IS15301:2003
REAFFIRMED

IndianStandard
INSTALLATIONANDMAINTENANCEOF
FIREFIGHTINGPUMPSCODEOF
PRACTICE
ICS13.220.10
BIS2003
BUREAUOFINDIANSTANDARDS
MANAKBHAVAN,9BAHADURSHAHZAFARMARG
NEWDELHI110002
April2003
PriceGroup4
i

FireFightingSectionalCommittee,CED22

FOREWORD
ThisIndianStandardwasadoptedbytheBureauofIndianStandards,after
thedraftfinalizedbytheFireFightingSectionalCommitteehadbeenapprovedby
theCivilEngineeringDivisionCouncil.
Allbuildingsdependingupontheoccupancyuseandheightareprotectedby
fixedfirefightinginstallationsaspertheprovisionslaiddowninSP7(Part4).The
fixedfirefightinginstallationsareprovidedinmultistoreyedbuildingofheight15
metresoraboveandalsoothercategoriesofbuildingsoflesserheightbutwith
specialrisks/basement,etc.Similarly,allfactories/manufacturingindustriesalsogo
forinstallationoffixedfirefightingsystemforprotectionofthepropertyandlife.
Thesystemmaybeintheformofwetriser,externalhydrantorintheformof
sprinkler/emulsifiers,etc,orallofthem.Themostimportantcomponentinsucha
systemisthefirepump.Acarefullychosenfirepumpofappropriatecapacityand
installedproperlywillformthebackboneofsuchsystem.Evenafterinstallation,it
isabsolutelyessentialthatthefirepumpsareproperlymaintainedandregularly
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html

1/15

3/22/2016

IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE

testedsothattheyareinserviceableconditionandcomeintooperationinstantlyat
thetimeofexergencies.
Therequirementsinregardtotheinstallationandmaintenanceofinternalor
externalfirehydrantsarecoveredinseparateIndianStandards(seeIS3844andIS
13039).
ThecompositionoftheCommitteeresponsibleforformulationofthis
standardisgiveninAnnexA.
Forthepurposeofdecidingwhetheraparticularrequirmentofthisstandard
iscompliedwith,thefinalvalue,observedorcalculated,expressingtheresultofa
testoranalysis,shallberoundedoffinaccordancewithIS2:1960Rulesfor
roundingoffnumericalvalues(revised).Thenumberofsignificantplacesretained
intheroundedoffvalueshouldbethesameasthatofthespecifiedvalueinthis
standard.
IndianStandard
INSTALLATIONANDMAINTENANCEOFFIRE
FIGHTINGPUMPSCODEOFPRACTICE

ii

1SCOPE
Thisstandardlaysdowntherequirementsofinstallationandmaintenanceof
firefightingpumps.

2REFERENCES
Thestandardslistedbelowcontainprovisionswhichthroughreferenceinthis
text,constituteprovisionsofthisstandard.Atthetimeofpublication,theeditions
indicatedwerevalid.Allstandardsaresubjecttorevisionandpartiestoagreements
basedonthisstandardareencouragedtoinvestigatethepossibilityofapplyingthe
mostrecenteditionsofthestandardsindicatedbelow:
ISNo.

Title

1710:

Specificationforverticalturbinepumpsforclear,cold,freshwater(second

1989

revision)

2974

Codeofpracticefordesignandconstructionofmachinefoundations:Part3

(Part3): Foundationsforrotarytypemachines(mediumandhighfrequency)(second
1992

revision)

2974

Codeofpracticefordesignandconstructionofmachinefoundations:Part4

(Part4): Foundationsforrotarytypemachinesoflowfrequency(firstrevision)
1979
3844:

Codeofpracticeforinstallationandmaintenanceofinternalfirehydrantsand

1984

hosereelonpremises

5120:

Technicalrequirementsforrotodynamicspecialpurposepumps(firstrevision)

1977
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html

2/15

3/22/2016

IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE

6070:

Codeofpracticeforselection,operationandmaintenanceoftrailerfirepumps,

1983

portablepumps,watertendersandmotorfireengines(firstrevision)

9137:

Codeforacceptancetestforcentrifugal,mixedflowandaxialpumpsClassC

1978
13039:

ExternalhydrantsystemsProvisionandmaintenanceCodeofpractice

1991
SP7

NationalbuildingcodeofIndia:Part4Fireprotection(firstrevision)

(Part4):
1983

3TERMINOLOGY
Forthepurposeofthisstandard,thefollowingdefinitionsshallapply.

