Beruflich Dokumente
Kultur Dokumente
DIgSILENT GmbH
Heinrich-Hertz-Str. 9
72810 - Gomaringen
Germany
T: +49 7072 9168 0
F: +49 7072 9168 88
http://www.digsilent.de
info@digsilent.de
Version: 15.2
Edition: 1
Copyright 2014, DIgSILENT GmbH. Copyright of this document belongs to DIgSILENT GmbH.
No part of this document may be reproduced, copied, or transmitted in any form, by any means
electronic or mechanical, without the prior written permission of DIgSILENT GmbH.
Two-Winding Transformer (3-Phase) (ElmTr2,TypTr2)
Contents
Contents
1 General Description
1.1 Model diagrams
4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
13
14
15
17
17
17
. . . . . . . . . . . . . . . . . . . . . . . .
18
21
22
3 Short-Circuit Analysis
25
25
25
26
4 RMS-Simulation
26
5 EMT-Simulation
26
26
26
27
27
31
Contents
32
33
34
6.1.1 K-Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
35
6.1.2 Factor-K . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
35
6.1.3 FHL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
35
36
36
37
37
37
7.2.1 Yd-transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
37
7.2.2 YNyn/YNy/Yyn-transformer . . . . . . . . . . . . . . . . . . . . . . . . . .
37
38
39
39
42
43
43
48
10 References
53
List of Figures
54
List of Tables
55
General Description
General Description
The two-winding transformer model is a highly-detailed model for various kinds of three-phase,
two-winding transformers in power systems. It can be used to represent network transformers,
block transformers, phase-shifters, auto transformers or MV-voltage regulators.
The 2-winding transformer model in PowerFactory is comprised of the 2-winding transformer
element (ElmTr2), and the 2-winding transformer type (TypTr2). The transformer element allows
input of data relating to the control of the transformer under steady-state conditions, and the
transformer type allows input of the physical properties of the transformer. For simplicity, these
will simply be referred to hereafter as the element and the type, respectively.
The first section of this document describes the general model which is valid for all PowerFactory
calculation functions. Other aspects such as saturation or capacitive effects, which are only
relevant to specific calculation functions are described in later sections. Section 7 provides
useful tips for special applications of the 2-winding transformer model.
1.1
Model diagrams
1.1.1
The positive sequence (per-unit) equivalent circuit of the transformer is shown in Figure 1.1.
The leakage reactances and winding resistances are included on the HV and LV sides, and the
magnetising branch accounts for core losses. These losses are represented by the magnetising
reactance and a parallel resistance. The ideal transformer has a complex winding ratio with a
magnitude of 1:1 and models the phase shift representing the vector groups of the two windings.
Figure 1.1: Positive sequence (per-unit) equivalent circuit of the 2-winding transformer
The relation between the mathematical parameters in the model and the parameters in the
transformer type and element dialogs are described below, and the corresponding nomenclature
is provided in Table 1.1.
The nominal impedance is given by:
Zr,HV =
Urh 2
Sr
()
(1)
Zr,LV =
Url 2
Sr
()
(2)
The short-circuit impedance (zsc ), short-circuit resistance (rsc ), and short-circuit reactance (xsc )
are calculated as follows:
usc
zsc =
(p.u.)
(3)
100
Two-Winding Transformer (3-Phase) (ElmTr2,TypTr2)
General Description
PCu /1000
(p.u.)
Sr
p
= zsc 2 rsc 2 (p.u.)
(4)
rsc =
xsc
(5)
(p.u.)
(p.u.)
(6)
(7)
The resistive losses in the windings (HV and LV sides, respectively) are represented by:
rCu,HV = rsc R,HV,1
(p.u.)
(p.u.)
(8)
(9)
(p.u.)
(p.u.)
(10)
(11)
The magnetising impedance is dependent on the no-load current, I0 , and is given by:
zM =
1
I0 /100
(p.u.)
(12)
Sr
PF e /1000
(p.u.)
(13)
1
1
zM 2
(p.u.)
(14)
rF e 2
Table 1.1 provides a comprehensive list of the input- and calculation parameters described
above, and their associated symbols and descriptions.
General Description
Symbol
Urh
Url
Sr
PCu
usc
zsc
rsc
xsc
X,HV,1
Unit
kV
kV
MVA
kW
%
p.u.
p.u.
p.u.
p.u.
itrdl lv
X,LV,1
p.u.
itrdr
R,HV,1
p.u.
itrdr lv
R,LV,1
p.u.
rCu,HV
rCu,LV
zshv
zshl
x,HV
x,LV
curmg
pf e
zM
xM
rF e
1.1.2
I0
PF e
p.u.
p.u.
p.u.
p.u.
p.u.
p.u.
%
kW
p.u.
p.u.
p.u.
Description
Nominal impedance, HV side
Nominal impedance, LV side
Rated voltage on HV side
Rated voltage on LV side
Rated power
Copper losses
Relative short-circuit voltage
Short-circuit impedance
Short-circuit resistance
Short-circuit reactance
Proportion of transformer short-circuit reactance on HV
side in the positive sequence system
Proportion of transformer short-circuit reactance on LV
side in the positive sequence system
Proportion of transformer short-circuit resistance on HV
side in the positive sequence system
Proportion of transformer short-circuit resistance on LV
side in the positive sequence system
Resistance on HV side
Resistance on LV side
Leakage impedance on HV side
Leakage impedance on LV side
Leakage reactance on HV side
Leakage reactance on LV side
No-load current
No-load losses
Magnetising impedance
Magnetising reactance
Shunt resistance
The zero sequence equivalent model of a Yd-transformer including a tap changer at the HV
side is shown in Figure 1.2. Transformer models for a variety of configurations are provided in
Section 7.2.
General Description
(a)
(b)
Figure 1.2: Zero sequence equivalent circuit of a Yd-transformer with HV side tap changer (a)
detailed representation (b) simplified representation
1.2
Tap changer
The tap changer is represented by an additional, ideal transformer connected to either the HV
or LV side (see Figure 1.3 and Figure 1.4). For most applications, the winding ratio of this
transformer is real and is defined by the actual tap position (in number of steps) multiplied by
the additional voltage per step.
Figure 1.3: Transformer model with tap changer modelled at the HV side
Two-Winding Transformer (3-Phase) (ElmTr2,TypTr2)
General Description
Figure 1.4: Transformer model with tap changer modelled at the LV side
Phase-shifting transformers are modelled by a complex ratio using a complex value, du, which
is expressed as:
du = dutap (cos(phitr) + j sin(phitr))
(15)
This is illustrated for the asymmetrical tap changer model in Figure 1.5.
For the symmetrical phase shifter, as illustrated in Figure 1.6, du1 and du2 are expressed as:
du1 = j
dutap
2
du2 = j
dutap
2
(16)
(17)
General Description
1.3
The transformer type provides the option Internal Delta Winding for transformers defined as
YN-YN. The internal zero sequence model of a YN-YN transformer is depicted in Figure 1.7.
From the transformer type data, the quantities z0H , z0L and z0T are calculated. When the
Internal Delta Winding option is ticked, uk0 and ur0 between the HV and LV windings are:
uk0 = |z0H + z0L |
(p.u.)
