Guidance on Practice for


Fire and Gas Detection

GP 30-85

BP GROUP
ENGINEERING TECHNICAL PRACTICES

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

Foreword
This is the first issue of Engineering Technical Practice (ETP) BP GP 30-85. This Guidance on
Practice (GP) is based on parts of heritage documents from the merged BP companies as follows:

Amoco
A PS-F&GD-00-E

Process SafetyF&G Detection and Alarm EquipmentEngineering


Specification, May 1997.
A PS-F&GD-00-G
Process SafetyF&G Detection and Alarm EquipmentGuide, May
1997.
A PS-F&GD-FDA-P
Process SafetyF&G Detection and Alarm EquipmentFire Detection
and AlarmsSupply Specification, May 1997.
A PS-F&GD-GD&A-P Process SafetyF&G Detection and Alarm EquipmentGas Detection
and AlarmsSupply Specification, May 1997.

BP (pre 1999)
RP 30-7
GS 130-10

Design Philosophy for Fire and Gas Detection and Control Systems,
February 1994.
Guidance for Specification 130-10, Specification for the Supply of Fire &
Gas Systems, January 1994.

BP Exploration
SPR/G/97/005
SPR/G/97/005
SPR/G/97/005
SPR/G/97/005

Guidance on F&G Detection, SPR Operational Integrity Team, General


Requirements, Part 1, April 1997.
Guidance on F&G Detection, SPR Operational Integrity Team, Setting
Performance Requirements, Part 2, April 1997.
Guidance on F&G Detection, SPR Operational Integrity Team, Detector
Specification, Part 3, July 1997.
Guidance on F&G Detection, SPR Operational Integrity Team, Audit &
Inspection, Part 6, April 1997.

Copyright 2002, BP Group. All rights reserved. The information contained in this
document is subject to the terms and conditions of the agreement or contract under which
the document was supplied to the recipients organization. None of the information
contained in this document shall be disclosed outside the recipients own organization
without the prior written permission of Manager, Standards, BP Group, unless the terms of
such agreement or contract expressly allow.

Page 2 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

Table of Contents
Page
Foreword......................................................................................................................................... 2
1. Scope........................................................................................................................................... 6
2. Normative references................................................................................................................... 6
3. Terms and definitions................................................................................................................... 7
4. Symbols and abbreviations.......................................................................................................... 7
5. General........................................................................................................................................ 8
5.1. Legislative regulations, local codes, and standards.........................................................8
5.2. Safety management........................................................................................................8
5.3. Specifier role................................................................................................................... 8
5.4. Performance.................................................................................................................... 9
5.5. Hazards........................................................................................................................... 9
6. Fire detection performance.........................................................................................................11
6.1. General......................................................................................................................... 11
6.2. Fire sensitivity levels fire risk analysis...........................................................................12
6.3. Fire risk categories........................................................................................................12
6.4. Area types and use.......................................................................................................13
6.5. Grade definitions........................................................................................................... 14
6.6. Assigning grades to hydrocarbon handling areas..........................................................15
6.7. Assigning grades to nonhydrocarbon handling areas....................................................16
6.8. Assigning grade to special areas...................................................................................16
6.9. Fire detection voting......................................................................................................18
6.10. Manual fire alarm stations...........................................................................................19
7. Flammable gas detection performance......................................................................................19
7.1. General......................................................................................................................... 19
7.2. Risk volume assessment...............................................................................................20
7.3. Gas detection control actions........................................................................................22
7.4. Gas detection voting.....................................................................................................22
8. Toxic gas detection performance...............................................................................................23
8.1. General......................................................................................................................... 23
8.2. Carbon monoxide.......................................................................................................... 23
8.3. Carbon dioxide.............................................................................................................. 23
8.4. Hydrogen sulphide........................................................................................................ 24
8.5. Hydrogen cyanide......................................................................................................... 24
8.6. Hydrogen fluoride.......................................................................................................... 24
9. Safe havens............................................................................................................................... 24
10. Detector type selection............................................................................................................. 25
10.1. General....................................................................................................................... 25

Page 3 of 45

29 January 2003

10.2.
10.3.
10.4.
10.5.
10.6.