3.1StaticWaterTank
Undergroundorsurfacewatertank,constructedtostorewaterforfire
fightingpurpose.

3.2TerraceTank
Aconcrete/masonry/plastic/steeltankconstructedorerectedonterraceof
buildingforfirefightingpurpose.

3.3PrimingTank
Asmalltankerectedinside/overthepumphouseandabovethefirefighting
pumpstokeepthepumpcasingandsuctionofthefirepumppermanentlyflooded.
Thisisrequiredincaseofnegativesuction.

3.4FootValvecumStrainer
3.4.1
Avalvefixedinthesuctionstrainerofthefirepumpwhichopensonly
inwardstoallowinflowofwaterintothepumpsuctionandfirepumpwhenthe
pumpisactuatedautomatically/manually,ThisisrequiredincaseofNegative
suction.
3.4.2
Inapositive(flooded)suction,astrainerplacedinthesuctionlinebetween
thefiretankandfirepumptoarrestanydirt/obstructionbeingfedintothepump
suction.

https://law.resource.org/pub/in/bis/S03/is.15301.2003.html

3/15

3/22/2016

IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE

3.5JockeyPump
Apumpofsmallcapacitywhichissettocomeintooperationautomatically
withdropinstaticpressureinthesystemandtoautomaticallystopwhenthepreset
pressureisreachedagain.

3.6TerracePump
Anelectricallydrivenpump,locatedontheterraceconnectedtoaterrace
tankwithgatevalveonsuctionsideandtotheinternalhydrantsystemwithnon
returnvalveondeliveryside.

3.7FirePump
Anelectric/dieselpumpinstalledatstaticwatertanktochargethewetriser
systems/sprinklersystem,etc.
1

3.8StandbyPump
Apumpofsamecapacityasfirepump,drivenbyadieselengineorconnected
toanyotheralternatesourceofelectricsupply.

3.9PumpPanel
Panelcomprisingstarting,stoppingandindicatingdevicesoffirepumps.

3.10PressureSwitch
Aswitchconnectedondeliverylineoffirepump,orinthebodyofhydro
pneumatictankatpresetpressurelevelsodesignedtoautomaticallystartthefire
pumporjockeypump,asthecasemaybe,whenthepressureinthesystemfalls
belowthepresetlevel.

3.11CirculationReliefValve
Thecirculationreliefvalveputinbelowtheshutoffpressuretoprovide
circulationandtherebyrelievetheextrapressureinthepump.

4FIREPUMPSANDPUMPHOUSE
4.1
Thepumphouseshouldbelocatedpreferablyoutsidethebuildingwitha
minimumclearanceof6mfromadjoiningbuildings.Thepumphouseshouldhave
adequatenaturalventilationwithwindows,fittedwithexpandedmetalfor
protection.Inordertofacilitateproperinstallationandmaintenanceoffirefighting
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html

4/15

3/22/2016

IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE

pumps,thereshouldbeprovisionofmildsteelgirderofappropriatexsectionat
suitableheightinpumphouseforfixingchainpulleyblock.

4.2
Ifthepumphousehasadieselpump,theexhaustpipeofthedieselengine
shouldbeextendedtooutsidethepumphouseandexhaustdischargedatan
appropriateheightintheopenair.

