Installation Instructions
MODEL ID-60T-135 Thermal Detector
These instructions are written in accordance with
the installation guidelines of NFPA No. 72,
STANDARD FOR AUTOMATIC FIRE
DETECTORS.
CAUTION
Detection Device Storage
DO NOT install this detection device until all
construction is completed.
DO NOT store this detection device where it can
be contaminated by dirt, dust, or humidity.
DETECTOR PLACEMENT
Locate the ID-60T-35 on the ceiling, at least 4 inch-
es from the side walls. For an ideal, smooth ceiling
condition, place the detectors at a maximum center
‘spacing of 50 feet (2500 square feet), 25 feet from
side walls or room partitions.
Cerberus Pyrotronics
8 Fernwood Road
Florham Park, New Jersey 07932 P/N 315-090288-2+ + + + + + ToNext Base
Ss 4+ ~
Detector Base Remote Relay a
Model DB-3S Base Model DB-x3AS
euigures Zone Wires
Wiring Diagram fom Gerberus Relay" soa
Pyrotronics Contacts
Compatible ‘3A, 120 VAC 2
Controt Sptionat 3A, 30 VDC.
ipmen lomote
en ‘Alarm es)
Indicator
Models RLI-1/RLI-2 -
+ t 4+ >
= ES - = = To Next Base
Actual job conditions and sound engineering judgment DETECTOR MOUNTING
must determine detector spacing. Consider environ-
mental factors including ambient temperature fluctua-
tion, and the nature of the fire hazard. Room or area
configuration and ceiling type (sloped or flat, smooth or
beamed) also dictates placement.
Should questions arise regarding detector placement,
follow the drawings provided and/or approved by
Cerberus Pyrotronics or by its authorized distributors.
This is extremely important! The detector placements
shown on these drawings were chosen after a careful
evaluation of the area being protected. Cerberus Pyro-
tronics extensive experience in design of the system
assures the best detector placement by following these
drawings.
DETECTOR WIRING
Connect the detector as shown in Figure 1 and wire it
to the contro! panel by following the Wiring Diagram
on the control panel cover or in the system manual.
2
The detector has a separate base which attaches to a
standard 4 inch square, 4 inch octagonal, or single gang
switchbox. The size and depth of the box is determined
by the NEC for the number and size of conductors used.
A finishing trim ring (Model RA-ADB) is available for
bases using a 4 inch square box.
TO MOUNT:
Route all wires outward from outlet box.
« When viewing the alarm LED is critical, position the
LED mark in the base in the necessary direction.
(See Figure 2.)
« Mount base to outlet box and route wires through the
hole in the center of the base. Make connections
directly to the base terminals. Refer to Figure 1 for
details.
¢ When mounting the detector base and routing wires
through the cutouts in the air shield, make sure the
ashield is sealed against air leaks. Open the cutouts
only as much as required.
e Remove factory installed jumper in base between
terminals 1a and 1b,
Note: To ensure proper installation of the detector
head into the base. check that the wires are
properly dressed at installation.
a. Position all wires flat
against the base.
b. Take up all slack in
the outlet box.
c. Route wires away
from connector
terminals.
BASE MOUNTING
HOLES
Figure 2 LOCATION WITH
i DETECTOR
Detector Installation ystacteo in BASE
INSTALLATION OF DETECTOR HEAD
1. Align notch in detector, cover
to raised surface on outer
ring of base (See Figure 3).
2. Push detector head into
base and rotate clockwise
to make electrical connec-
tions. The detector auto-
matically stops and locks Figure 3
into place. Detector Mounting