(18)
and
ur0 = | Re(z0H ) + Re(z0L )|
(p.u.)
(19)
The quantities uk0 and ur0 will be overwritten by the defined Measurement Report. The zero
sequence impedance of the delta (tertiary) winding will be kept constant. The zero sequence
contribution factor will also be kept constant and is calculated from the corresponding type data,
Distribution factor for the zero sequence reactance:
x0dist =
Im(z0H )
Im(z0H ) + Im(z0L )
(p.u.)
(20)
General Description
Re(z0H )
Re(z0H ) + Re(z0L )
(p.u.)
(21)
If the sum of the real parts equals zero, r0dist will be set to x0dist. If the sum of the imaginary
parts also equals zero, the distribution factor, x0dist, will be set to 0.5. The zero sequence
impedance for the HV and LV winding (dependent on the tap position) is then calculated as
follows:
x0hv = x0(tap) x0dist (p.u.)
(22)
x0lv = x0(tap) (1 x0dist)
(p.u.)
(23)
and
r0hv = r0(tap) r0dist
r0lv = r0(tap) (1 r0dist)
with:
(24)
(p.u.)
(p.u.)
(25)
uk0(tap)2 ur0(tap)2
100
ur0(tap)
r0(tap) =
(p.u.)
100
x0(tap) =
(p.u.)
(26)
(27)
To determine the complex impedances in Figure 1.7, three measurements are required:
1. The zero sequence current injected at the HV terminal with the LV terminal short-circuited:
q
(28)
z0HLs = ur0hls + j uk02hls ur02hls (p.u.)
where uk0hls is the HV impedance (in p.u.) and ur0hls is the HV resistance (in p.u.), with the LV
terminal short-circuited in both cases.
2. The zero sequence current injected at the HV terminal with the LV terminal open-circuited:
q
z0HLo = ur0hlo + j uk02hlo ur02hlo (p.u.)
(29)
where uk0hlo is the HV impedance (in p.u.) and ur0hlo is the HV resistance (in p.u.), with the LV
terminal open-circuited in both cases.
3. The zero sequence current injected at the LV terminal with the HV terminal open-circuited:
q
z0LHo = ur0lho + j uk02lho ur02lho (p.u.)
(30)
where uk0lho is the LV impedance (in p.u.) and ur0lho is the LV resistance (in p.u.), with the HV
terminal open-circuited in both cases.
For the first measurement:
z0HLs = z0H +
z0L z0T
z0L + z0T
(p.u.)
(31)
(p.u.)
(32)
(p.u.)
(33)
10
General Description
(p.u.)
(34)
(p.u.)
(35)
Substituting (34) and (35) into (31), the tertiary impedances are obtained:
p
z0T = z0LHo (z0HLo z0HLs ) (p.u.)
Equation (36) leads to two solutions:
p
z0T (1) = + z0LHo (z0HLo z0HLs )
p
z0T (2) = z0LHo (z0HLo z0HLs )
(36)
(p.u.)
(37)
(p.u.)
(38)
The HV and LV zero sequence impedances are calculated for both solutions (37) and (38).
z0H (1) = z0HLo z0T (1)
(p.u.)
(39)
(p.u.)
(40)
(p.u.)
(41)
(p.u.)
(42)
For the first (1) and second (2) solutions, the following series reactances are calculated:
x0HL (1; 2) = x0H (1; 2) + x0L (1; 2)
(p.u.)
(HV LV )
(43)
(p.u.)
(HV T )
(44)
(p.u.)
(LV T )
(45)
1.3.1
Dependent parameters
When the Internal Delta Winding option in the transformer type is ticked, the six measured parameters are calculated from existing parameters:
The HV zero sequence impedance is:
Im(z0H ) = zx0hlh
uk0tr2 ur0tr2
(p.u.)
(46)
11
General Description
(47)
(p.u.)
uk0tr2 ur0tr2
(p.u.)
(48)
(p.u.)
(49)
(p.u.)
(50)
uk0tr
1 + rtox0n 2
(p.u.)
(51)
z0L z0T
z0L + z0T
uk0hls = |z0HLs |
(p.u.)
(p.u.)
ur0hls = Re(z0HLs )
(52)
(53)
(p.u.)
(54)
(p.u.)
(55)
(p.u.)
ur0hlo = Re(z0HLo )
(56)
(p.u.)
(57)
(p.u.)
(58)
(p.u.)
ur0lho = Re(z0LHo )
(p.u.)
(59)
(60)
If the Internal Delta Winding option is ticked and one of the six impedances is changed, z0H ,
z0L and z0T are calculated according to Section 1.3.1, and the parameters below are calculated
as follows:
Zero sequence impedance:
uk0tr = |z0H + z0L |
ur0tr = Re(z0H + z0L )
(p.u.)
(61)
(p.u.)
(62)
(p.u.)
(63)
|z0T |
|z0H + z0L |
Re(z0T )
(p.u.)
Im(z0T )
It should be noted that rtox0n is only set when rtox0n 0.
rtox0n =
(64)
|z0H |
|z0H + z0L |
(p.u.)
(65)
12
General Description
1.4
Short-circuit impedance
The short-circuit impedance can be entered on the Basic Data page of the type, depending on
the user-selected Input option. These Input options are described in Table 1.2, Table 1.3 and
Table 1.4.
Table 1.2: Type Basic Data: Positive sequence impedance
Positive sequence impedance
Short-Circuit Voltage uk and Copper Losses
Input
Short-Circuit Voltage
uk
Copper Losses
Short-Circuit Voltage
uk
SHC-Voltage Re(uk)
ukr
Short-Circuit Voltage
uk
Ratio X/R
Reactance x1
Resistance r1
Param. Unit
uktr
%
pcutr
uktr
kW
%
uktrr
uktr
xtor
x1pu
r1pu
p.u.
p.u.
Table 1.3: Type Basic Data: Zero sequence impedance (no internal delta winding)
Zero sequence impedance
Short-Circuit Voltage uk0 and SHC-Voltage Re(uk0)
Input
Short-Circuit Voltage
uk0
SHC-Voltage Re(uk0)
ukr0
Short-Circuit Voltage
uk0
Ratio X0/R0
Reactance x0
Resistance r0
Param. Unit
uk0tr
%
ur0tr
uk0tr
x0tor0
x0pu
r0pu
p.u.
p.u.
13
General Description
Table 1.4: Type Basic Data: Zero sequence impedance: YN-YN; with internal delta winding
Input
Param. Unit
HV-SHC-Voltage uk0
(LV short-circuit)
HV-SHC-Voltage
Re(uk0)
(LV short-circuit)
HV-SHC-Voltage uk0
(LV open)
HV-SHC-Voltage
Re(uk0)
(LV open)
LV-SHC-Voltage uk0
(HV open)
LV-SHC-Voltage
Re(uk0)
(HV open)
HV-SHC-Voltage uk0
(LV short-circuit)
HV-Ratio X0/R0
(LV short-circuit)
HV-SHC-Voltage uk0
(LV open)
HV-Ratio X0/R0
(LV open)
LV-SHC-Voltage uk0
(HV open)
LV-Ratio X0/R0
(HV open)
HV-Reactance x0
(LV short-circuit)
HV-Resistance r0
(LV short-circuit)
HV-Reactance x0
(LV open)
HV-Resistance r0
(LV open)
LV-Reactance x0
(HV open)
LV-Resistance r0
(HV open)
uk0hls
ur0hls
uk0hlo
ur0hlo
uk0lho
ur0lho
uk0hls
xtr0hls
uk0hlo
xtr0hlo
uk0lho
xtr0lho
1.4.1
x0puhls p.u.
r0puhls p.u.
x0puhlo p.u.
r0puhlo p.u.
x0pulho p.u.
r0pulho p.u.
