t(d)
k
13.5
80
0.14
120
Selected Descrinimation
=
180 msec
Notes:
1)
100 msec descrinimation has been considered between series feeders
2)
100 msec descrimination has been considered between the transformer primary and secondar
75 msec
28 msec
20 msec
25 msec
30 msec
178 msec
1
2
0.02
1
Primary load current for plug setting has been considered as follows,
= 110% of Transformer Secondary current (Switchboard contains Transformer Incomer)
= 105% of connected load current (Bus coupler)
= 80% of starting current of the motor
= 120% of Transformer Primary current (Switchboard contains Transformer outgoing)
= 110% of connected load current (Switchboard contains feeder incomer)
Feeder description
Feeder type
Voltage
grade
6.6
HV
ABB
1250
10227.05
894.66
984.13
Relay type
Actual
load
Starting
Primary load
current of Connected
current for plug
largest load current
setting
motor
Voltage
level
FLC of
largest
motor
Non-TFR
A
A
A
A
HSWG-034-D301-IN01 (6.6kV
SWITCHGEAR INCOMER 01)
Non-TFR
6.6
HV
RET620
1250
10227.05
894.66
984.13
HSWG-034-D301-BT01 (6.6kV
SWITCHGEAR BUS COUPLER 01)
Non-TFR
6.6
HV
RET620
1250
10227.05
894.66
939.39
Outgoing to TF-034-23DN01A/B
Transformer
6.6
HV
REF615
400
2000
0.00
0.00
174.96
192.46
Outgoing to TF-034-23DN02A/B
Transformer
6.6
HV
REF615
400
3700
0.00
0.00
323.68
356.04
Outgoing to TF-034-23DN03A/B
Transformer
6.6
HV
REF615
400
3700
0.00
0.00
323.68
356.04
k
13.5
80
0.14
120
Selected Descrinimation
=
180 msec
Notes:
1)
100 msec descrinimation has been considered between series feeders
2)
100 msec descrimination has been considered between the transformer primary and secondar
75 msec
28 msec
20 msec
25 msec
30 msec
178 msec
1
2
0.02
1
Primary load current for plug setting has been considered as follows,
= 110% of Transformer Secondary current (Switchboard contains Transformer Incomer)
= 105% of connected load current (Bus coupler)
= 80% of starting current of the motor
= 120% of Transformer Primary current (Switchboard contains Transformer outgoing)
= 110% of connected load current (Switchboard contains feeder incomer)
Feeder description
Feeder type
Voltage
level
Voltage
grade
Relay type
Actual
load
FLC of
largest
motor
Starting
Primary load
current of Connected
current for plug
largest load current
setting
motor
LSWG-034-N301(440V SWITCHGEAR
Maximum Sym.3-phase faul (I"k):
Minimum Sym.3-phase faul (I"k):
Maximum Ground fault:
Minimum Ground fault:
AT SS#023)
50110
30830
48290
32230
Transformer
0.44
LV
REF615
3150
2000
0.00
0.00
2624.40
3018.06
Non-TFR
0.44
LV
REF615
3150
2000
0.00
0.00
2624.40
2886.84
Outgoing to MCC-034-N301
Non-TFR
0.44
LV
REF615
630
110.06
0.00
0.00
144.42
202.19
Outgoing to MCC-034-N302
Non-TFR
0.44
LV
REF615
630
108.71
0.00
0.00
142.65
199.71
Outgoing to DB-034-N301
Non-TFR
0.44
LV
REF615
1250
486.14
0.00
0.00
637.91
956.87
A
A
A
A
k
13.5
80
0.14
120
Selected Descrinimation
=
180 msec
Notes:
1)
100 msec descrinimation has been considered between series feeders
2)