GP 30-85
Guidance on Practice for Fire and Gas Detection

Flame.......................................................................................................................... 25
Gas............................................................................................................................. 26
Heat............................................................................................................................ 28
Oil mist........................................................................................................................ 29
Smoke......................................................................................................................... 29

11. Detector deployment................................................................................................................ 31


11.1. General....................................................................................................................... 31
11.2. Flame.......................................................................................................................... 31
11.3. Gas............................................................................................................................. 31
11.4. Heat............................................................................................................................ 32
11.5. Oil mist........................................................................................................................ 32
11.6. Smoke......................................................................................................................... 32
12. Control and indicating equipment.............................................................................................33
13. Maintenance............................................................................................................................. 33
14. Audit and inspection................................................................................................................. 33
14.1. General....................................................................................................................... 33
14.2. Audit criteria................................................................................................................ 34
14.3. System design review.................................................................................................34
14.4. Installed equipment review..........................................................................................35
14.5. Reliability and availability review.................................................................................36
14.6. Personnel review.........................................................................................................36
Annex A
(Normative)
F&G detection performance record sheets............................................................................37
Annex B
(Normative)
Test requirements for high-sensitivity smoke detection systems...........................................42
B.1 General................................................................................................................................... 42
B.1 General................................................................................................................................... 42
B.1.1 Scope........................................................................................................................ 42
B.1.1 Scope................................................................................................................................... 42
B.1.2 Fire simulation........................................................................................................... 42
B.1.2 Fire simulation...................................................................................................................... 42
B.2 Test equipment....................................................................................................................... 42
B.2 Test equipment....................................................................................................................... 42
B.3 Test procedure........................................................................................................................ 42
B.3 Test procedure........................................................................................................................ 42
Bibliography.................................................................................................................................. 43

List of Tables
Table 1 - Comparison of RHO and apparent flame area................................................................10
Table 2 - Fire risk categorisation....................................................................................................12

Page 4 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

Table 3 - Fire detection grade definitions.......................................................................................14


Table 4 - Fire detection sensitivity recommended defaults.............................................................15
Table 5 - Typical performance requirements..................................................................................15
Table 6 - Typical requirements for Grade T and Grade V...............................................................17
Table 7 - Exposure limits for common toxic gases.........................................................................23

List of Figures
Figure 1 - Method for setting fire detection requirements...............................................................44
Figure 2 - Method for setting flammable gas detection requirements.............................................45

Page 5 of 45

29 January 2003

1.

GP 30-85
Guidance on Practice for Fire and Gas Detection

Scope
a.

This GP provides guidance on practice for fire and gas (F&G) detection for BP facilities
including:
1.

Required performance.
There are no recognised national or international codes or standards that cover the
performance specification of F&G detection systems.

b.

2.

2.

Selection.

3.

Design.

4.

Installation.

5.

Operation.

6.

Maintenance.

7.

Audit of system designs and installations.

This GP does not cover detection by analysers. Refer to ETPs in ETP document
category 31 for information on analysers.

Normative references
The following normative documents contain requirements that, through reference in this text,
constitute requirements of this technical practice. For dated references, subsequent amendments to, or
revisions of, any of these publications do not apply. However, parties to agreements based on this
technical practice are encouraged to investigate the possibility of applying the most recent editions of
the normative documents indicated below. For undated references, the latest edition of the normative
document referred to applies.

BP
GP 12-60
GP 30-45
GP 30-75
GP 30-76
GP 30-80
GP 30-81
GIS 30-851

Guidance on Practice for Hazardous Area Electrical Installations.


Guidance on Practice for Human Machine Interface for Process Control.
Guidance on Practice for Safety Instrumented Systems (SIS)
Management of the Safety Lifecycle.
Guidance on Practice for Safety Instrumented Systems (SIS)
Development of the Process Requirements Specification.
Guidance on Practice for Safety Instrumented Systems (SIS)
Implementation of the Process Requirements Specification.
Guidance on Practice for Safety Instrumented Systems (SIS)
Operations and Maintenance.
Guidance on Industry Standard for Fire and Gas Detection.