If r1pu and x1pu are available as inputs on the Basic Data page of the transformer type:
p
uktr = r1pu2 + x1pu2 100 (%)
pcutr = r1pu 1000 strn
Two-Winding Transformer (3-Phase) (ElmTr2,TypTr2)
(66)
(67)
14
General Description
Accordingly, if tap dependent, r1putmn, r1putmx and x1putmn, x1putmx are available as inputs
on the Load Flow page, Tap Changer tab of the type.
For the minimum tap:
uktmn =
(%)
(68)
(69)
p
r1putmx2 + x1putmx2 100
(%)
1.4.2
(70)
(71)
The two additional input options for zero sequence impedance are available via the options page
in the type: Short-Circuit Voltage uk0 and X0/R0 Ratio and Reactance in p.u. and Resistance
in p.u. Based on the combination of selections of Internal Delta Winding and vector groups for
the HV and LV sides, there are two situations:
1. If Internal Delta Winding is not ticked or vector group is not YN-YN:
If uk0tr and x0tor0 are available as inputs on the Basic Data page of the transformer type:
p
r0pu = ur0tr/100/ 1 + x0tor02 (p.u.)
(72)
s
2
uk0tr
x0pu =
r0pu2 (p.u.)
(73)
100
Accordingly, if tap dependent, uk0tmn, uk0tmx and x0tor0tmn, x0tor0tmx are available as
inputs on the Load Flow page, Tap Changer tab of the type.
For minimum tap:
p
r0putmn = uk0tmn/100/ 1 + x0tor0tmn2 (p.u.)
s
2
uk0tmn
x0putmn =
r0putmn2 (p.u.)
100
(74)
p
r0putmx = uk0tmx/100/ 1 + x0tor0tmx2 (p.u.)
s
2
uk0tmx
x0putmx =
r0putmx2 (p.u.)
100
(76)
(75)
(77)
If r0pu and x0pu are available as inputs on the Basic Data page of the transformer type:
p
uk0tr = r0pu2 + x0pu2 100 (%)
(78)
(79)
(%)
15
General Description
x0tor0 =
x0pu
r0pu
(80)
(p.u.)
Accordingly, if tap dependent, r0putmn, r0putmx and x0putmn, x0putmx are available as inputs
on the Load Flow page, Tap Changer tab of the type.
For minimum tap:
uk0tmn =
(%)
(81)
(%)
(82)
(p.u.)
(83)
x0putmx
r0putmx
(%)
(84)
(%)
(85)
(p.u.)
(86)
(p.u.)
(87)
(p.u.)
(88)
(p.u.)
(89)
(p.u.)
(90)
(p.u.)
(91)
(p.u.)
(92)
(%)
(93)
(%)
(94)
(%)
(95)
(%)
(96)
(%)
(97)
(%)
(98)
xtr0hls =
x0puhls
r0puhls
(p.u.)
(99)
xtr0hlo =
x0puhlo
r0puhlo
(p.u.)
(100)
xtr0lho =
x0pulho
r0pulho
(p.u.)
(101)
16
The Load Flow Calculation in PowerFactory uses the detailed model of the transformer; i.e. all
shunt and branch impedances are considered appropriately in the positive- and zero sequence
systems.
As the tap changer is of particular interest in load flow calculations, data relating to the tap
changer is input as follows:
On the Load Flow page of the transformer element: control data and measurement report);
On the Load Flow page of the transformer type: tap changer positions and tap-dependent
impedance).
2.1
Element data
2.1.1
Measurement report
This can be used for the precise definition of a tap changer. It allows all tap-dependent parameters to be entered per tap step. If the option According to measurement report is ticked, the
corresponding type parameters are overwritten by their respective element parameters. The
input parameters are described in Table 2.1.
Table 2.1: Measurement report data (transformer element)
Parameter
Description
Unit
Voltage
Angle
kV
Degrees ( )
uk
PCu
Add. rating Factor
uk0
ur0
%
kW
p.u.
The following points should be noted regarding the zero sequence impedance, uk0 and ur0, in
the Measurement report:
17
1. If the transformer type options Internal Delta Winding and Tap dependent impedance are
disabled:
The column uk0 is set to the value of uk0tr (absolute uk0) from the transformer type;
The column ur0 is set to the value of ur0tr (resistive part ukr0) from the transformer
type.
2. If the transformer type option Internal Delta Winding is disabled and Tap dependent impedance
is enabled:
The column uk0 is set to the corresponding spline-interpolated value of uk0 (at tap)
from the transformer type;
The column ur0 is set to the corresponding spline-interpolated value of ur0 (at tap)
from the transformer type.
3. If the transformer type option Internal Delta Winding is enabled and the option Tap dependent impedance is disabled:
The column uk0 is set to the value of the calculated uk0 (absolute uk0) from the
transformer type;
The column uk0r is set to the value of the calculated ur0 (resistive part ukr0) from
the transformer type.
2.1.2
This is activated by setting the corresponding option on the Load Flow page of the transformer
element. Additionally, automatic tap adjustment can be globally enabled or disabled via the
Load Flow Calculation command (ComLdf ). The inputs required for the definition of tap changer
control are described in Table 2.2.
18
Description
According to
Measurement
Report
Tap Position
Automatic Tap
Changing
Tap
Changer
Controlled
Node
is at
Control
Mode
Setpoint
Remote Control
Voltage Setpoint
Lower/Upper
bound
Voltage control includes optional line drop compensation (LDC). This function controls the voltage at a remote busbar without measuring the voltage at that busbar. Instead, the value is
estimated by measuring the voltage at the HV or LV side of the transformer and simulating the
voltage drop across the line.
The principle of line drop compensation is shown in Figure 2.1 and the corresponding transformer element input parameters are provided in Table 2.3.
19
Description
Unit
Current
transformer rating
Voltage
transformer ratio
RSet, XSet
There is usually more than one possible solution to a load flow problem considering automatic
tap changer control. In meshed networks in particular, several transformers can control the
voltage in certain areas. In the case of parallel transformers, the problem can usually be solved
by operating the two parallel transformers in master-slave mode.
In a general configuration however, especially when parallel transformers have different shortcircuit impedances or different tap steps, the steady-state network solution cannot be easily
obtained. PowerFactory addresses this problem by allowing the user to enter a controller time
constant, specifying the speed of control actions and hence the participation of several transformers regulating the voltage at the same busbar.
