FSSS
The Furnace Safeguard Supervisory
System (FSSS) is designed to ensure
the execution of a safe, orderly
operating sequence in the start up and
shutdown of fuel firing equipment.
The FSSS shall be designed to perform
the following functions Prevent
fuel
firing
unless
a
satisfactory furnace purge has been
completed.
Prevent start-up of the fuel firing
equipment unless certain permissive &
interlocks have been completed.
3/25/16
FSSS
Monitor and control the correct
component sequencing during startup and shut-down of the equipment.
Provide
component
condition
feedback to the operator .
Provide flame supervision when fuel
firing equipment is in service and
effect of fuel trip upon certain
unacceptable firing conditions.
Initiate a MFT of Unit when a certain
abnormal operating conditions exist.
3/25/16
FSSS
The following operational functions are
included in FSSS Furnace purge supervision.
FSSS
FURNACE PURGE-
PURGE PERMISSIVES
All HONVs and HOTV Closed
Press
purg
e PB
DELAY
300
SEC
MFT
RESE
T
PURGE
COMPL
ETE
FSSS
FURNACE PURGEWhen the furnace purge cycle is started by the
operator, by pressing PURGE START push
button, a five minutes purge timer is energized as
indicated by the PURGING" light coming on.
At the end of the five minutes, the boiler trip
circuit is reset, provided no boiler trip command is
present. The "PURGING" light goes out and yellow
PURGE COMPLETE light comes on. Once the
Boiler trip circuit is reset (on purging complete),
the close circuits of H.O. trip valve and L.O. trip
valve are de-energised permitting the operator to
open it as described below 3/25/16
HOTV
3/25/16
No MFT
HFO Header temperature satisfactory
HFO supply pressure adequate
All HONVs closed
Atomising steam pressure adequate
HORV open
Unit 24V DC Power supply available
3/25/16
AND
OR
OR
3/25/16
10
Before any main fuel can be fired the heavy oil must be
brought to proper temperature.
This is accomplished by recirculating H.O. through the oil
recirculation system by means opening of the H.O.T.V and
H.O. recirculation valves (HORV) .
FSSS permits the opening of HOTV for oil recirculation
purpose following a boiler trip and prior to starting a
furnace purge cycle as follows:
1) Depressing the "H.O. recirculation valve open push button"
will Open the Recirculation valve (long), provided all the
H.O. nozzle valves are fully closed.
2) When the H.O.R.V. is fully open as indicated by the HORV
open light (red) being on, depress the "H.O.T.V. open push
button". This will start the H.O. recirculation .
3/25/16
11
LOTV
3/25/16
12
13
3/25/16
14
FSS
LIGHT OIL PAIR MODE START
S ( ELEVATION AB )
FSSS
H O PAIR MODE START ( ELEVATION
AB ,CD &EF)
FSSS
ELEVATION MODE START UP
FSS
PAIR
S -MODE SHUTDOWN
3/25/16
18
FSS
S-
BOWL MILL
3/25/16
20
BOWL MILL
3/25/16
21
N
D
For Mill B
O
R
For Mill C
CD elevation 3/4 HONVs proven open
O
R
For Mill D
CD elevation 3 / 4 HONVs proven open
O
Boiler load > 30 % and either Feeder- C or Feeder- E proven with >50% loading
For Mill E
EF elevation 3/4 HONVs proven open
O
R
For Mill F
O
3/25/16
23
FSSS
PULVERIZER START
O
R
Electrical Trip.
When one PA fan or one FD fan trips and three or more pulverizers
are in service, each pulverizer with a 2 sec time delay a trip
3/25/16
command will be given starting from the top most elevation, until
the number of pulverizers remaining in service is reduced to
25
A
N
D
Feeder in Remote
Pulveriser ignition permit available
No MFT
Pulveriser ON
Feeder SAV open
Feeder O/L gate open
3/25/16
26
3/25/16
27
Both ID Fans Off 2/3 hardwire contact for each fans from HT SWGR
Both FD Fans Off - 2/3 hardwire contact for each fans from HT SWGR
O
R
3/25/16
Loss Of All Fuel (Arming any HO/LO nozzle valves not closed.)