British Standards Institute (BSI)


BSI BS 5839 Part 1

Fire detection and alarm systems for buildings.

International Electrotechnical Commission (IEC)


IEC 61508

Functional safety of electrical/electronic/programmable electronic safetyrelated systems Parts 1 to 4.

Page 6 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

National Fire Protection Association (NFPA)


NFPA 72

3.

National Fire Alarm Code.

Terms and definitions


For the purposes of this GP, the following terms and definitions apply:
1ooN
One out of (1oo) the number (N) of detectors or circuits in the voting group in a specific area is in
alarm.
1oo2d
One out of (1oo) the number (N, in this case N = 2) of detectors or circuits in the voting group is in
alarm, and a different detector or circuit in the same voting group is in fault condition.
2ooN
Two out of (2oo) the number (N) of detectors or circuits in the voting group are in alarm.
Blockage ratio
Proportion of unobstructed area on all the boundary faces of a volume. For example, an enclosed box
has a blockage ratio of 1.0.

4.

Symbols and abbreviations


For the purpose of this GP, the following symbols and abbreviations apply:
BS

British standard.

ESD

Emergency shutdown.

FPSO

Floating production, storage and offloading (vessel).

LEL

Lower explosive limit.

LFL

Lower flammable limit.

OD

Outside diameter.

RHO

Radiant heat output.

SIL

Safety integrity level.

STEL

Short-term exposure limit.

TWA

Time weighted average.

UEL

Upper explosive limit.

UFL

Upper flammable limit.

VESDA

Very early smoke detection apparatus. (VESDA is a registered trademark of Vision


Systems. Mention of the VESDA name in this GP should not be inferred as a preference
for this product over other similar products).

Page 7 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

The pair of terms LEL and LFL and the pair of terms UEL and UFL are practically
interchangeable. They are all units of measurement for gas flammability. The terms
LFL and UFL are more common in the Americas, and LEL and UEL are more
common in Europe.

5.
5.1.

General
Legislative regulations, local codes, and standards
a.

If F&G legislative requirements for an area conflict with guidance given in this GP,
legislative requirements shall take precedence.
In practice, this is not usually an issue. Legislation generally only mandates that a
detection system be provided and does not dictate the quality or sensitivity of the
detection system.

b.

F&G detection equipment shall comply with local codes and standards.
No national or international standards that cover the requirement for F&G
detection at BP facilities are available at the time of creating this GP. For offshore
installations, ISO 13702 provides guidance in the broader subject of control and
mitigation of fires and explosions and ISO 10418 (2003 version) provides guidance
on emergency support systems including fire and gas detection systems.

c.

5.2.

Specification of performance requirements should include expectations and assumptions


of:
1.

Facility management.

2.

Risk assessors.

3.

Safety teams.

4.

Maintenance crews.

5.

Auditors.

6.

System designer.

Safety management
Processes for competency of people, planning activities, documentation and verification should
be in accordance with GP 30-75. GP 30-75 shall be followed if any of the F&G detection
functions require SIL 1 or higher integrity.

5.3.

Specifier role
a.

b.

Specifiers of F&G system performance requirements should have the following


capabilities:
1.

Be experienced in design of F&G detection systems.

2.

Have a familiarity with other engineering disciplines (in particular, process, electrical,
and instrumentation) and how they interact with one another.

3.

Have an understanding of site operations.

Specifiers shall ensure that F&G detection systems comply with:


1.

Local codes and standards.

2.

Safety requirements for the site.

Page 8 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

Compliance with local codes and standards is important. However, the specifiers
role is to ensure that the performance of the F&G detection system complies with
the safety requirements for the site and not just the minimum to comply with code.

5.4.

c.

Specifiers role shall include coordination and communication.

d.

Required level of performance for all parts of the F&G detection system shall be recorded
on sheets, such as those provided in Annex A.