The approach is based on controller block diagrams according to Figure 2.2. In the case of
flow controllers (P-/Q-control), the controller sensitivity translating a power mismatch into an
equivalent turns-ratio percentage can be entered additionally.
In the load flow algorithm, which only considers steady-state conditions, controller time constants and sensitivities are translated into equivalent participation factors.
20
(a)
(b)
The controller input parameters for the transformer element are described in Table 2.4.
Table 2.4: Dynamic and static control parameters
2.2
Parameter
Description
Unit
Controller time
constant
Controller
sensitivity dv/dP
Controller
sensitivity dv/dQ
%/MW
%/Mvar
Type data
The type data inputs available for the tap changer are listed in Table 2.5.
Table 2.5: Load Flow tap changer data
Parameter
Description
Unit
Type
At side
Degrees ( )
Additional voltage
per tap
Phase of du
Neutral/min./max.
position
21
2.2.1
The transformer tap model supports the definition of two taps, which may have differing types:
Ratio/Asym. Phase Shifter
Ideal Phase Shifter
Symmetrical Phase Shifter
Ideal phase shifter If this option is selected for the tap changer type, the magnitude of the
voltage will not be changed, only the angle. The parameter dphitap or/and dphitap2 should not
be set to 0 , 180 or 180 . This model is illustrated in Figure 2.3.
If the tap is on the HV side, the complex transformer ratio is calculated as follows:
thv = cos(nntapint dphitap) + j sin(nntapint dphitap)
(102)
(103)
Symmetrical phase shifter If this option is selected for the tap changer type, the parameter
dphitap will be automatically set to 90 . A second tap definition is not available. The complex
transformer ratio is calculated as shown for the following cases:
1. If tap changer 1 is modelled at the HV side:
thv = 1 + nntapint
du
(cos(phitr) + j sin(phitr))
2
(104)
22
with phitr = 90
and for the opposite tap at the LV side:
tlv = 1 nntapint
du
(cos(phitr) + j sin(phitr))
2
(105)
du
(cos(phitr) + j sin(phitr))
2
(106)
with phitr = 90
and for the opposite tap at the HV side:
thv = 1 nntapint
du
(cos(phitr) + j sin(phitr))
2
(107)
(108)
A positive tap position (tap > neutral) leads to a negative voltage angle at the LV side.
du
(cos(phitr) + j sin(phitr))
2
du2
= 1 + nntap2int
(cos(phitr2) + j sin(phitr2))
2
ttap1 = 1 + nntapint
ttap2
(109)
23
If the second tap changer is an ideal phase shifter, the corresponding tap (ttap2 ) is calculated
according to:
ttap2 = cos(nntap2int dphitap2) + j sin(nntap2int dphitap2)
(110)
(111)
(112)
tlv = 1
2. If both tap changers are modelled at the LV side:
thv = 1
(113)
(114)
tlv = ttap2
4. If tap changer 1 is at the LV side and tap changer 2 is at the HV side:
thv = ttap2
(115)
tlv = ttap1
The internal voltages and currents are transferred accordingly:
uhv
thv
= ihv thv
u0 hv =
i0 hv
(116)
u0 lv =
i0 lv
(117)
Tap dependent impedance Data relating to the tap dependent impedance can be entered
when the Tap dependent impedance option in the type has been selected. Parameters that
can be considered to be tap dependent are the short-circuit impedances and copper losses
(short-circuit resistance) in the positive- and zero sequence systems. For tap positions between
minimum and neutral, and between neutral and maximum, tap dependent parameters are interpolated using splines.
Transformer type Load Flow tap dependent impedance data is shown in Table 2.6.
24
Short-Circuit Analysis
Description
Unit
Reactance x1
p.u.
Resistance r1
Reactance x0
Resistance r0
Ratio X0/R0
p.u.
p.u.
p.u.
p.u.
Zero sequence magnetising admittance calculation The zero sequence magnetising admittance is always calculated from uk0 at the neutral position of the transformer type (independent of the Measurement Report or whether the option Tap dependent impedance is enabled).
For a transformer with the option Internal Delta Winding ticked, the zero sequence magnetising
admittance is ignored. In such cases, the calculated zero sequence impedance for the internal
delta winding (tertiary winding) is used instead.
Short-Circuit Analysis
3.1
3.1.1
IEC calculations
Element data
The VDE/IEC Short-Circuit page of the transformer element provides inputs which are used to
calculate the impedance correction factor of the transformer. The first option, Unit Transformer,
defines whether the transformer is a unit transformer or a network transformer. In the case
of unit transformers, one common correction factor is applied to transformers and generators,
independent of the actual operating conditions of a selected transformer. Network transformers
are considered individually.
The second option, Long-term operating conditions before short-circuit are known, is more specific (requiring additional input data) and may lead to more precise calculation results.
If the following combination of options have been ticked:
Unit Transformer (VDE/IEC Short-Circuit page of the transformer element); and
Long-term operating conditions before short-circuit are known (VDE/IEC Short-Circuit
page of the transformer element); and
On-load Tap Changer (VDE/IEC Short-Circuit page of the transformer type),
then the parameter Minimum Operating Voltage can be entered on the VDE/IEC Short-Circuit
page of the transformer element.
25
EMT-Simulation
3.1.2
Type data
Short-circuit calculations according to IEC assume that the shunt impedances (i.e. magnetising
reactances and iron losses) in the positive- and negative sequence are neglected. The shunt
impedances in the zero sequence however, must be considered. These input parameters are
available on the VDE/IEC Short-Circuit page of the type dialog.
The short-circuit calculation according to IEC distinguishes between no-load and on-load tap
changers. Different impedance correction factors apply for each group. On-load variation of the
tap changer can be ticked on the VDE/IEC Short-Circuit page of the type dialog.
RMS-Simulation
The model used by the RMS simulation is identical to the load flow model. However, tap controller definitions are not considered. For the simulation of tap controllers, a separate dynamic
model must be defined that can be interfaced with the transformer using the input variable
nntapin (tap-input).
EMT-Simulation
5.1
5.1.1
Element data
Stray capacitances
In high frequency EMT applications, e.g. switching or lightning studies, transformer capacitances should be considered.
The stray capacitances of a transformer do not only depend on the physical characteristics of
the transformer (i.e. the length of the windings, insulating material, core dimensions, etc) but
also on the installation environment as well (indoor or outdoor transformer; proximity to other
grounded components, walls, etc).
The following capacitances can be defined after ticking the Consider Capacitances option on
the EMT-Simulation page of the transformer element:
Capacitance HV to ground : applies to the positive- and zero sequence
Capacitance LV to ground : applies to the positive- and zero sequence
Capacitance HV-LV, positive sequence
Capacitance HV-LV, zero sequence
Two-Winding Transformer (3-Phase) (ElmTr2,TypTr2)
26
EMT-Simulation
5.2
Type data
5.2.1
Saturation characteristic
Figure 5.1 shows the equivalent model of a 2-winding, 3-phase transformer for the positive sequence. For simplicity, the tap changer is not illustrated in the Figure, however it is considered in
the model according to Figure 1.3, Figure 1.4 and Figure 1.5 as described in previous sections.
