144

144/168

10
66 110 110
/
/
3
3
3

88 110 110 110 110 110 132 110 110 154 110 110
/
/
/
/
/
/
/
/
3
3
3
3
3
3
3
3
3
3
3
3
100 /100

(VA/VA)

1.0/3P

Accuracy class
Current
transformer

170

Rated short-duration power-frequency withstand voltage (kV)

Rated gas pressure

Circuit breaker

72.5

Bushing (Ring core) type

Type
Rated current

(A)

Rated burden

(VA)

Primary currentaccording to specifications


Secondary current1A, 5A
15, 20, 30

Ratings ( Based on IEEE std C37, 122)


Rated voltage

(kV)

Rated current

(A)

2000/2500/3150

(kA)

20/25/31.5/40/50

Rated short-time withstand current


Rated insulation
level

Low frequency withstand voltage


Rated BIL
Rated gas pressure
Rated lnterrupting current

Circuit breaker

Rated lnterrupting time

72.5

121/123

(kV)

160

215

310

365

350

550

650

750

(MPa . at 20)

0.5

(kA)

0.6
20/25/31.5/40/50

(Cycle)

3 to 5

Operating mechanism

Spring
Motor

Surge arrester

Manual/Spring

Operating mechanism
Rated voltage (1)

(kV)

Rated discharge current

(kA)

Primary voltage (kV) -ratio


Voltage (potential)
Burden (per phase)
transformer
Accuracy class

(kV/V/V)
(VA)

96/120

40.25350/600 : 1

69600/1000 : 1

120/144

144/168

80.5700/1200 : 1

92800/1400 : 1

10

Y(75VA)
0.6

Primary currentaccording to specifications


Secondary current1A, 5A

Rated current
Rated burden

60/72

Bushing (Ring core) type

Type
Current
transformer

169/170

(kV, crest)

Disconnect switch Operating mechanism


grounding switch

145

(VA)

15, 20, 30

Notes
1. The surge arrester rated voltage should be determined in accordance with the neutral grounding condition (effectively or non-effectively grounded).

IGP-18089-B ( 3/8 )

Single line diagram

Key
3
CB
DS
ES
(GS
FES
(FAGS
CT
VD
CSE
BUS

Live parts
Insulators
SF6 gas
Enclosures

:Circuit Breaker
:Disconnector
:Earthing Switch
:Grounding Switch)
:Fault making Earthing Switch
:Fast Acting Grounding Switch)
:Current Transformer
:Voltage Divider
:Cable Sealing End
:Busbar

Capacitive VD

Line ES(GS)
(FES) (FAGS)

Local control panel

CSE
BUS&DS

DSES (GS)

Rogowski CT

CB

BUS&DSES (GS)
Operating
mechanism
for DSES(GS)

IGP-18089-B ( 4/8 )

Spring operating mechanism


housing for CB

Single line diagram

Key
3
CB
DS
ES
(GS
FES
(FAGS
CT
VT
CSE
BUS

Live parts
Insulators
SF6 gas
Enclosures

:Circuit Breaker
:Disconnector
:Earthing Switch
:Grounding Switch)
:Fault making Earthing Switch
:Fast Acting Grounding Switch)
:Current Transformer
:Voltage Transformer
:Cable Sealing End
:Busbar

VT
Line ES(GS)
(FES) (FAGS)
CSE
Local control panel

BUS&DS

DSES (GS)
CT

CB

CT

BUS&DSES (GS)
Operating
mechanism
for DSES(GS)

Spring operating mechanism


housing for CB

IGP-18089-B ( 5/8 )

BUS
VT

L1

T1

BUS
SECTION

L2

T2

BUS
VT

BUS - B

BUS - A
G

APPROX.
560
(1.9)

1000 1000 1000 1000 1000 1000


(3.3)
APPROX.7000
(23)
G

APPROX.
410
(1.4)

BUS-B
BUS-A
FRONT VIEW
APPROX.
2000
(6.6)
ES
(GS) VT

VT

APPROX.
2350
(7.7)

CT
CB

APPROX.3000
(9.9)

CSE

LCP

DS/ES
(GS)

LCP

CT
CB

CSE

APPROX.4750
(15.6)

APPROX.4750
(15.6)

SECTION A-A

FES
(FAGS)

DS/ES
(GS)

APPROX.3900
(12.8)

FES
(FAGS)

DS/ES
(GS)

SECTION B-B

SECTION C-C
VT

APPROX.
2450(8)

LCP

CT

DS/ES
(GS)

LCP

CB

CB

APPROX.4800
(15.8)

SECTION D-D

IGP-18089-B ( 6/8 )

CSE

DS/ES
(GS)

CT

APPROX.4800
(15.8)

SECTION E-E

APPROX.3000
(9.9)

DS/ES
(GS)
CT

FES
(FAGS)

DS/ES
(GS)

LCP

CB

DS/ES
(GS)

CT

CSE
APPROX.3900
(9.9)

FES
(FAGS)

APPROX.
2000
(6.6)
ES
(GS)

VT

APPROX.4800
(15.8)

SECTION F-F

SECTION G-G

L1

T1

BUS
COUPLER

T2

BUS
VT

L2

T3

BUS - A
BUS - B
D

A
APPROX.
2500
(8.2)

2800
(9.2)

APPROX.7600
(25)

APPROX.
2500
(8.2)

APPROX.
560
(1.9)

APPROX.
500

800 1000 800 1000 800 800

(1.7)

(2.6) (3.3)
APPROX.6260
(20.6)
D

A
BUS - A

BUS - B

FRONT VIEW
APPROX.7600
(25)
VT
DS/ES
(GS)

LCP

CT
CT CB

FES
(FAGS)

DS/ES
(GS)

LCP

DS/ES
(GS)

CT
CB

CSE

APPROX.2900
(9.5)

FES
(FAGS)

APPROX.3900
(12.8)

DS/ES
(GS)

DS/ES
(GS)

APPROX.4740
(15.6)
DS

SECTION A-A

SECTION B-B

APPROX.3050
(10)
ES(GS)

LCP

ES
(GS)

SECTION C-C

VT

APPROX.
2450
(7.9)

APPROX.
2400
(7.9)

VT

DS/ES
(GS)

APPROX.4780
(15.7)
DS/ES
(GS)
CT

CT

CB

SECTION D-D

IGP-18089-B ( 7/8 )

TR No.1

FES
(FAGS)

VT

DS/ES
(GS)
CSE

LCP

L1

CB

CT

APPROX.3400
(11.2)

DS/ES
(GS)

APPROX.4000
(13.1)

SECTION B-B
3

L2
3

TR No.2

(3.3)

APPROX.5000
(16.4)

(4.9)

1000

TR NO.1

APPROX.6000
(19.7)
1500
1500 1000

APPROX.
560
(1.9)

SECTION C-C

APPROX.
410
(1.4)

APPROX.6000
(19.7)

APPROX.
2100
(6.9)
APPROX.8300
(27.2)

APPROX.8400
(27.6)

APPROX.4300
(14.1)

TR NO.2

APPROX.16700
(54.8)

TR

VT

DS/ES
(GS)

ES
(GS)

LCP

CB

TR

APPROX.6200
(20.4)

GIS

APPROX.6000
(19.7)

CT

APPROX.4000
(13.1)

SECTION A-A

Improper use of products can cause severe injury or death, and may result in damage to product and other property.
Please read instruction manual before installing or using product.

IGP-18089-B ( 8/8 )