100 msec descrimination has been considered between the transformer primary and secondar
75 msec
28 msec
20 msec
25 msec
30 msec
178 msec
1
2
0.02
1
Primary load current for plug setting has been considered as follows,
= 110% of Transformer Secondary current (Switchboard contains Transformer Incomer)
= 105% of connected load current (Bus coupler)
= 80% of starting current of the motor
= 120% of Transformer Primary current (Switchboard contains Transformer outgoing)
= 110% of connected load current (Switchboard contains feeder incomer)
Feeder description
Outgoing to DB-034-N302
Feeder type
Non-TFR
HE-34-01-CP01/02/03/04
Non-TFR
Voltage
level
Voltage
grade
0.44
LV
Relay type
Actual
load
FLC of
largest
motor
Starting
Primary load
current of Connected
current for plug
largest load current
setting
motor
REF615
1250
479.53
0.00
0.00
629.24
943.86
REF615
3150
3700
0.00
0.00
3096.03
3150.00
panel AT SS#024)
A
A
A
A
0.69
LV
If
nd secondary
Actual fault
current
CT (sec)
CT (pri)
Calculated
Plug setting
Selected
Plug
setting
Down
stream
relay
operating
time
0.79
0.79
0.86
0.10
0.96
IEC Standard
inverse
988
0.79
0.79
0.69
0.180
0.87
IEC Standard
inverse
988
0.75
0.79
0.51
0.180
0.69
IEC Standard
inverse
0.5
0.50
0.41
0.100
0.51
0.89
0.89
0.11
0.180
0.89
0.89
0.11
0.180
Discrimination
time
Desired
operation
time
Phase over
current
@ LV
Fault
current
in
Reflected
relay
coil
(If)
fault current
PSM
Operating
time of
Calculated
the relay
TMS
@ TMS=1
Selected TMS
18000
14.40
18.23
0.02
0.14
2.342
0.410
0.44
23148.0
18.52
23.44
0.02
0.14
2.150
0.404
0.4
988
23148.0
18.52
23.44
0.02
0.14
2.150
0.320
0.32
IEC Standard
inverse
200
50110
3340.7
8.35
16.70
0.02
0.14
2.417
0.209
0.21
0.29
IEC Standard
inverse
356
37930
3965.4
9.91
11.14
0.02
0.14
2.835
0.102
0.1
0.29
IEC Standard
inverse
356
37930
3965.4
9.91
11.14
0.02
0.14
2.835
0.102
0.1
If
nd secondary
Actual fault
current
CT (sec)
CT (pri)
Calculated
Plug setting
Selected
Plug
setting
Down
stream
relay
operating
time
0.96
0.92
0.21
0.180
0.92
0.92
0.05
0.32
0.32
0.32
0.77
Discrimination
time
Desired
operation
time
Fault
current
in
Reflected
relay
coil
(If)
fault current
@ LV
0.39
IEC Standard
inverse
2898
50110
50110.0
15.91
17.29
0.02
0.14
2.387
0.165
0.17
0.180
0.23
IEC Standard
inverse
2898
50110
50110.0
15.91
17.29
0.02
0.14
2.387
0.097
0.09
0.00
0.05
0.05
IEC Standard
inverse
202
50110
50110.0
79.54
248.56
0.02
0.14
1.200
0.042
0.04
0.32
0.00
0.05
0.05
IEC Standard
inverse
202
50110
50110.0
79.54
248.56
0.02
0.14
1.200
0.042
0.04
0.77
0.00
0.05
0.05
IEC Standard
inverse
963
50110
50110.0
40.09
52.06
0.02
0.14
1.702
0.029
0.03
PSM
Operating
time of
Calculated
the relay
TMS
@ TMS=1
Phase over
current
Selected TMS
If
nd secondary
Actual fault
current
CT (sec)
CT (pri)
Calculated
Plug setting
Selected
Plug
setting
Down
stream
relay
operating
time
0.76
0.77
0.00
0.05
1.00
1.00
0.10
0.00
Discrimination
time
Desired
operation
time
Fault
current
in
Reflected
relay
coil
(If)
fault current
@ LV
0.05