The excitation current of a transformer (no-load test) consists of an imaginary part, which is the
magnetising current flowing through the non-linear reactance XM 1 in Figure 5.1, and a smaller
real part flowing through the resistance RF e , which accounts for the excitation losses.
The non-linear magnetising reactance XM represents the saturation characteristic of the transformer and is defined in the transformer type (EMT-Simulation page). The model supports the
following options, which are explained in detail in the following sections:
Linear : no saturation considered.
Two slope : the saturation curve is approximated by two linear slopes.
Polynomial : the saturation curve is approximated by a polynomial of user-defined order. The
polynomial fits asymptotically into the piecewise-linear definition.
Current/Flux values : the user inputs current-flux values as a sequence of points and selects
either piecewise-linear or spline interpolation.
Figure 5.1: Positive sequence equivalent circuit of the 2-winding, 3-phase transformer
The position of the magnetising branch in the equivalent model of Figure 5.1 is defined in terms
of the distribution of the leakage reactance and resistance (in the type, on the EMT Simulation
page). The default value is 0.5, which means that the total leakage impedance of the transformer
(short-circuit impedance) is equally distributed between the HV and LV windings. The user can
change the position of the magnetising branch in the transformer model by modifying these
factors accordingly.
Two slope and polynomial characteristic Figure 5.2 shows the magnetising current-flux
plots for the two slope and polynomial characteristics. The input parameters of both plots are
the same except for the saturation exponent, which only applies to the polynomial characteristic.
The input parameters are listed in Table 5.1.
27
EMT-Simulation
Description
Unit
Knee Flux
p.u.
Linear
(unsaturated)
reactance
Saturated
reactance
Saturation
exponent
p.u.
p.u.
-
The reciprocal of the p.u. unsaturated reactance is equal to the p.u. magnetising current (i.e.
the imaginary part of the exciting current). Therefore, PowerFactory automatically adjusts the
unsaturated reactance based on the no-load current and no-load losses entered on the Load
Flow page of the type, and vice-versa:
s
2
2
IM
1
Pexc
=
(118)
XM
IR
SR
where:
IM : magnitude of the exciting current in the no-load test. This can be entered on the Load
Flow page of the transformer type, under Magnetising Impedance; No Load Current (in
%);
Two-Winding Transformer (3-Phase) (ElmTr2,TypTr2)
28
EMT-Simulation
Figure 5.3: Equivalent (per-unit) circuit of the 2-winding, 3-phase transformer (magnetising current)
The per-unit values used for the definition of the saturation characteristic of the positive sequence model are referred to the following base quantities:
Ubase [kV ]: nominal voltage of the (energising) winding, i.e. the winding used for the noload test;
Sbase [M V A]: nominal power of the (energising) winding;
29
EMT-Simulation
Sbase [M V A]
Ibase [A] =
1000
3 Ubase [kV ]
Ubase [kV ]/ 3
base [V s] =
1000
2f [kHz]
2
Ubase
[kV ]
1
Lbase [H] =
Sbase [M V A]
2f [Hz]
bmsat
1
bm
log
(ksat + 1)
0 = M knee e
iknee
(p.u.)
(120)
(p.u.)
(121)
ksat
k
M knee sat
bm
=
M knee 1 +
0
0
bmsat
((a, b, c) M knee )
0
(p.u.)
(122)
bmsat
((a, b, c) + M knee )
0
(p.u.)
(123)
otherwise:
bmsat
iM X (a, b, c) =
(a, b, c)
0
!
(a, b, c) ksat
1+
0
(p.u.)
(124)
and:
iM (a, b, c) = uM (a, b, c) gm(a, b, c) + iM X (a, b, c)
(p.u.)
(125)
where gm(a, b, c) are available as input signals for EMT simulations and are initialised using gm,
which is defined as:
gm = pf e/1000/strn (p.u.)
(126)
and:
ymag =
bm =
curmg
100
(p.u.)
ymag 2 gm2 0
or
bm =
0
xmlin
(p.u.)
(p.u.)
0 = 2 fnom
(rad/s)
(127)
(128)
(129)
(130)
30
EMT-Simulation
bmsat =
M knee =
1
0
xmair
ksat + 1
0
ksat
(p.u.)
(p.u.)
(131)
(132)
and xmair is the saturated reactance (p.u.), 0 is the knee flux (p.u.), and ksat is the saturation
exponent.
Current-flux values The saturation curve can also be defined in terms of measured currentflux values, and a choice of either piecewise linear or spline interpolation is available.
The current-flux values in the table are peak values in p.u. In a power transformer with impressed voltage, the magnetising flux in p.u. is equal to the magnetising voltage in p.u., thus
flux and voltage are interchangeable and the p.u. current-flux curve also represents a p.u.
current-voltage curve. Furthermore, it can be assumed that the applied voltage remains fairly
linear during no-load tests, hence the ratio of RMS to peak values of the voltage is given by 2.
The magnetising current, on the other hand, is distorted (i.e. non-sinusoidal) because of the
saturation
curve. Consequently, the ratio of RMS to peak value of the magnetising current is no
longer 2 and the user is required to enter true peak values in the table.
The base quantities of the p.u. values in the current-flux table are also referred to the peak
values of the corresponding nominal variables:
Ibase [A] =
base [V s] =
5.2.2
Sbase [M V A]
2
1000
3 Ubase [kV ]
Ubase [kV ]/ 3
1000
2f [kHz]
The zero sequence magnetising current depends largely on the physical characteristics of the
transformer core (three-legged, five-legged, shell-type, etc.) and its vector group. Figure 5.4
shows the zero sequence equivalent circuit.
Figure 5.4: Zero sequence equivalent circuit of the 2-winding, 3-phase transformer
Transformer with delta-connected windings If the transformer has delta-connected windings, then any zero sequence excitation approximates a zero sequence short-circuit, as the
delta-connected winding short-circuits the zero sequence current. In such cases there is no
need to represent zero sequence saturation.
Two-Winding Transformer (3-Phase) (ElmTr2,TypTr2)
31
EMT-Simulation
Transformer without delta-connected windings If the transformer does not have deltaconnected windings, then the zero sequence excitation current is generally higher than the
positive sequence excitation current and largely depends on the core type.
To account for the higher zero sequence linear exciting current when no delta-connected winding is available, PowerFactory allows for the definition of a linear (unsaturated) zero sequence
magnetising impedance. This zero sequence magnetising impedance and its R/X ratio are defined in the type, on the Load Flow page. The input parameters are displayed in the dialog
depending on the vector group (and are therefore hidden in cases where a delta-connected
winding has been selected).
To account for the core type dependency of the zero sequence saturation characteristic, the
transformer model supports the following two options on the EMT-Simulation page of the type:
3-Limb core: this option should be used for three-legged core designs. In this core type, the
fluxes are roughly equal in the three legs and must therefore return outside the core
through the air-gap and the tank. Because of the fact that the air-gap and the tanks are
non-magnetic, the zero sequence magnetising current is almost linear and therefore the
model uses the linear zero sequence magnetising impedance defined on the Load Flow
page. In other words, zero sequence saturation effects are not considered.