FSSS
BOILER
TRIPS
When the Boiler trips the following
events takes place .Boiler trip red
lamp comes on.
MFT A ,B & C trip lamp comes on and reset lamp goes off.
Cause of trip memory can not be reset till the furnace
purge is completed.
F D Fans Control is transferred to manual.
I D fans vane position is transferred to manual.
Pulverizers and coal feeders are tripped.
P A Fans are tripped.
HFO & LDO trip valve closes.
All HFO Nozzle valves closes.
Auxiliary air damper opens and control is transferred to
manual.
S/H and R/H spray block valves closes and can not be
opened unless furnace purge is completed.
Turbine Trips
FSS
BOILER TRIP PROTECTION
S - LOSS OF ALL FUEL TRIP
THE LOSS OF ALL FUEL TRIP CIRCUIT BECOMES ARMED ONCE
ANY ONE NOZZLE VALVES LIFTS FROM CLOSED POSITION IN
ANY ELEVATION.
ONCE THE TRIP CIRCUIT IS ARMED, LOSS OF FUEL TRIP WILL
OCCUR,IFALL FEEDERS ARE OFF.
AND
LOTV/HOTV IS NOT OPEN. OR ALL ELEVATION LONV /HONV
CLOSED.
FSSS
BOILER TRIP PROTECTION
12- UNIT FLAME FAILURE TRIP
RUNNING COAL ELEVATION ADJACENT FIRE
BALL SCANNER ARE NOT SHOWING
2/4FLAME & IT IS NOT SUPPORTED BY
3/4 OIL GUNS THEN THESE ELEVATION NO
FLAME OR FLAME FAILURE OCCURED.
IF THESE CONDITION OCCURED IN ALL
ELEVATION THEN UNIT FLAME FAILURE.
FSSS
BOILER TRIP CONDITIONS
ANY FEEDER PROVEN (FEEDER ON >50 SEC.)
GENERATOR CB CLOSE
ANY HPCV & HPBP < 2 %
ANY IPCV & LPBP < 2 %
FSSS
SCANNER AIR FAN
CONTROL
Scanner fan A
- or B can be started manually by
FSSS
-
3/25/16
35
FSSS
SEAL AIR FAN CONTROL
:-
There are two seal air fans that serve air for mill and
feeder sealing, one working and one standby.
Any seal air fan can be started manually by depressing its
START PB. This action gives start command to the motor.
The seal air fan which is not in service is started on Auto
command if, Any PA fan is on .AND. Seal air header to cold
PA header DP is low for > 10 secs
The seal air fan A will start automatically 5 sec. after the
seal air fan B trips or fails to start on receiving start
command (SA fan B starts automatically if SA fan A
fails to start).
Any seal air fan can be stopped by depressing its STOP
PB, provided the following conditions are satisfied.
Seal Air Header / Cold Air duct DP not low
.AND.
Both Seal Air fans on
Both Seal Air Fans are tripped once Both PA Fans are off >
15 Secs .
FSSS
-
3/25/16
37
FSSS
-
SADC
3/25/16
38
FSSS
-
FUNCTION
39
All elevations of the aux. air dampers will be automatically switched to modulation
control and then commanded to open 100%, if any one of the following conditions
exist.
Also the auxiliary air control loop is tripped to manual if any of the following
conditions exist.
When the auxiliary air control is placed in the Auto mode of operation , the
auxiliary air dampers modulate to control wind box to furnace differential pressure
at a predetermined set point.
During the furnace purge cycle, all auxiliary air dampers modulate to maintain
windbox to furnace differential pressure at a predetermined set point.
When the unit load exceeds 30% of MCR, the following events occurs :
The wind box to furnace differential set point is gradually increased as the unit
load is increased. Conversely, the differential pressure set point is gradually
decreased as unit load is decreased.
The rate of increase (or decrease) is controlled by the auxiliary damper
controller.
The wind-box to furnace differential pressure set point reverts to its original
value during putting in auto.
When the Post Trip Purge Time Expired command is established and all FD / ID
fans are not off and a Master fuel trip command doesnt exist, then a 35 40
3/25/16
seconds counting period is started. After it expires, the Open All Auxiliary Air
41
42
3/25/16
43
MODULATION OF OFA
DAMPERS
3/25/16
44