IEC Standard
inverse
963
50110
50110.0
40.09
52.06
0.02
0.14
1.702
0.029
0.03
0.10
IEC Standard
inverse
3150
37930.00
37930.00
12.04
12.04
0.02
0.14
2.744
0.036
0.04
PSM
Operating
time of
Calculated
the relay
TMS
@ TMS=1
Phase over
current
Selected TMS
Operating
time
1.03
0.86
0.69
0.51
0.28
0.28
Remarks
Operating
time
0.41
0.21
0.05
0.05
0.05
Remarks
Operating
time
0.05
0.11
Remarks
k
13.5
80
0.14
120
Selected Descrinimation
=
180 msec
Notes:
1)
100 msec descrinimation has been considered between series feeders
2)
100 msec descrimination has been considered between the transformer primary and secondar
75 msec
28 msec
20 msec
25 msec
30 msec
178 msec
1
2
0.02
1
Primary load current for plug setting has been considered as follows,
= 110% of Transformer Secondary current (Switchboard contains Transformer Incomer)
= 105% of connected load current (Bus coupler)
= 80% of starting current of the motor
= 120% of Transformer Primary current (Switchboard contains Transformer outgoing)
= 110% of connected load current (Switchboard contains feeder incomer)
Feeder description
Feeder type
Voltage
grade
6.6
HV
ABB
1250
10227.05
894.66
984.13
Relay type
Actual
load
Starting
Primary load
current of Connected
current for plug
largest load current
setting
motor
Voltage
level
FLC of
largest
motor
Non-TFR
A
A
A
A
HSWG-034-D301-IN01 (6.6kV
SWITCHGEAR INCOMER 01)
Non-TFR
6.6
HV
RET620
1250
10227.05
894.66
984.13
HSWG-034-D301-BT01 (6.6kV
SWITCHGEAR BUS COUPLER 01)
Non-TFR
6.6
HV
RET620
1250
10227.05
894.66
939.39
Outgoing to TF-034-23DN01A/B
Transformer
6.6
HV
REF615
400
2000
0.00
0.00
174.96
192.46
Outgoing to TF-034-23DN02A/B
Transformer
6.6
HV
REF615
400
3700
0.00
0.00
323.68
356.04
Outgoing to TF-034-23DN03A/B
Transformer
6.6
HV
REF615
400
3700
0.00
0.00
323.68
356.04
k
13.5
80
0.14
120
Selected Descrinimation
=
180 msec
Notes:
1)
100 msec descrinimation has been considered between series feeders
2)
100 msec descrimination has been considered between the transformer primary and secondar
75 msec
28 msec
20 msec
25 msec
30 msec
178 msec
1
2
0.02
1
Primary load current for plug setting has been considered as follows,
= 110% of Transformer Secondary current (Switchboard contains Transformer Incomer)
= 105% of connected load current (Bus coupler)
= 80% of starting current of the motor
= 120% of Transformer Primary current (Switchboard contains Transformer outgoing)
= 110% of connected load current (Switchboard contains feeder incomer)
Feeder description
Feeder type
Voltage
level
Voltage
grade
Relay type
Actual
load
FLC of
largest
motor
Starting
Primary load
current of Connected
current for plug
largest load current
setting
motor
LSWG-034-N301(440V SWITCHGEAR
Maximum Sym.3-phase faul (I"k):
Minimum Sym.3-phase faul (I"k):
Maximum Ground fault:
Minimum Ground fault:
AT SS#023)
50110
30830
48290
32230
Transformer
0.44
LV
REF615
3150
2000
0.00
0.00
2624.40
3018.06
Non-TFR
0.44
LV
REF615
3150
2000
0.00
0.00
2624.40
2886.84
Outgoing to MCC-034-N301