Performance
a.

The following shall be reviewed and recorded to determine F&G performance


requirements:
1.

Legislative requirements for F&G detection.

2.

Operator expectations for the system. This review should include a discussion of
hazards in terms of damage they can cause, such as:

3.

a)

Size of fires.

b)

Time to escalation.

c)

Tolerable levels of damage.

Integrity levels determined in accordance with GP 30-76, claims of safety studies,


and any other claims for F&G detection system performance.
These claims are often discussed in terms of outcomes and probabilities for
successful risk reduction.

b.

Default performance levels to be used for assigning performance requirements for each
part of the site shall be specified, including any interactions with other mitigation measures
(for example, ESD and blowdown).

c.

The following shall be assigned for each part of the site that requires gas detection:
1.

Gas detection risk volume category. Refer to Table 2 for this categorisation.

2.

Fire detection grade. Refer to Table 3 for fire detection grade definitions.
a)

If default values are not appropriate in the judgement of the specifier, special
requirements for F&G detection shall be specified.

b)

Special requirements shall take site-specific risks into account (for example,
risks to safety, environment, production, or reputation).

Good practice requirements are a straightforward issue. However, special


requirements can be difficult because they are more subjective.
Special requirements are defined by what consequences BP wants to prevent and
how BP expects fire or gas detection to provide confidence that these consequences
can be prevented.
5.5.

Hazards

5.5.1.

General

F&G hazard shall be defined as one of the following:


a.

Flaming fire.

b.

Flammable gas.

c.

Toxic gas.

Page 9 of 45

29 January 2003

5.5.2.

GP 30-85
Guidance on Practice for Fire and Gas Detection

Flaming fire

Radiant heat output (RHO) should be used to specify fire detection targets for flaming fires.
Table 1 compares RHO with flame area for some typical hydrocarbon fires. The measurement is
the apparent area of the flame to a bystander, not the flames base area.
Table 1 - Comparison of RHO and apparent flame area
10 kW

50 kW
1,5 m (16 ft )

3 m (32 ft )

7,5 m2 (80 ft2)

Oil jet

0,25 m2 (2.5 ft2)

1,3 m2 (14 ft2)

2,5 m2 (27 ft2)

6,5 m2 (70 ft2)

0,5 m (5 ft )

1,9 m (20 ft )

250 kW

0,3 m (3 ft )
2

100 kW

Gas jet
Oil pool

4 m (43 ft )

8,5 m2 (91 ft2)

The base area of a fire is not a good measure of the damage a fire can do. A small
premixed propane torch flame, for example, can be much more aggressive than a
larger diffusion flame. For this reason, BP defines a fire hazard by its RHO. RHO is
a good indication of the potential damage and the probability that a fire will
escalate or cause loss.
5.5.3.

Flammable gas

5.5.3.1.

General area coverage

a.

In areas sufficiently confined or congested, flammable gas hazards should be defined by


their size based on the gas type and geometry of the area in terms of the confinement and
congestion.

b.

Stoichiometric concentration should always be assumed, and the gas cloud specified in
terms of a sphere.
The consequence of an explosion can either be direct loss and damage through
blast, or escalation through further releases caused by pressure pulses that can
move pipes or even large vessels and wind effects that can hurl missiles. These
events are unlikely to occur if the flame speed is below about 100 m/s (330 ft/s).
In the same way that an athlete performing long jumps needs a runup to reach
takeoff speed, the flame front of an explosion needs a space in which to accelerate.
For many types of gases (typically alkanes) that BP handles at upstream facilities
and the geometry of BP plants, the minimum acceleration distance is about 5 m to
6 m (16 ft to 19 ft), even if assuming perfect combustion.

5.5.3.2.

Nonhazardous spaces

In areas containing electrical apparatus that have not been assessed as hazardous (as defined by
relevant national or international standards) and are supplied by mechanical ventilation for overpressurisation, the hazard is from gas ingress via the ventilation system.
5.5.3.3.