4.3
Thefloorofthepumphouseshouldbeslopedtothefarthestendtodrain
awayanywaterleakingfromglands,valves,etc.

4.4
Thepumphouseshouldhavenormallighting,andalsoemergencylighting
facility,eitherfromasecondsourceorfromthegenerator.

4.5
Ifthepumphouseislocatedinsidethebuilding,eitherongroundfloororin
thebasement,itshouldbeseparatedfromtherestportionwithawallhaving2hfire
ratingandfirecheckdooratitsentrancehaving1hfirerating.Forpumphousein
basement,forcedmechanicalventilationshouldbeprovided.Pumphouseinground
floorshouldbelocatedonperipheryofbuildingwithaccessdirectlyfrom
outside/openarea.Thepumphouselocatedinthebasementshouldalsohaveeasy
accessibilityfromoutsidepreferablythroughramp.

5ARRANGEMENTOFPUMPS
5.1
Thelayoutplansofpumpsinstalledandfirewaterlinesshouldbedisplayed.
Thepumphouseshouldbeofadequatedimensiontohouseallthepumpswith
suction,deliverypipes,fittingsandstartercontrolpanel,airvessel,etc,with
adequatecirculationarea.Adequateheadroomclearanceallaroundthepumpfor
maintenanceshallbemadeavailable.Aminimumclearanceof1matfrontandback
and0.75monsidesandbetweenpumpsshouldbeprovidedforallmajorpumps
exceeding22801/mincapacity.Forsmallerpumps,includingjockeypumps,the
clearancerequiredshouldbe0.75matfrontandbackand0.60matsidesand
betweenpumps.Theheadroomclearanceforallpumphousesshouldbeminimum
2.75m.

5.2

https://law.resource.org/pub/in/bis/S03/is.15301.2003.html

5/15

3/22/2016

IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE

Thepumpcontrolpanelwhichshouldalsobehousedinthepumproombut
easilyaccessible,shouldbeofadequatedimensiontoincorporatetripplepooland
neutral(TPN)switchandhighrupturecapacity(HRC)switchbothofadequate
capacity,selectorswitchammeter,voltmeterandphaseindicatinglights,single
phasepreventer,startandstoppushbuttons,automanualswitch,auxiliary
contractorsforinterlocking/sequenceofoperationsandallnecessarygauges,fittings
requiredtocompletethesystem(thebusbarshouldbeofcopperofappropriate
thickness).Thepanelshouldbefloormountedwithpropergroutingwiththefloor
andbecompartmentalized.Thegaugethicknessofpanelshouldbe1.8mm.

5.3
Wheredieselpumpisprovided,itshouldhaveaseparatepanel,alsolocatedin
thesamepumproomoradjoiningseparateroom.Thepanelshouldhaveitsseparate
battery,withbatterychargingdevice,andautomanualchangeoverarrangement.It
shouldincorporateaninterlockingdevicewiththemainpumppanelsothatboth
theelectricpumpandthedieselpumpdonotoperatesimultaneously.Adequate
precautionshouldbetakentoavoidspillageofdieseltoavoidanyfireexergency.

5.4
Airvesselofadequatecapacityshouldbeinstalledinthepumphouse,with
pressureswitchesincorporatedonthedeliveryline.Thereshouldbetwopressure
switchesonewithupperandlowerlimitforjockeypumpandanotheronewith
onlyforlowerpressurelimitforthemainpump.Stoppingofmainpumpsshouldbe
onlybymanualpushbuttonwhichshouldbeprominentlyindicatedonthepump
panel.

5.5
Similarlowerpressurelimitswitchshouldalsobeincorporatedinthediesel
pumptomakethestartautomaticallyatpresetdropinpressure.