Non-TFR
0.44
LV
REF615
630
110.06
0.00
0.00
144.42
202.19
Outgoing to MCC-034-N302
Non-TFR
0.44
LV
REF615
630
108.71
0.00
0.00
142.65
199.71
Outgoing to DB-034-N301
Non-TFR
0.44
LV
REF615
1250
486.14
0.00
0.00
637.91
956.87
A
A
A
A
k
13.5
80
0.14
120
Selected Descrinimation
=
180 msec
Notes:
1)
100 msec descrinimation has been considered between series feeders
2)
100 msec descrimination has been considered between the transformer primary and secondar
75 msec
28 msec
20 msec
25 msec
30 msec
178 msec
1
2
0.02
1
Primary load current for plug setting has been considered as follows,
= 110% of Transformer Secondary current (Switchboard contains Transformer Incomer)
= 105% of connected load current (Bus coupler)
= 80% of starting current of the motor
= 120% of Transformer Primary current (Switchboard contains Transformer outgoing)
= 110% of connected load current (Switchboard contains feeder incomer)
Feeder description
Outgoing to DB-034-N302
Feeder type
Non-TFR
HE-34-01-CP01/02/03/04
Non-TFR
Voltage
level
Voltage
grade
0.44
LV
Relay type
Actual
load
FLC of
largest
motor
Starting
Primary load
current of Connected
current for plug
largest load current
setting
motor
REF615
1250
479.53
0.00
0.00
629.24
943.86
REF615
3150
3700
0.00
0.00
3096.03
3150.00
panel AT SS#024)
A
A
A
A
0.69
LV
If
nd secondary
Actual fault
current
CT (sec)
CT (pri)
Calculated
Plug setting
Selected
Plug
setting
Down
stream
relay
operating
time
0.79
0.79
0.86
0.10
0.96
IEC Standard
inverse
988
0.79
0.79
0.69
0.180
0.87
IEC Standard
inverse
988
0.75
0.79
0.51
0.180
0.69
IEC Standard
inverse
0.5
0.50
0.41
0.100
0.51
0.89
0.89
0.11
0.180
0.89
0.89
0.11
0.180
Discrimination
time
Desired
operation
time
Phase over
current
@ LV
Fault
current
in
Reflected
relay
coil
(If)
fault current
PSM
Operating
time of
Calculated
the relay
TMS
@ TMS=1
Selected TMS
18000
14.40
18.23
0.02
0.14
2.342
0.410
0.44
23148.0
18.52
23.44
0.02
0.14
2.150
0.404
0.4
988
23148.0
18.52
23.44
0.02
0.14
2.150
0.320
0.32
IEC Standard
inverse
200
50110
3340.7
8.35
16.70
0.02
0.14
2.417
0.209
0.21
0.29
IEC Standard
inverse
356
37930
3965.4
9.91
11.14
0.02
0.14
2.835
0.102
0.1
0.29
IEC Standard
inverse
356
37930
3965.4
9.91
11.14
0.02
0.14
2.835
0.102
0.1
If
nd secondary
Actual fault
current
CT (sec)
CT (pri)
Calculated
Plug setting
Selected
Plug
setting
Down
stream
relay
operating
time
0.96
0.92
0.21
0.180
0.92
0.92
0.05
0.32
0.32
0.32
0.77
Discrimination
time
Desired
operation
time
Fault
current
in
Reflected
relay
coil
(If)
fault current
@ LV
0.39
IEC Standard
inverse
2898
50110
50110.0
15.91
17.29
0.02
0.14
2.387
0.165
0.17
0.180
0.23
IEC Standard
inverse
2898
50110
50110.0
15.91
17.29
0.02
0.14
2.387
0.097
0.09
0.00
0.05
0.05
IEC Standard
inverse
202
50110
50110.0
79.54
248.56
0.02
0.14
1.200
0.042
0.04
0.32
0.00
0.05
0.05
IEC Standard
inverse
202
50110
50110.0
79.54
248.56
0.02
0.14
1.200
0.042
0.04
0.77
0.00
0.05
0.05
IEC Standard
inverse
963
50110
50110.0
40.09
52.06
0.02
0.14
1.702
0.029