Perimeter monitoring

Gas hazards that may result from ignition of gas that has migrated from large unconfined and
uncongested areas containing hydrocarbon handling equipment shall require detection of
significant gas volumes leaving the handling area.
Examples of such application would be onshore gas terminals or refineries. The
base area of most offshore installations would generally be too small for perimeter
detection to be effective.
5.5.4.

Toxic gas

Toxic gas hazard performance requirements shall be specified in terms of concentration and
response time.
Page 10 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

Toxic gas effects are directly linked to concentration, and for some gases, exposure
time.

6.
6.1.

Fire detection performance


General
The method described below is based on many years experience gained at many
facilities. The method tailors detection requirements to the type of hazard and levels
of risk on a site, and is strongly linked to workforce expectations and major risk
reduction requirements. The process is summarised in Figure 1.
a.

Fire detection requirements shall be determined using the process defined in Figure 1.

b.

Legislative requirements for automatic fire detection shall be established.

c.

Site shall be divided into areas for the purpose of determining level of fire detection.

d.

Required fire sensitivity levels shall be defined for the site.

e.

Areas shall be assigned grades according to defined criteria.

f.

Areas shall be assessed to determine where fire detection could reduce risk of personnel
exposure to fire.
Area assessment is normally performed through formal safety studies.

g.

Potential losses from fire damage shall be assessed in terms of plant replacement or lost
production costs. Determination of how automatic fire detection could reduce such losses
shall be made.

h.

Risks shown in Table 2 should be used to determine the need for and quality of fire
detection.

i.

Fire detection grading should be performed as follows:


1.

A risk classification shall be assigned to each area.

2.

A protection grade shall be assigned to each area.


Fire detection requirements for an area are determined by the risk in that area, and
defined by the grade of protection required.

6.1.2.

Grading basis

Areas within a site shall be assigned a grade based on the following factors:
a.

Legislative requirements for automatic fire detection that apply to the site.

b.

Safety studies.

c.

Required fire sensitivity level.

d.

Fire risk category.

e.

Type of area, including:

f.

1.

Hydrocarbon handling area.

2.

Nonhydrocarbon-handling area.

3.

Special risk area.

Purpose and use of the area, including:


1.

Human occupation.

2.

Turbines and other engines.

Page 11 of 45

29 January 2003

6.1.3.

GP 30-85
Guidance on Practice for Fire and Gas Detection

3.

Special equipment.

4.

Ventilation air intake.

Legislative requirements

Legislative requirements that apply to the site shall be recorded and applied to the grading
process.
6.1.4.

Safety studies

Previous site safety studies shall be examined and applicable results incorporated into the
grading process.
6.2.

Fire sensitivity levels fire risk analysis


a.

A fire risk analysis for the site should be performed to determine fire sensitivity levels of
Low, Medium, and High.

b.

Sensitivity levels should be set relative to the type of site.


For example, a fire of sufficient heat output to damage 6 mm (0,25 in) OD
instrument tubing may have no effect on 0,9 meter (36 in) heavy wall pipe.

c.

6.3.

Fire risk analysis should be based on one or more of the following:


1.

Qualitative analysis based on experience of fire risk analysis.

2.

Site-specific safety studies.

3.

Project-specific safety studies.

Fire risk categories


A fire risk category shall be assigned to each area of the site in accordance with Table 2.
Table 2 - Fire risk categorisation
Damage replacement
cost level (L)

Cost of
lost production

Possibility of operator
action to reduce
consequences

Minor (L1)

Minor (F1)

Possible (P1)

Unlikely (P2)

Possible (P1)

Unlikely (P2)

Possible (P1)

Unlikely (P2)

Possible (P1)

Unlikely (P2)

Possible (P1)

Unlikely (P2)

Possible (P1)

Unlikely (P2)

Major (F2)
Moderate (L2)

Minor (F1)
Major (F2)

Major (L3)

Minor (F1)
Major (F2)

Risk
category

Notes
1. Fire Risk Category 0 requires no automatic fire detection.
2. Examples of Fire Risk Category 1 include onshore gas terminals, oil refineries, and
chemical plants.
3. Examples of Fire Risk Category 2 include offshore platforms, FPSOs (Floating
Production, Storage, and Offloading units) and onshore enclosed production plants.
4. Facilities may justify changes to these values with risk-based assessments.