6INSTALLATIONOFFIREPUMPS
6.1
Thecapacityofthefirepumpshouldbecarefullychosentomeetthe
maximumrequirementfortherisk
2

tobeprotected.Thefirepumpshavebeendividedintothefollowing
capacities:
a.4501/min,
b.9001/min,
c.22801/min,

https://law.resource.org/pub/in/bis/S03/is.15301.2003.html

6/15

3/22/2016

IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE

d.28501/min,and
e.45001/minandforspecialrisks67001/min.
Oftheabove,(a)and(b)arebasicallythepumpstobeinstalledontheterrace
tofeedtheDownComerSystem.Theotherpumpsaretobehousedinthepump
house.Thepumphousemaybebelowthelevelofthewatertankorconstructed
abovethewatertankdependingupontheengineeringconveniences.Forfire
fightingpurpose,apumphousehavingthepumpsbelowthewatertankisalways
desirable,asthiseliminatesthenecessitytohavenegativesuctionincorporating
primingtank,footvalveandotherextravalves,etc.Allpumpsarerequiredtobe
startonAuto,whenthereisadropofpressureinthemains.Thesearerequiredto
bepresetonpredeterminedpressuresuitabletoparticularrisk.

6.2
Ifthepumpiselectricdriven,thecapacityofthepumpvisvisits
revolutionsperminutemustmatchwiththeelectricmotorbeingchosenforthe
samejob.Electricmotorsrequiredtofeedthepumpupto22801/minareusually
runningat2900rev/minandthepumpsrequiredtomatchthemotorsmustalso
runatthesamerevolutionsperminute.ThesepumpsareknownasSingleStage
PumpsandthesuctionisattheendofthepumpsothatthesearecalledEnd
SuctionPumps.Smallcapacitypumps/jockeypumpsarealsoavailable/requiredtobe
usedinmultistagedesign.Thespeedsofthesepumpsaresuitablefor2polemotor
or4polemotor.

6.3
Thefirefightingpumpsarealmostinvariablycentrifugaltypeexceptingin
sometypicalcaseswhereverticalturbineorsubmersiblepumpsareinstalled.After
thecapacityofthepumpandmotorhasbeencarefullychosen,tomatcheachother
perfectly,installationofthepumpsinthepumphouseshouldbedonewithutmost
care.Ashasbeensaidabove,thepumphouseshallhaveadequatespacestokeep
enoughcirculationareawithinthepumphouseforthepumpoperatorintimesof
emergencyormaintenance.Thepumpandthemotorsarealwayscasesconnected
togetherbyconnectingcouplersandtheyaremountedonacommonbaseplate
whichissuppliedbythepumpmanufacturersalongwiththepump.Thebaseplate
shallbeofsufficientlengthandwidthtohousethepumpandthemotor
comfortably.

6.4
Inthefirststageoftheinstallation,pumpsaretobemountedonaconcrete
foundationhavingminimumgradeofreinforcedconcreteasM15.Thefoundation
shallbeofadequatethicknessanddimensiondependinguponthetypeofthepump
whichwillbeinstalled.Thethicknessofthefoundationshallbe50mmminimum
forsmallpumpsupto9001/mincapacity,75mmforpumpsupto22801/min
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html

7/15

3/22/2016

IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE

capacityand100mmforbiggerpumpsupto45001/min.Forextraordinarybig
pumps,thethicknessmaygoupto150mm.Thesizeofthefoundationshallcover
thefulllengthandwidthofthepumpandatleast150mmonthefrontandbackof
thepumpand75mmonthesidesasclearance.Thefoundationshallbedesignedas
perIS2974(Part3)andIS2974(Part4).

6.5
Itisrecommendedtoprovideajockeypumptotakecareofsystemlosses.The
capacityofthejockeypumpshallneitherbelessthan3percent(withaminimumof
1801/min)normorethan10percentoftheinstalledpumpingcapacity.

6.6
Eachpumpshallbeprovidedwithapressuregaugeonthedeliveryside
betweenthepumpandthenonreturnvalveandamanufacturersplateindicatingthe
deliveryhead,capacityandthenumberofrevolutionsperminute.

6.7
Pumps(otherthanJockeypumps)shouldbeabletodevelopheadofgreater
than65percentofratedheadatcapacityof150percentofratedcapacity.Therated
headforverticalturbinepumpswillberatedbowlhead.Theshutoffheadofpumps
(otherthanjockey)shouldnotexceed120percentofratedheadforhorizontal
pumpsand140percentofratedbowlheadofverticalturbinepumps.