0.03
PSM
Operating
time of
Calculated
the relay
TMS
@ TMS=1
Phase over
current
Selected TMS
If
nd secondary
Actual fault
current
CT (sec)
CT (pri)
Calculated
Plug setting
Selected
Plug
setting
Down
stream
relay
operating
time
0.76
0.77
0.00
0.05
1.00
1.00
0.10
0.00
Discrimination
time
Desired
operation
time
Fault
current
in
Reflected
relay
coil
(If)
fault current
@ LV
0.05
IEC Standard
inverse
963
50110
50110.0
40.09
52.06
0.02
0.14
1.702
0.029
0.03
0.10
IEC Standard
inverse
3150
37930.00
37930.00
12.04
12.04
0.02
0.14
2.744
0.036
0.04
PSM
Operating
time of
Calculated
the relay
TMS
@ TMS=1
Phase over
current
Selected TMS
Operating
time
1.03
0.86
0.69
0.51
0.28
0.28
Remarks
Operating
time
0.41
0.21
0.05
0.05
0.05
Remarks
Operating
time
0.05
0.11
Remarks
0.2 sec
k
13.5
80
0.14
120
1
2
0.02
1
Primary load current for plug setting has been considered as follows,
= 110% of Transformer Secondary current (Switchboard contains Transformer Incomer)
= 110% of connected load current (Bus coupler)
= 80% of starting current of the motor
= 120% of Transformer Primary current (Switchboard contains Transformer outgoing)
Feeder description
Feeder type
Voltage
level
Voltage
grade
Relay type
kV
1
Existing Plant CB
CT
CT
Second Max.kW
Primary
ary
motor
current
current
kW
Actual
load
kVA
FLC of
largest
motor
A
Starting
Connected Primary load
current of
load
current for plug
largest
current
setting
motor
A
Calculated
Plug
setting
Selected
Plug
setting
2000
20000
174.96
210.00
0.11
0.15
OHL
66
HV
GE D60
Non-TFR
66
HV
Alstom P442
250
20000
174.96
209.95
0.84
1.05
66
HV
Alstom P642
250
20000
174.96
183.71
0.73
0.73
Incomer to GIS
Bus coupler
Non-TFR
5.78
MV
Sepam T81
2500
20000
1997.81
1997.81
0.80
0.80
Transformer
5.78
MV
Sepam T81
2500
20000
1997.81
2197.59
0.88
0.88
5.5
MV
Sepam S80
250
209.95
230.95
0.92
0.92
Transformer feeders
3
2000
0.00
0.00
0.2 sec
k
13.5
80
0.14
120
1
2
0.02
1
Primary load current for plug setting has been considered as follows,
= 110% of Transformer Secondary current (Switchboard contains Transformer Incomer)
= 110% of connected load current (Bus coupler)
= 80% of starting current of the motor
= 120% of Transformer Primary current (Switchboard contains Transformer outgoing)
Feeder description
Feeder type
Voltage
level
Voltage
grade
Relay type
kV
CT
CT
Second Max.kW
Primary
ary
motor
current
current
Actual
load
kW
kVA
FLC of
largest
motor
A
Starting
Connected Primary load
current of
load
current for plug
largest
current
setting
motor
A
Calculated
Plug
setting
Selected
Plug
setting
5.5
MV
Sepam S80
250
2000
0.00
0.00
209.95
230.95
0.92
0.92
5.5
MV
Sepam S80
250
2000
0.00
0.00
209.95
230.95
0.92
0.92
5.5
MV
Sepam S80
250
2000
0.00
0.00
209.95
230.95
0.92
0.92
5.5
MV
Sepam S80
250
2000
0.00
0.00
209.95
230.95
0.92
0.92
5.5
MV
Sepam S80
300
2500
0.00
0.00
262.44
288.68
0.96
0.96
Motor Feeders
9
10
5.5
MV
Sepam M81
50
180
22.00
130.00
0.00
104.00
2.08
2.10
5.5
MV
Sepam M81
100
395
48.00
240.00
0.00
192.00
1.920
1.90