5-Limb core: this option should be used for five-legged and shell-type cores. As the zero
sequence fluxes return inside the core, the model uses the saturation characteristic (of
the positive sequence) in the zero sequence magnetising reactance as well.
5.3
Residual flux
The residual flux is the magnetising flux that remains in the core after the transformer has
been switched off. A residual flux, as opposed to a remnant flux1 , implies the circulation of a
magnetising current (M = LM IM ).
Once the transformer has been switched off, this magnetising current circulates through the
no-load losses resistance, Rm , and de-magnetises the core. The flux then decays exponentially
with a time constant, Lm /Rm , where Lm is the linear magnetising inductance. To simulate the
decaying magnetising current, and hence the decaying residual flux, it is necessary to define
the no-load losses. Otherwise, if Rm = 0, the magnetising current cannot circulate and PowerFactory will automatically set the residual flux to zero as soon as the transformer has been
switched off.
The user can also define the residual flux in the EMT simulation via a parameter event. The
residual flux is entered in -components using the following signals:
psimd: residual flux ( ), -component in p.u.
psimq: residual flux ( ), -component in p.u.
psim0: residual flux ( ), -component in p.u.
1 The
32
Harmonics/Power Quality
2
1
1
3
3
3
a
1
1
3
3
1
1
1
3
3
3
The inverse transformation is given by:
1
b =
2
c
1
3
2
The calculation parameters c:psim c, c:psim b and c:psim c give the resulting flux (as a result
of the simulation) in natural components for the phases a, b and c, respectively.
Generally speaking, it is difficult to reliably predict the residual flux of a transformer. However, as
the residual flux strongly influences the amplitude of inrush currents, it should be considered in
the model. If it is not known, typical maximum values between 0.8 and 0.9 p.u. can be assumed
for worst-case conditions.
Harmonics/Power Quality
In order to accurately model the high frequency effects of transformers, additional capacitances
need to be considered, as shown in Figure 6.1. These capacitances are equivalent capacitances of the model and do not represent the actual winding capacitances. In order to obtain
equivalent capacitances from winding capacitances, the winding connection (D/Y) must be additionally considered. The high frequency model according to Figure 6.1 provides an accurate
frequency response with respect to voltages and currents at the transformer terminals. However, internal effects such as internal voltage stress cannot be simulated.
33
Harmonics/Power Quality
(a)
(b)
Figure 6.1: HF model for (a) external capacitances in the positive sequence system; and (b)
zero sequence system
6.1
Transformers experience increased losses in the presence of power system harmonic currents.
In the worst-case, excessive losses can lead to transformer overheating and subsequent failure.
To assist in the selection of an appropriate transformer, various factors are available:
K-factor (UL 1562); mainly used in the US
Factor-K (BS 7821); mainly used in Europe
Harmonic Loss Factor (FHL) (IEEE C.57.110-1998)
These factors are indicators of the ability of a transformer to handle harmonic loads. Non-linear
loads in the power system produce harmonic currents which are capable of causing unwanted
side-effects, including increased transformer losses. Transformer losses are comprised of:
Stray magnetic losses in the transformer core; and
Eddy current and resistive losses in the transformer windings.
In the presence of harmonic currents, eddy current losses can become large because they
increase with the square of the frequency. The eddy current loss at harmonic order h is given
Two-Winding Transformer (3-Phase) (ElmTr2,TypTr2)
34
Harmonics/Power Quality
by:
Ph = Pf Ih 2 h2
(133)
where Pf is the eddy current loss at the fundamental frequency f ; Ph is the eddy current loss at
harmonic order h; and Ih is the fraction of total rms load current at harmonic order h. The total
eddy current loss is given by the following summation:
Pt = Pf
hX
max
Ih 2 h2
(134)
h=1
6.1.1
K-Factor
The K-Factor accounts for the increased eddy current losses due to harmonic currents. Mathematically, it is the ratio of eddy current losses in the presence of non-linear and linear loads
[3]:
hX
max
Pt
=
Ih 2 h2
(135)
K=
Pf
h=1
Following the calculation of the K-Factor, an appropriate K-transformer can then be selected
which has a higher K-rating.
6.1.2
Factor-K
e
K = 1+
1+e
I1
I
2
hX
max
hq
h=2
Ih
I1
2 !#0.5
(136)
where e is the eddy current loss at the fundamental frequency divided by the loss due to a dc
current equal to the rms values of the sinusoidal current, both at reference temperature. The
harmonic order is represented by h, and the exponential constant, q, depends on the type of
winding and the frequency. Typical values are 1.7 for transformers utilising round/rectangular
cross-section conductors in both windings, and 1.5 for transformers which use foil-type low
voltage windings. This value should be available from the transformer manufacturer. I is the
rms value of the sinusoidal current including all harmonics, and is given by:
I=
hX
max
!0.5
2
(Ih )
= I1
"h
2 #0.5
max
X
Ih
h=1
6.1.3
h=1
I1
(137)
FHL
(138)
35
Harmonics/Power Quality
6.1.4
Input data
For the calculation of any of these factors, the ratio of eddy current losses to copper losses
should be entered in the transformer type (Harmonics/Power Quality page) using input parameter Ratio: eddy current-/copper losses. By default, this value is set to 0.1 (i.e. 10%).
Additionally, for the calculation of Factor-K, the exponent q (from (136)) must be entered in
the Harmonic Load Flow command (ComHldf ) via input parameter Calculation of Factor-K for
Transformers (Exponent).
6.2
On the Harmonics page of the transformer type, a frequency-dependent zero sequence impedance
can be defined. If the zero sequence impedance is included in the Measurement Report, the
characteristic should be defined as relative otherwise the value in the Measurement Report will
be overwritten. The distribution factor for the zero sequence impedance will be kept constant
and is obtained as follows:
From the transformer type, Distribution of Zero Sequ. Leakage-Impedances (zx0hl h) for
a transformer with no Internal Delta Winding;
For a transformer with an Internal Delta Winding, the distribution factors are calculated as
in Section 1.3.
36
7
7.1
All transformer parameters entered in p.u. or % are referred to the transformer ratings. Transformer rated voltages different from nominal busbar voltages are correctly considered.
7.2
7.2.1
This model is described in detail in Section 1.1.2 as a general example for zero sequence
system modelling.
If no accurate data is available from the manufacturer, the following estimations can be used for
the zero sequence impedance voltages as seen from the grounded side:
Core-type transformer (3-limb) : usc,0 = 0.85 Usc,1 ;
Shell-type transformer (4/5-limb) : usc,0 = 1.0 Usc,1 ;
uRr,0 = 0
uRr,0 = 0
0 =
7.2.2
1
(A + B + C )
3
(139)
YNyn/YNy/Yyn-transformer
The zero sequence equivalent circuit diagram of the YNyn transformers is depicted in Figure 7.1.
The equivalent circuit diagram of star connected transformers with isolated star point can be
derived from this equivalent circuit by assuming infinite grounding impedances at the respective
side.