6.8
Eachfireservicepumpshallbeprovidedwithanindependentsuctionpipe
withoutanysluiceorcutoffvalvestherein,unlessthepumpissituatedbelowthe
levelofthewatersupplyinwhichcasesluiceorcutoffvalvesisessential.Wherethe
NetPositiveSuctionHead(NPSH)availableatsiteislessthan0.5minexcessofthe
actualvaluerequiredat150percentofthedutypointasperthemanufacturers
curvesorwherethewatersupplyhasfibrousorequallyobjectionablematterin
suspensionormudand/orsandliabletocausedepositionintheinstallation,suction
pipe(s)shallbeinstalledinajackwell(suctiontank),fedthroughapipe/pipesof
appropriatediafromthemainwatersupply.Atthesupplyendofthemajortank,
wherethemainsupplysourceisatadistanceexceeding20m,asluiceorgatevalve
shallbeprovided.Fromfirewaterstoragereservoirtwoseparateconnectionsare
takentosuctionheader(fromeachcompartmentoffirewaterstorage.)

6.9
Thediameterofthesuctionpipeshallbesuchthattherateofflowofwater
throughitdoesnotexceed1.5m/swhenthepumpisdeliveringatitsrated
discharge.If,however,thepumpissituatedbelowthelevelofitswatersupply,the
diameterofthesuctionpipe/headershallbebaseduponarateofflowof2m/s.
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html

8/15

3/22/2016

IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE

6.10
Whenthepumpisabovethelevelofitswatersupply,thereshallbeafoot
valveandaprimingarrangement,thelatterconsistingofatank(havingacapacity
atleastthreetimesthatofthesuctionpipeincludingthepumpcasingfromthepump
tothefootvalve),connectedtothedeliverysideofthepumpbyametalpipehaving
aminimuminternaldiameterof100mminthecaseofcentrifugalpumpswitha
stopvalveandanonreturnvalvethereinofthesamesize.Adependable
independentfillingarrangementandalevelindicatorshallbeprovidedforthe
primingtank.Theprovisionofavacuumgaugeforthesuctionpipeisrecommended.
Wherecircumstancespermit,centrifugalpumpsshallbefixedpreferablybelowthe
levelofthewatersupply.Ifthepumpisautomaticinaction,itshallnecessarilybeso
fixed.

6.11
However,forlightandordinaryhazardoccupanciesifthepriming
arrangementsaresuchastoensurethatthesuctionpipeshallbeautomatically
maintainedfullofwaternotwithstandingaseriousleakagetherefrom(thepump
beingautomaticallybroughtintoactiontoreplenishtheprimingtankshouldthe
latterbedrawnuponatagreaterratethantherateatwhichitisfedfromanyother
source),positivesuctionmaynotbeinsisted.Insuchcases,thecapacityofthe
primingtankneednotexceed4501andthediameteroftheprimingpipeneednot
exceed50mm.Eachpumpshallbeprovidedwithanautomaticbypassconnection
andreliefvalvesetbelowtheshutoffpressure.Itshallprovidecirculationof
sufficientwatertopreventthepumpfromoverheatingwhenoperatingwithclosed
deliveryandnodischarge.Thecirculationreliefvalveshoulddischarge
approximately35percentofthepumprating.
TestLineEachpumpshallbeprovidedwithtestlineandshutoffvalvefor
individualtestingofpumpswithoutdischargingthesystem.

6.12
Pumpsshallnotbeinstalledintheopen.Thepumproomshallbesolocated
astobebotheasilyaccessibleandwhereanyfallingmasonryandthelikefromother
buildingsoccasionedbyfireorothercause,cannotdamagethepumproom.
Normally,pumproomsshallbelocated6mawayfromallsurroundingbuildingsand
overheadstructures.Wherethisisnotfeasible,theymaybeattachedtoabuilding
providedaperfectseperationwallhaving4hfireratingisconstructedbetweenthe
pumproomandtheattachedbuilding,theroofofthepumproomisofRCC
constructionatleast100mmthickandaccesstothepumproomisfromtheoutside.
Thepumproomsshallnormallyhavebrick/concretewallsandnoncombustible
roofwithadequatelighting,ventilationanddrainagearrangements.

