Sie sind auf Seite 1von 1

RESULTS

~
Project / Job

CRDTCT100-50-4-Dyn11-MyTrafo-ST/1
MyTrafo

Designed

ST

Verified

ST

Approved

ST

General Project Data


Power [kVA]
Frequency [Hz]
Ucc % (Ur / Ux)
Pcc / Total losses [W]

100(100)

Ambient

50

40

Group

4.30(1.77/3.92)

Transformer weight [kg]

340.5

Air flow rate [m^3/h]

156.9

1774.8/2222.2@75DegC

No load current [%]

2.5

Inrush current [p.u.]

12.9

Dyn-11

DP [Pa] - DTair [K]

0.3/33.1

Sound Level / Power [dbA]


IEC 76 IEC 726

49/53

Reference Rules:
100 kVA - EXEMPLE
Dimensions
Dimensions [mm]

Length

Transformer Dimensions
Core Dimensions

Section [cm2]
Steps

Width

Height

645

247

565

510

147

540

114.0
1

Flux Density [T]


Core Material

Window Width [mm]


Core Weight [kg]
Core Diameter [mm]

135
188.4
N/A

Window Height [mm]


Core Losses [W]
Column Delta T [K]

First Sheet Wide [mm]

80

1 Sheet Wide [mm]

80

Yoke Delta T [K]


Core Composition
1 Sheet Step Deep [mm]

1.66
M6(M150-35S)
380
447.3
58.3
58.2
146.90

2 Sheet Wide [mm]

2 Sheet Step Deep [mm]

3 Sheet Wide [mm]

3 Sheet Step Deep [mm]

4 Sheet Wide [mm]

4 Sheet Step Deep [mm]

5 Sheet Step Deep [mm]]

6 Sheet Step Deep [mm]

5 Sheet Wide [mm]


6 Sheet Wide [mm]

7 Sheet Wide [mm]


8 Sheet Wide [mm]

7 Sheet Step Deep [mm]


8 Sheet Step Deep [mm]

9 Sheet Wide [mm]

9 Sheet Step Deep [mm]

10 Sheet Wide [mm]

10 Sheet Step Deep [mm]

Cut steps on one side only


Total Deep (both sides) [mm]

0
146.9