0.2 sec
k
13.5
80
0.14
120
1
2
0.02
1
Primary load current for plug setting has been considered as follows,
= 110% of Transformer Secondary current (Switchboard contains Transformer Incomer)
= 110% of connected load current (Bus coupler)
= 80% of starting current of the motor
= 120% of Transformer Primary current (Switchboard contains Transformer outgoing)
Feeder description
Feeder type
Voltage
level
Voltage
grade
Relay type
kV
CT
CT
Second Max.kW
Primary
ary
motor
current
current
Actual
load
kW
kVA
FLC of
largest
motor
A
Starting
Connected Primary load
current of
load
current for plug
largest
current
setting
motor
A
Calculated
Plug
setting
Selected
Plug
setting
11
5.5
MV
Sepam M81
50
315
40.00
220.00
0.00
176.00
3.52
3.52
12
5.5
MV
Sepam M81
100
450
57.98
347.86
0.00
278.29
2.78
2.40
13
5.5
MV
Sepam M81
50
240
29.00
170.00
0.00
136.00
2.72
2.70
PSM
If
Down
stream
relay
operating
time
Actual fault
current
CT (sec)
CT (pri)
Phase over
current
Fault
current in
relay coil (If)
@ LV
Reflected
fault current
PSM
Operating
time of
Calculated
the relay
TMS
@ TMS=1
Selecte
d TMS
sec
Operating
time
sec
sec
sec
sec
0.99
0.10
1.09
IEC Standard
inverse
300
6940.0
3.47
23.13
0.02
0.14
2.159
0.507
0.51
1.10
0.79
0.20
0.99
IEC Standard
inverse
263
5298.0
21.19
20.18
0.02
0.14
2.260
0.440
0.44
0.99
0.78
0.00
0.78
IEC Standard
inverse
183
23148
2027.2
8.11
11.11
0.02
0.14
2.838
0.276
0.28
0.79
0.40
0.20
0.60
IEC Standard
inverse
2000
23148.0
9.26
11.57
0.02
0.14
2.789
0.214
0.21
0.59
0.59
0.20
0.79
IEC Standard
inverse
2200
23148.0
9.26
10.52
0.02
0.14
2.905
0.270
0.27
0.78
0.38
0.00
0.38
IEC Standard
inverse
230
55209
4216.0
16.86
18.33
0.02
0.14
2.337
0.161
0.16
0.37
PSM
If
Down
stream
relay
operating
time
Actual fault
current
CT (sec)
CT (pri)
Phase over
current
Fault
current in
relay coil (If)
@ LV
Reflected
fault current
PSM
Operating
time of
Calculated
the relay
TMS
@ TMS=1
Selecte
d TMS
sec
Operating
time
sec
sec
sec
sec
0.38
0.00
0.38
IEC Standard
inverse
230
55184
4214.1
16.86
18.32
0.02
0.14
2.338
0.161
0.16
0.37
0.38
0.00
0.38
IEC Standard
inverse
230
54797
4184.5
16.74
18.19
0.02
0.14
2.344
0.160
0.16
0.37
0.38
0.00
0.38
IEC Standard
inverse
230
55094
4207.2
16.83
18.29
0.02
0.14
2.339
0.161
0.16
0.37
0.37
0.00
0.37
IEC Standard
inverse
230
47152
3600.7
14.40
15.66
0.02
0.14
2.475
0.151
0.15
0.37
0.40
0.00
0.40
IEC Standard
inverse
288
58978
4503.8
15.01
15.64
0.02
0.14
2.476
0.160
0.16
0.40
0.00
3.70
3.70
IEC Standard
inverse
105
23148.0
23148.0
462.96
220.46
0.02
0.14
1.229
3.012
7.1
8.72
0.00
4.30
4.30
IEC Standard
inverse
190
23148.0
23148.0
231.48
121.83
0.02
0.14
1.389
3.097
6.7
9.30
PSM
If
Down
stream
relay
operating
time
Actual fault
current
CT (sec)
CT (pri)
Phase over
current
Fault
current in
relay coil (If)
@ LV
Reflected
fault current
PSM
Operating
time of
Calculated
the relay
TMS
@ TMS=1
Selecte
d TMS
sec
Operating
time
sec
sec
sec
sec
0.00
2.20
2.20
IEC Standard
inverse
176
23148.0
23148.0
462.96
131.52
0.02