37
zM 0
zsc,0
7.2.3
= 3 . . . 10
zM 0
zsc,0
An internal tertiary delta winding can be considered by either using the PowerFactory threewinding model or, in a simplified way, by taking into account that the short-circuit impedance of
the internal delta winding can be modelled by an impedance parallel to the zero sequence magnetising impedance as shown in Figure 7.2. Hence, an internal delta winding can be modelled
by simply assuming a very low zero sequence magnetising reactance.
Typical values are:
zM 0
= 1, . . . , 2.4
zsc,0
The short-circuit resistance of the delta-tertiary winding can be entered as R/X ratio in the Mag.
R/X field available on the Load Flow page of the transformer type.
Two-Winding Transformer (3-Phase) (ElmTr2,TypTr2)
38
7.2.4
Model of YNzn/YNz/Zyn-transformer
A zig-zag winding completely decouples the primary and secondary sides of the zero sequence
system, as shown in Figure 7.3.
Figure 7.3: YNzn-transformer (zero sequence system) with HV side tap changer (detailed representation)
7.3
The PowerFactory model for the auto transformer is a special case of the 2-winding star/star
(Yy)-transformer. The option Auto Transformer can be ticked on the Basic Data page of the
element, however this option is only visible when the transformer has no assigned type, or
39
when the assigned type has its vector group set to YY.
The effect of this connection can be seen in Figure 7.4. Besides the additional connection
between the star points, only one grounding impedance can be entered.
Figure 7.4: Yy-transformer (zero sequence system) in auto transformer configuration (incl. tap
changer on the HV side)
For the Yy auto transformer the currents on the HV side and the LV side both flow through the
same grounding impedance ZE = RE + jXE . The voltage over this grounding impedance, ZE ,
therefore affects the zero sequence system voltages on both sides. This makes it necessary to
consider the absolute values of the impedances, currents and voltages and not the p.u. values.
An additional delta tertiary winding is often used to reduce the zero sequence impedance of
auto transformers. The approach for modelling this is equivalent to the internal delta tertiary
winding modelling of Yy transformers.
40
41
Figure 8.1: Input/output definition of 2-winding transformer model for RMS- and EMT-simulation
Description
Unit
nntapin
Description
Unit
psimd
psimq
psim0
p.u.
p.u.
p.u.
Table 8.3: Additional parameters and signals for EMT transformer model (calculation parameters)
Parameter
Description
Unit
psim a
psim b
psim c
im a
im b
im c
p.u.
p.u.
p.u.
p.u.
p.u.
p.u.
42
9
9.1
Description
loc name
nt2ph
strn
frnom
utrn h
utrn l
uktr
Name
Technology
Rated Power
Nominal Frequency
Rated Voltage: HV-Side
Rated Voltage: LV-Side
Positive Sequence Impedance:
Short-Circuit Voltage uk
Positive Sequence Impedance:
Copper Losses
Positive Sequence Impedance:
SHC-Voltage (Re(uk)) ukr
Positive Sequence Impedance: Ratio
X/R
Vector Group: HV-Side
Vector Group: LV-Side
Vector Group: Internal Delta Winding
Vector Group: Phase Shift
Vector Group: Name
Zero Sequ. Impedance, Short-Circuit
Voltage: Absolute uk0
Zero Sequ. Impedance, Short-Circuit
Voltage: Resistive Part ukr0
Tap Changer: at Side
Tap Changer: Additional Voltage per
Tap
Tap Changer: Phase of du
Tap Changer: Neutral Position
Tap Changer: Minimum Position
Tap Changer: Maximum Position
Magnetising Impedance: No Load
Current
Magnetising Impedance: No Load
Losses
Zero Sequence Magnetising
Impedance:
Mag. Impedance / uk0
Zero Sequence Magnetising R/X ratio:
Mag. R/X
Distribution of Zero Sequ.
Leakage-Impedances: z, Zero Sequ.
HV-Side
pcutr
uktrr
xtor
tr2cn h
tr2cn l
iIntDelta
nt2ag
vecgrp
uk0tr
ur0tr
tap side
dutap
phitr
nntap0
ntpmn
ntpmx
curmg
pfe
zx0hl n
rtox0 n
zx0hl h
Unit
MVA
Hz
kV
kV
%
kW
%
*30deg
%
%
%
deg
%
kW
43
Parameter
Description
zx0hl l
x0tor0
x0pu
r0pu
uk0 hls
ur0 hls
uk0 hlo
ur0 hlo
uk0 lho
ur0 lho
x0pu hls
xtr0 hls
r0pu hls
x0pu hlo
xtr0 hlo
r0pu hlo
x0pu lho
xtr0 lho
r0pu lho
uk0delta
ur0delta
x0tor0delta
x0delta
r0delta
itapch
tapchtype
Unit
p.u.
p.u.
%
%
%
%
%
%
p.u.
p.u.
p.u.
p.u.
p.u.
p.u.
%
%
p.u.
p.u.
44
Parameter
Description
tap side
dutap
dphitap
itapch2
tapchtype2
tap side2
dutap2
dphitap2
phitr2
nntap02
ntpmn2
ntpmx2
itapzdep
uktr
x1pu
x1putmn
x1putmx
pcutr
uktrr
xtor
r1pu
r1putmn
r1putmx
uk0tr
x0pu
x0putmn
x0putmx
ur0tr
Unit
%
deg
%
deg
deg
%
p.u.
p.u.
p.u.
kW
%
p.u.
p.u.
p.u.
%
p.u.
p.u.
p.u.
%
45
Parameter
Description
x0tor0
r0pu
x0tor0tmn
r0putmn
x0tor0tmx
r0putmx
itapzdep
uktmn
uktmx
pcutmn
ukrtmn
xtortmn
pcutmx
ukrtmx
xtortmx
uk0tmn
uk0tmx
uk0rtmn
uk0rtmx
itrdl
itrdl lv
itrdr
itrdr lv
itrldf
satcue
satvol
Unit
p.u.
p.u.
p.u.
%
%
kW
%
kW
%
%
%
%
%
%
p.u.
46
Parameter
Description
Unit
satflux
iInterPol
smoothfac
p.u.
iLimb
itratioadpt
pT
ansiclass
pict1
pitt1
itrtype
pict2
pitt2
itrmt
psi0
xmlin
xmair
ksat
it0mt
pStoch
eddypc
fcharr1
fcharl1
fcharr0
fcharl0
strnfc
oltc
gnrl modif
gnrl modby
manuf
chr name
dat src
for name
doc id
desc
appr status
appr modif
appr modby
%
p.u.
s
p.u.
s
p.u.
p.u.
p.u.