6.13
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html

9/15

3/22/2016

IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE

Thesubstation(s)and/orD.G.House(s)supplyingpowertothefirepump(s)
shallbeofincombustibleconstructionandshallbelocatedatleast6mawayfromall
surroundingbuildings.Wherethisisnotfeasible,alldoorandwindowopeningsof
thesurroundingbuildingswithin6mofthesubstation(s)and/orD.G.House(s)
shallbeprotectedbysinglefireproofdoorsand6mmthickwiredglassesinsteel
frameworkrespectively.Likewise,roofeaves,ifanyofthesurroundingbuildings
fallingwithin6mofthesubstation(s)and/orD.G.House(s),shallbecutandwall
raisedasaparapet.Theaboveprovisionsshallalsoapplywhenthesubstation(s)and
D.G.House(s)arewithin6mofeachother.
Wherethesubstation(s)andD.G.House(s)areattachedtobuildings,afour
hourratedwallshallbeconstructedtosegregatethesubstation(s)andD.G.
House(s).ThisshallbeofRCCconstructionatleast200mmthickorofmasonry
constructionatleast230mmthick.

6.14
TransformercubiclesinsidethesubstationsshallbeseparatedfromH.T.and
L.T.cubiclesandfromeachotherbywallsofbrick/stone/concreteblocksor355
mmthicknessorofRCCof200mmthicknesswithdooropenings,ifany,therein
beingprotectedbysinglefireproofdoorshaving2hourfireresistance.Thesub
station(s)and/orD.G.House(s)shallalsobeseperatedfromeachotherasabove.
Transformersinstalledoutdoors,whicharesupplyingpowertofirepump(s)shall
alsobelocatedatleast6mawayfromallsurroundingbuildings[includingsub
station(s)and/orD.G.House(s)].Wherethisisnotfeasible,alldoorandwindow
openingsofthebuilding(s)[includingsubstation(s)and/orD.G.House(s)within6
mofthetransformers]shallbeprotectedbysinglefireproofdoorsand6mmthick
wiredglassesinsteelframeworkrespectively.Likewise,roofeavesofthebuilding(s)
fallingwithin6mofthetransformersshallbecutandwallraisedasaparapet.Blast
wallsofbricks/stone/concreteblocksof355mmthicknessorofRCCof200mm
thicknessshallbeconstructedbetweentransformersandthesewallsshallbe
extendedhorizontally600mmbeyondtheextremitiesofthetransformersand
vertically600mmabovethehighestpointofthetransformers.

6.15
Theelectricsupplytothepumpset(s)shallbeentirelyindependentofall
otherequipmentinthepremises,thatis,evenwhenthepowerthroughoutthe
entirepremisesisswitchedoff,thesupplyofthepumpshallcontinuetobeavailable
uninterrupted.Thiscanbeachievedbytakingtheconnectionforthepump(s)from
theincomingsideofthemainL.T.Breaker.However,incaseswheretwoormore
transformersand/orsourcesofsupplyareconnectedtoacommonbusbarorwhere
thereisprovisionofa
4

buscouplerbetweenthebusbarsections,theconnectionmaybetaken
throughthebusbars.

6.16FireExtinguisher
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html

10/15

3/22/2016

IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE

Thepumproomshouldbeprotectedbyappropriatetypeofextinguishers
eitherC02orDCP.Ifthepumpsareinbasement,itisdesirabletohavethepumps
protectedbyautomaticsprinklersystem.

7MAINTENANCE
7.1
Thefirepumpshallbemaintainedregularlyandproperly.Therefore,itis
absolutelyessentialthatsomeoneresponsiblepersonshouldbegiventhechargeof
ensuringthatthefirepumpsareproperlymaintained.

