SOLUTIONS TO REVISED FIRE SEPARATION
REQUIREMENTS FOR EXISTING COMMERCIAL
PREMISES / BUILDINGS UNDER CHAPTER 502 FIRE
SAFETY (COMMERCIAL PREMISES) ORDINANCE AND
CHAPTER 572 FIRE SAFETY (BUILDINGS) ORDINANCE
Ir K T LEUNG
BEng(Hons),GDAS, MSc, RPE(FRE), CEng, CEnv, CSHP FIFireE, MHKIE,
FEI, MCIBSE, MIGEM, MCIPHE, CMIOSH, RSO, RSA
Email : kt.leung@pfprc.net or kt.leung@intumescent-sys.com
Phone : 9520 3484
MAJOR CHALLENGE IN
NEW FIRE SEPARATION REQUIREMENTS
INSULATION CRITERIA FOR FIRE SEPARATION
APPLIED TO EXISTING COMMERCIAL
PREMISES UNDER CHAPTER 572 LAWS OF
HONG KONG BY AMENDMENT OF FRC 1996
THROUGH PNAP APP-83
CONTROVERSAL ISSUES ON
SPRINKLER PROTECTED FIRE SHUTTER
SHOULD SPRINKLER BE USED
FOR SUPPLEMENT THE FRR OF
FIRE SHUTTERS ?
CAN FIRE SAFETY
REQUIREMENTS FOR FIRE
COMPARTMENTATION BE
LIFTED UP FOR SPRINKLER
PROTECTED BUILDINGS ?
?
?
CRITICAL CONCERNS ON
SPRINKLER PROTECTED FIRE SHUTTER
NEITHER LPC RULES NOR BS EN 12845:2003 COVER
ANY SPECIFICATIONS OF SPRINKLER PROTECTION FOR
FIRE SHUTTER
BD CLARIFICATION ON
SPRINKLER DESIGN FOR
FIRE SHUTTER PROTECTION
BD EMAIL ON 11TH JUNE 2015
CLARIFIED THAT IT WAS
BEYOND THE JURISDICTION OF
BD. FSD SHOULD BE
CONSULTED ON THE
REQUIREMENTS ON
SPRINKLER SYSTEM OF A
BUILDING
?
?
?
CONTROVERSAL ISSUES ON
SPRINKLER PROTECTED FIRE SHUTTER
SDO (NEW PROJECT) CHAN
KAM FAI OF FSD CLEARLY
EXPRESSED HIS SERIOUS
CONCERN ON SUCH
REQUIREMENTS AND
INDICATED THAT HE DID NOT
SUPPORT THIS APPROACH
AND WOULD NOT CARRY OUT
INSPECTION TO SUCH
INSTALLATION DURING AN
HKIE SEMINAR IN 2014
?
?
MINUTES
DISCHARGE DENSITY = 10 l / m2 / min
HOWEVER, NO AMENDMENT OR UPDATES TO COVER
SPRINKLER PROTECTION FOR FIRE SHUTTER
FIRE
SHUTTER
SPRINKLER PROECTED
SHUTTER
LOSS INTEGRITY
BLOCKAGE OF SHUTTER
12
RISK OF FAILURE
CONCERNED ISSUES ON
SPRINKLER PROTECTED FIRE SHUTTER
NO CODES AND STANDARDS PROVIDE SPECIFICATIONS
ON THE DETAILED DESIGN OF SPRINKLER FOR
SUPPLEMENTING THE INSULATION PERFORMANCE OF
FIRE SHUTTER
NO FIRE TEST HAVE BEEN CARRIED OUT TO ESTABLISH
THE INSULATION PERFORMANCE OF SPRINKLER
PROTECTED FIRE SHUTTER
NO APPROVED / LISTED SPRINKLER PRODUCTS FOR FIRE
SHUTTER PROTECTION AND WETTING
LIABILITY CONCERN ON
SPRINKLER PROTECTED FIRE SHUTTER
WHO SHOULD TAKE SUCH LIABILITIES FOR
INAPPROPRIATE DESIGN AND
INAPPROPRIATE APPLICATION OF
SPRINKLER FOR PROTECTION OF FIRE
SHUTTERS KNOWINGLY ?
THE GOVERNMENT AUTHORITIES ?
THE PROJECT AUTHORIZED PERSON?
THE FIRE ENGINEER?
THE FSI CONTRACTOR? OR
THE OWNER OF THE PREMISES?
?
?
?
IS
SK
CT
SW
TO
OF
TO
OF
LIMITED SPAN
LARGE HEADROOM
REQUIRED GUIDE
RAILS
TRADITIONAL CONCEPT ON
FIRE PERFORMANCE OF FABRIC
COMBUSTIBLE
NON-FIRE RESISTING
NEW TECHNOLOGY ON
FIRE PERFORMANCE OF FABRIC
NON-COMBUSTIBLE
FIRE RESISTING TO 1 HOUR, 2
HOURS AND 4 HOURS
INTUMESCENT COATING
PROVIDE RADIATION
INSULATION PERFORMANCE
SPECIAL COATING PROVIDE
WATER-PROOF, CHEMICAL
RESISTING, AND SMOKE SEAL
PERFORMANCE
NEW TECHNOLOGY ON
FIRE PERFORMANCE OF FABRIC
COMPOSITE
INSULATED MATERIALS
PATENTED
PROVIDE INSULATION PERFORMANCE UP TO 4 HOURS
THICKNESS UP TO 11.8 MM
WITH DIFFERENT LAYERS
OF FIRE RESISTING AND
HEAT INSULATION FABRIC
THICKNESS OF OTHER
BRAND UP TO 28 MM
WITH
3
HOURS
INSULATION ONLY
NEW TECHNOLOGY ON
FIRE PERFORMANCE OF FABRIC
FIRE RESISTING
THREAD ALLOWS
SEWING
TO
LARGE SIZE UP
TO 100 M2
50 MM IN THICKNESS
800 MM
HI-TECH PRO
INSULATED
FIRE SHUTTER
408 MM
OTHER BRAND
INSULATED FIRE SHUTTER
810 MM
980 MM
BUDGET COST
(HK$/M2)
2,800
3,100
4,500
36,000
18,000
10,000
8,000
4,500
800
1000
1500
3,500
RECOMMENDATIONS
PRODUCTS TESTING AND CERTIFICATIONS
CONTRACTOR COMPETENCE AND TRAINING
THIRD PARTIES ASSESSMENT AND CERTIFICATION
PERIODICAL MAINTENANCE AND INSPECTIONS
UNDER MBIS