StoTyptrf
MVA
47
9.2
Description
loc name
typ id
bushv
bushv bar
buslv
buslv bar
iZoneBus
outserv
ntnum
ratfac
Snom
i auto
Name
Type (TypTr2)
HV-Side (StaCubic)
HV-Side
LV-Side (StaCubic)
LV-Side
Zone
Out of Service
Number of: parallel Transformers
Rating Factor
Rated Power
Connected Star Points (Auto
Transformer)
HV-side, phase 2 internally grounded
Grounding Impedance, HV Side:
Neutral Point
Grounding Impedance, HV Side: Re
Grounding Impedance, HV Side: Xe
LV-side, phase 2 internally grounded
Grounding Impedance, LV Side:
Neutral Point
Grounding Impedance, LV Side: Re
Grounding Impedance, LV Side: Xe
r (Sbase)
x (Sbase)
r0 (Sbase)
x0 (Sbase)
Zone
Area
Area
Thermal Rating (IntThrating)
Rated Power (act. )
Neutral Conductor: N-Connection
Neutral Conductor: HV-Neutral
(StaCubic)
Neutral Conductor: HV-Neutral
Neutral Conductor: LV-Neutral
(StaCubic)
Neutral Conductor: LV-Neutral
Neutral Connection
HV-side, phase 2 connected
Internal Grounding Impedance, HV
Side: Star Point
i eahv
ignd h
re0tr h
xe0tr h
i ealv
ignd l
re0tr l
xe0tr l
rSbasepu
xSbasepu
r0Sbasepu
x0Sbasepu
cpZone
iAreaBus
cpArea
pRating
Snom a
cneutcon
bushvn
bushvn bar
buslvn
buslvn bar
iintgnd
i hvcon
cgnd h
Unit
MVA
Ohm
Ohm
Ohm
Ohm
p.u./Sbase
p.u./Sbase
p.u./Sbase
p.u./Sbase
MVA
48
Parameter
Description
Unit
cpeter h
p.u.
kA
kA
%
deg
deg
%
deg
49
Parameter
Description
Unit
phitr2
nntap2
c ptapc
Phase of du
Tap Changer 2: Tap Position
Controller, Tap Changer 1: External
Tap Controller
Controller, Tap Changer 1: External
Station Controller
Tap: Remote Control
Tap: Controlled Node
(StaBar,ElmTerm)
Tap: Controlled Branch (Cubicle)
(StaCubic)
Tap: Voltage Setpoint
Tap: Lower Voltage Bound
Tap: Upper Voltage Bound
Tap: Active Power Setpoint
Tap: Lower Active Power Bound
Tap: Upper Active Power Bound
Tap: Reactive Power Setpoint
Tap: Lower Reactive Power Bound
Tap: Upper Reactive Power Bound
Tap: Controller Time Constant
Controller, Tap Changer 1: Controller
Sensitivity dv/dQ
Controller, Tap Changer 1: Controller
Sensitivity dv/dP
Tap: Line Drop Compensation
Tap: Current Transformer Rating
Tap: Voltage Transformer Ratio
Tap: Rset V
Tap: Xset V
Tap Controller (ElmTr2)
Measured at
Measurement Report
Unit Transformer
Long-term operating condition before
short-circuit are known
Values for LV-Side: Highest Operating
Voltage
Values for LV-Side: Highest Operating
Current
Values for LV-Side: Power factor
Values for HV-Side (only for Unit
Transformer): Minimum Operating
Voltage
Frequent Fault ( >10(5)/lifetime,
Category II(III) )
deg
c pstac
i rem
p rem
p cub
usetp
usp low
usp up
psetp
psp low
psp up
qsetp
qsp low
qsp up
Tctrl
Kqctrl
Kpctrl
ildc
ldcct
ldcpt
ldcrs
ldcxs
tapctrl
iMeasLoc
mTaps
iblock
ilt op
Ub lv
Ib lv
cosphib lv
Ubqmin hv
ifrqft
p.u.
p.u.
p.u.
MW
MW
MW
Mvar
Mvar
Mvar
s
%/Mvar
%/MW
kV
kA
kV
50
Parameter
Description
iopt hf
Cg h
Consider HF-Parameter
HF-Parameter: Capacitance
HV-Ground
HF-Parameter: Capacitance
LV-Ground
HF-Parameter: Capacitance HV-LV,
1-Sequence
HF-Parameter: Capacitance HV-LV,
0-Sequence
Optimal Power Flow Constraints: Max.
Loading
Optimal Power Flow Controls: Tap
Position
Optimal Power Flow Controls:
Optimise
Optimal Power Flow Controls: Control
Mode
Feeder
Distance from infeed in number of
buses
Lateral Index
Distance from first infeed in number of
buses
Distance from infeed in number of
buses including switches
Distance from first infeed in number of
buses including switches
Forced Outage Rate
Forced Outage Expectancy
Forced Outage Duration
Ideal component
Type model
Element model
Failures Double Earth Fault:
Frequency of single earth faults
Failures Double Earth Fault:
Conditional probability of a second
earth fault
Failures Double Earth Fault: Repair
duration
Time-Overcurrent Plot: Frequent Fault
( >10(5)/lifetime, Category II(III) )
Time-Overcurrent Plot: ANSI Curve
Shift
Time-Overcurrent Plot: Draw Inrush
Current
Cg l
Cc1 hl
Cc0 hl
iOPFCload
i uopt
ionlyPre
i uoptCont
cpFeed
ciDist
ciLater
ciDistRoot
ciDistAll
ciDistAllRoot
FOR1
FOE
FOD
iperfect
pTypStoch
pStoch
CCEarFr
CCEarProb
CCEarRepMu
ifrqft
iansish
drawInr
Unit
uF
uF
uF
uF
1/a
h/a
h
StoTyptrf
1/a
%
51
Parameter
Description
fr coldload
coldloadtab2
i uopt
maxload
gnrl modif
gnrl modby
sernum
constr
iComDate
chr name
dat src
for name
doc id
pOwner
pOperator
desc
appr status
appr modif
appr modby
ifc
sOpComment
cimRdfId
dpl1
dpl2
dpl3
dpl4
dpl5
Unit
52
10
10
References
References
[1] Guidelines for representation of network elements when calculating transients. Technical
report, Cigre Working Group 33.02, 1990.
[2] Three phase oil-immersed distribution transformers, 50 hz, from 50 to 2500 kva with highest
voltage for equipment not exceeding 36 kv. Determination of the power rating of a transformer loaded with non-sinusoidal currents, 1995.
[3] IEEE Std c57.110-1998 Recommended Practice for Establishing Transformer Capability,
1999.
[4] Allan Greenwood. Electrical Transients in Power Systems. John Wiley & Sons, 1991.
53
List of Figures
List of Figures
1.1 Positive sequence (per-unit) equivalent circuit of the 2-winding transformer
. . .
1.2 Zero sequence equivalent circuit of a Yd-transformer with HV side tap changer
(a) detailed representation (b) simplified representation . . . . . . . . . . . . . .
. . . . . . . . . . .
20
21
22
23
27
28
29
31
6.1 HF model for (a) external capacitances in the positive sequence system; and (b)
zero sequence system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
34
38
39
7.3 YNzn-transformer (zero sequence system) with HV side tap changer (detailed
representation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
39
40
41
8.1 Input/output definition of 2-winding transformer model for RMS- and EMT-simulation 42
54
List of Tables
List of Tables
1.1 Input- and calculation parameters . . . . . . . . . . . . . . . . . . . . . . . . . . .
13
1.3 Type Basic Data: Zero sequence impedance (no internal delta winding) . . . . .
13
1.4 Type Basic Data: Zero sequence impedance: YN-YN; with internal delta winding
14
17
19
20
21
21
25
28
42
42
8.3 Additional parameters and signals for EMT transformer model (calculation parameters) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
42
55