7.2
Thefollowingmaintenancescheduleshallbemaintained.
7.2.1
Afterthefirefightingpumphasbeencommissionedandthesystemhasbeen
takenoverbytestingitaccordingtotheperformanceparameterslaiddownforthe
firepump,thisshouldberecordedinamaintenanceregister,tobekeptinthepump
house.Theinitialtestshouldshowthefollowing:
a.Flowobtainedat7kgf/cm2,
b.Flowobtainedat4.5kgf/cm2(65percentof7kg),and
c.Pressuregaugerecordingat120percentof7kg.

7.3
Afterthisinitialtakeoverofthepump,thefollowingshallbetheroutine
maintenanceschedule.
7.3.1DailyCheck
a.TestingoftheJockeyPump
Testthejockeypumpdailybyopeningthedeliveryvalve/hosereelvery
slightlytoallowthepressuretodropuptothepresetlevel.Notethetiming
takenbythejockeypumptorestorethepressureautomaticallybycutoff
switch.
b.MainPump
Themainpumpshallbetesteddailyatleastfor5min.Releasethe
systempressurebyopeningthehydrantvalvepartially.Thejockeypumpwill
comeinoperation.Openthevalvefullywhenfurtherdropinpressurewhich
willallowthemainpumptostartautomatically.Closethedeliveryoutletand
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html

11/15

3/22/2016

IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE

allowthepumptorunfor5mineverymorning.
c.Checkthepumpglands,packings,etc,andreplacethedamagedglandfor
packingwheneverfounddamagedorwornout.
7.3.2WeeklyCheck
a.Checkbearingsgreasecutonceaweekandlubricateasneeded.
b.Cleaningofstartercontactseveryweek.
c.Checktheinsulationresistanceofpumpmotorcircuiteveryweek.
d.Checktheenginefueloiltankandensurethatthisisofappropriategradeand
quality.
e.Checkthequantityoffueloilinthetank.Thisshouldbesufficientfor4h
runningwithoutreplenishment.Checkthesludgeandsedimenttrapas
providedintheauxiliaryequipmentlist.Checktheinspectionandcleaning
hole,checkthebattery/batteriesrequiredforstartingoftheengineandensure
thattheseareinsatisfactorycondition.Alsocheckthebatterycharging
arrangementbytrickiercharger.
Foreverycoldareas,spaceheatingisnecessarytokeeptheenginein
reasonablywarmconditionforimmediatestarting,Ifso,ensurethattheroom
heatingarrangementisworkingsatisfactory.
f.Startingdieselengineonceeveryweekandrunitfor10min.Thestarting
shouldbetestedbyswitchingoffthecurrentandallowingsystempressureto
dropuptothepresetlevelfordieselengine.Interlockarrangementwith
powersupplyshouldberestored.
g.Checkalignmentofpumpmotors,nuts,bolts,couplings,couplingguard,etc,
onceeveryweekafterthepumphasrunforcontinuous15min.
7.3.3
InspectionshallbecarriedoutaspertherequirementsgiveninIS1710,IS
5120,IS6070andIS9137.

7.4
Manufacturersshallprovidealistoffastmovingspares.
5

ANNEXA
COMMITTEECOMPOSITION
(Foreword)
FireFightingSectionalCommittee,CED22
Organization
MinistryoilHomeAffairs,NewDelhi

https://law.resource.org/pub/in/bis/S03/is.15301.2003.html

Representative(s)
ShriOmPrakash(Chairman)
12/15

3/22/2016

IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE

ShriD.K.Shami(Alternate)
AirportAuthorityofIndia,NewDelhi

ShriL.C.Gupta
ShriH.S.Rawat(Alternate)

AndhraPradeshFireServices,Hyderabad ShriSwaranjitSen
BhabhaAtomicResearchCentre,

ChiefFireOfficer

Mumbai
BombayFireBrigade,Mumbai

ChiefFireOfficer
ShriG.S.Sawant(Alternate)

CentralBuildingResearchInstitute,

DrT.P.Sharma

Roorkee
DrA.K.Gupta(Alternate)
CentralIndustrialSecurityForce,New

DeputyInspectorGeneral(Fire)

