PRESENTED BY :

AZIZUL BIN AB KADIR


GENERAL MANAGER
MHY PRO-POWER SERVICES SDN BHD
Malaysia
1

MHY PRO-POWER SERVICES SDN BHD (772150-W)

CURRENT DRM
ANALYSIS

DYNAMIC CURRENT
MEASUREMENT
CONTINUOUS DOWN PHASE 1U
-1W

MHY PRO-POWER SERVICES SDN BHD (772150-W)

DYNAMIC CURRENT
MEASUREMENT CONT. UP
PHASE 1U -1W

Abnormality at tap
suspected due to
current drop to almost
circuit
MHY PRO-POWERopen
SERVICES
SDN BHD (772150-W)

DYNAMIC CURRENT
MEASUREMENT
CONT DOWN PHASE 1V -1W

MHY PRO-POWER SERVICES SDN BHD (772150-W)

DYNAMIC CURRENT
MEASUREMENT CONT UP
PHASE 1V -1W

Abnormality at tap
suspected due to
current drop to almost
open circuit
6

MHY PRO-POWER SERVICES SDN BHD (772150-W)

OLTC TRANSITION
ANALYSIS

TRANSITION TIMES (ms ) CONT UP & DOWN


Tap
position

1U - 1V 1V - 1W 1U-1W

1U - 1V 1V - 1W 1U-1W

64.2

61

61.9

61.7

61.3

62.1

61.5

62

61.6

63.6

62.6

61.4

61.8

36.6

35.9

63.5

61.6

62

68.2

36.3

37.9

61.2

63.6

61.9

60.1

36.7

37

61

61.4

61.2

61.7

55.4

55.6

61.8

61.9

61

59.5

59

60.4

57

60

59.8

58.1

59.2

59.1

57.6

64.4

60.9

57.8

59.5

60

58.7

59.7

55.8

9A

58.3

59.9

61.4

9A

56.4

56.7

60.1

9B

59.2

62.5

61.3

9B

58

58.8

61

10

60.1

61.9

37

10

56.9

61.6

61.5

11

59.6

37

36.2

11

62.3

62.7

61.9

12

50.2

36.7

34.9

12

58.1

66.6

57.1

13

59.5

36.5

34.7

13

60.5

55.5

60

14

53.9

35.6

35.4

14

60.2

57.9

60.7

15

57.3

59.4

58.2

15

57.7

57.1

57.3

16

56.8

60

59.9

16

58.3

54.3

57.5

CONT UP
8

Tap
position

CONT DOWN
MHY PRO-POWER SERVICES SDN BHD (772150-W)

TRANSITION TIMES (ms ) CONTINUOUS RECORD UP & DOWN

CONT
UP

CONT DOWN

MHY PRO-POWER SERVICES SDN BHD (772150-W)

FURTHER ANALYSIS.
ZOOMING INTO
TRANSITIONS

10

COMPARISON BETWEEN GOOD AND BAD


TRANSITION TIME 1U-1W (TAP 3-4 CONT UP & CONT
DOWN )

BAD

Zoom in tap
4-3 cont
down

GOOD
11

MHY PRO-POWER SERVICES SDN BHD (772150-W)

COMPARISON BETWEEN GOOD AND BAD


TRANSITION TIME 1U-1W (TAP 14-15 CONT UP &
CONT DOWN )

Zoom in tap
14-15 cont up

12

BAD

Zoom in tap
15-14 cont
down

GOOD
MHY PRO-POWER SERVICES SDN BHD (772150-W)

COMPARISON BETWEEN GOOD AND BAD


TRANSITION TIME 1V-1W (TAP 3-4 CONT UP & CONT
DOWN )

Zoom in tap
3-4 cont up

13

BAD

Zoom in tap
4-3 cont
down

GOOD
MHY PRO-POWER SERVICES SDN BHD (772150-W)

COMPARISON BETWEEN GOOD AND BAD


TRANSITION TIME 1V-1W (TAP 14-15 CONT UP &
CONT DOWN )

Zoom in tap
14-15 cont
up

14

BAD

Zoom in tap
15-14 cont
down

GOOD
MHY PRO-POWER SERVICES SDN BHD (772150-W)

ZOOM IN TAP 3-4 CONT UP ABNORMAL TRANSITION TIME

15

MHY PRO-POWER SERVICES SDN BHD (772150-W)

EXAMPLE NORMAL TRANSITION TIME

16

MHY PRO-POWER SERVICES SDN BHD (772150-W)

COMPARISON BETWEEN GOOD AND BAD TRANSITION


TIME

BAD
17

GOOD
MHY PRO-POWER SERVICES SDN BHD (772150-W)

VISUAL SITE ANALYTICAL

18

SUSPECTED THE TENSIONAL


SPRING PROBLEM
OCCURRED AT SECOND
PARALLEL RESISTOR (PHASE
W)

19

MHY PRO-POWER SERVICES SDN BHD (772150-W)

BAD CONDITION SUSPECTED OCCURED AT FIXED


CONTACT

20

MHY PRO-POWER SERVICES SDN BHD (772150-W)

THE BAD CONDITION OF


THE ARCING TAP
SWITCH

21

MHY PRO-POWER SERVICES SDN BHD (772150-W)

EXPERTISE ANALYSIS

22

Based on Dynamic Current Measurement (DCM) profiles, the


arching tap switch and the current changes, there is some
indication of the bad contact condition.
Abnormality at some of the contact condition and few
selected current profiles indicates the ripple current drop to
almost an open circuit as showing in the graphs
Suspected tensional spring problem occurred at second
parallel resistor moving contact.

Transitions time of the OLTC operation averagely at 50 to


23

MHY
PRO-POWER
SDN&
BHD
(772150-W)
60 ms for normal condition except
for
phaseSERVICES
1U 1W
1V-

THANK YOU!!