0.14
1.366
1.611
5.35
7.31
0.00
1.50
1.50
IEC Standard
inverse
240
23148.0
23148.0
231.48
96.45
0.02
0.14
1.463
1.025
4.2
6.15
0.00
3.00
3.00
IEC Standard
inverse
135
23148.0
23148.0
462.96
171.47
0.02
0.14
1.292
2.322
6.4
8.27
Remarks
Remarks
Remarks
k
13.5
80
0.14
120
2
0.02
1
0.2 s
Primary load current for plug setting has been considered as follows,
= 110% of Transformer Secondary current (Switchboard contains Transformer Income
= 110% of connected load current (Bus coupler)
= 80% of starting current of the motor
= 120% of Transformer Primary current (Switchboard contains Transformer outgoing)
Feeder description
Feeder type
Voltage
level
Voltage
grade
Relay type
kV
CT Primary
current
CT
Secondary
current
Max.kW
motor
Actual load
kW
kVA
FLC of
largest
motor
A
Starting
current of Connected
largest load current
motor
A
Primary
load
current
for plug
setting
Calculated
Plug
setting
Bus coupler
Non-TFR
0.42
LV
REF 620
3200
132
2000
2749
0.86
B)
Incomer
Transformer
0.42
LV
REF 620
3200
132
2000
3024
0.95
Bus coupler
Non-TFR
0.42
LV
REF 620
3200
45
2000
0.86
B)
Incomer
Transformer
0.42
LV
REF 620
3200
45
2000
0.95
0.42
LV
REF 620
4000
27
2500
0.86
Bus coupler
Non-TFR
3436.71
B)
Incomer
Transformer
C)
EDG Incomer
Non-TFR
0.42
LV
REF 620
4000
27
2500
0.95
0.4
LV
SR 489
2500
27
1400
0.89
PSM
If
Actual fault
current
CT (sec)
CT (pri)
nsformer Incomer)
ormer outgoing)
Selected
Plug
setting
Down
stream
Discrimin
relay
ation
operating
time
time
sec
sec
sec
0.86
0.05
0.10
0.15
0.95
0.16
0.20
0.86
0.05
0.95
0.17
0.86
0.05
IEC curve
type
Phase
over
current
@ LV
Fault
current in
Reflecte relay coil (I )
f
d fault
current
PSM
Operating
time of the
relay @
TMS=1
Calculated
TMS
Selected Operating
TMS
time
IEC Standard
inverse
2752
55094
55094
17.22
20.02
0.02
0.14
2.267
0.066
0.07
0.16
0.36
IEC Standard
inverse
3040
55094
55094
17.22
18.12
0.02
0.14
2.347
0.153
0.16
0.38
0.10
0.15
IEC Standard
inverse
2752
47152
47152
14.74
17.13
0.02
0.14
2.395
0.063
0.07
0.17
0.20
0.37
IEC Standard
inverse
3040
47152
47152
14.74
15.51
0.02
0.14
2.484
0.148
0.15
0.37
0.15
IEC Standard
inverse
0.10
3440
58978
58978
14.74
sec
17.14
0.02
0.14
2.394
Remarks
sec
0.063
0.08
0.19
0.95
0.19
0.20
0.39
IEC Standard
inverse
3800
58978
58978
14.74
15.52
0.02
0.14
2.483
0.158
0.16
0.40
0.89
0.17
0.20
0.37
IEC Standard
inverse
2225
58978
58978
23.59
26.51
0.02
0.14
2.067
0.179
0.18
0.37
1997.81 A
8
24972.63 A
2186.997 A
for 50Protection, pick up is set at approx 130% of current reflected at the primary for a 3 ph
Pick up setting :
(ii)
2400 A
3437 A
6
57283.33 A
4374.364 A
for 50Protection, pick up is set at approx 130% of current reflected at the primary for a 3 ph
Pick up setting :
(iii)
5715 A
2 MVA,5.5/0.42kV Transformer
Secondary FLA :
% Z:
Through Fault current :
2749 A
6
45816.67 A
3498.727 A
for 50Protection, pick up is set at approx 130% of current reflected at the primary for a 3 ph
Pick up setting :
(iv)
MV Motor
4600 A
2405.697 A
5686.673 A
4548.345 A