Delhi
ShriS.L.Nagarkar(Alternate)
CentralPublicWorksDepartment,New

ChiefEngineer(E)

Delhi
CentreforEnvironmentandExplosive

ShriA.K.Kapoor

Safety,Delhi
ShriH.S.Kaparwan(Alternate)
ConcordAraiPvtLimited,Chennai

ShriR.Ramakrishnan

ControllerateofQualityAssurance(Fire), ColG.P.Krishnamurthy
Pune
DefenceResearchandDevelopment

Director(FireSafety)

Organization,Delhi
DeputyDirector(FireSafety)(Alternate)
DelhiFireService,NewDelhi

ShriR.C.Sharma
ShriSurinderKumar(Alternate)

DirectorateGeneralofSuppliesand

ShriM.Gangaraju

Disposals,Hyderabad
ShriV.K.Verma(Alternate)
EngineerinChiefsBranch,NewDelhi

ShriR.A.Dubey
ShriAjayShankar(Alternate)

FireandSafetyAppliancesCompany,

ShriS.N.Kundu

Kolkata
HomeDepartment(FireService),

Director

Chennai
DeputyDirector(Alternate)
InstitutionoffireEngineers(India),New President
Delhi
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html

13/15

3/22/2016

IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE

GeneralSecretary(Alternate)
KooverjiDevshi&Co(P)Limited,

ShriP.H.Sethna

Mumbai
ShriN.T.Panjwani(Alternate)
K.V.FireChemicals,NaviMumbai

ShriH.M.Sabadra

LossPreventionAssociationofIndia,

ManagingDirector

Mumbai
ShriD.K.Sarkar(Alternate)
MatherandPlatt(India)Limited,New

ShriDeepakAgarwal

Delhi
MECONLimited,Ranchi

ShriR.N.Chachra
ShriSunilDas(Alternate)

NewageIndustries,Mumbai

ShriB.J.Shah
ShriA.M.Shah(Alternate)

NorthernRailway,NewDelhi

ShriI.M.Mansoori

OilandNaturalGasCommission,Dehra ShriR.P.Saxena
Dun
ShriNeerajSharma(Alternate)
OilIndustrySafetyDirectorate,New

JointDirector(Process)

Delhi
RealValueAppliancesLimited,New

ShriAshutoshMangal

Delhi
SafexFireServicesLimited,Mumbai

ShriJitendraShah
ShriSandipShah(Alternate)

StateBankofIndia,Mumbai

ShriJ.S.Gahlaut

StateFireTrainingCentre,Mumbai

DrNavinchandraJain

SteelAuthorityofIndia,Rourkela

ShriB.N.Das
ShriB.P.Das(Alternate)

SteelAuthorityofIndia,Bokaro

ShriA.Rautela
ShriC.P.Singh(Alternate)

SteelageIndustriesLimited,NewDelhi

ChiefExecutive
ShriV.Kamalanatha(Alternate)

SurexProductionandSales(P)Limited,

ShriTaritSur

Kolkata
ShriD.Neogi(Alternate)
TariffAdvisoryCommittee,Mumbai

ShriT.R.A.Krishnan

TariffAdvisoryCommittee,Chennai

ShriA.Mukherjee
ShriH.C.MaheshKumar(Alternate)

VijayFireProtectionSystemsPvt
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html

ShriHarishSalot
14/15

3/22/2016

IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE

Limited,Mumbai
WestBengalFireService,Kolkata

ShriB.Pahak

Inpersonalcapacity(33/2965A,

ShriG.B.Menon

VennalaHighSchool,Vennala,Cochin)
Inpersonalcapacity(29/25,Rajendra

ShriS.K.Dheri

Nagar,NewDelhi)
BISDirectorateGeneral

ShriS.K.Jain,Director&Head(CivEngg)
[RepresentingDirectorGeneral(ExOfficio)]

MemberSecretary
ShriS.Chaturvedi
JointDirector(CivEngg),BIS
8
7

https://law.resource.org/pub/in/bis/S03/is.15301.2003.html

15/15