Page 12 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

6.4.

Area types and use

6.4.1.

Hydrocarbon handling areas

a.

An area shall be classified as a hydrocarbon handling area if it contains any item in the
facility intended to process, convey, consume, or store hydrocarbon fluids (for example,
oil, gas or condensates, and fuel gas).

b.

Areas containing significant quantities of flammable utility fluids (for example, diesel fuel,
and methanol) shall also be included as hydrocarbon handling areas.

c.

Exceptions to classification as a hydrocarbon handling area are:


1.

Pipework (except for vessels) outside the boundary of production, process, drilling,
utility, or accommodation areas.

2.

Turbine enclosures and other similar machinery enclosures that are described
separately.
Note that NFPA 30 (the Flammable and Combustible Liquids Code) uses different
and stricter definitions of the words combustible liquid and flammable liquid.

6.4.2.

Nonhydrocarbon handling areas

Nonhydrocarbon handling areas shall be enclosed spaces other than those designated as
hydrocarbon handling areas and that have one of the following characteristics:
a.

Is normally occupied.

b.

Contains machinery or electrical and electronic equipment.

c.

Contains significant inventory of flammable materials.

d.

Is a designated escape route that could be affected by one of the above (even if it contains
no fire hazard of its own).

6.4.3.

Special risk areas

6.4.3.1.

General

The following area types shall be classified as special risk:

6.4.3.2.

a.

Enclosures for turbines, other engines, and similar machinery.

b.

Ventilation air intakes.

c.

Areas that require fire detection, but to which no other previously defined area type
applies.

Turbine engine machinery enclosures

Machinery enclosures require early fire detection if either of the following applies:
a.

Fires in the enclosure would be difficult or dangerous to control.

b.

The type of fire that could occur may quickly lead to unacceptable damage or loss.
Examples of this type of fire are if a fire could be particularly aggressive (highpressure fuel or lubricating oil fires) or if equipment in the enclosure is easily
damaged and critical (fire pumps or analyser houses).

6.4.3.3.

Ventilation air intakes

a.

Ventilation air intake areas shall include air intakes that supply one of the following:

Page 13 of 45

29 January 2003

6.4.4.

GP 30-85
Guidance on Practice for Fire and Gas Detection

1.

Personnel.

2.

Plant areas that require monitoring.

b.

Air intakes that require incoming air to be monitored for the protection of the facility or
personnel within the area shall have smoke detection fitted.

c.

Applications that require toxic gas and fire detection on air intakes shall have fire detection
performance requirements specified in terms of:
1.

Smoke concentration.

2.

Toxic gas concentration.

3.

Required response time.

Areas requiring no detection

If fire detection is not required in an area, the reason shall be documented.


Changes in the facility (for example, new storage of flammable materials) may later
invalidate that decision.
6.5.

Grade definitions

6.5.1.

General

Fire detection grades shall be assigned to areas in accordance with Table 3.


Table 3 - Fire detection grade definitions
Grade

Area definition

A
B
C
D
E
F
S
T
V

Hydrocarbon handling, with high sensitivity.


Hydrocarbon handling, with normal sensitivity.
Hydrocarbon handling, with low sensitivity.
No hydrocarbons, with protection of human life.
No hydrocarbons, with protection of special equipment.
No hydrocarbons, with general coverage.
Special risk, where no other grade is appropriate.
Special risk, with turbine and other engine enclosures.
Special risk, with ventilation air intakes.

Facility management should agree on the definition for each grade, including the
sensitivity, function, and reliability of detection. With the exception of Grade S,
these definitions apply throughout the facility. Because Grade S areas are a special
case, each Grade S area has its own definition.
6.5.2.

Definition of grades in hydrocarbon handling areas

For each hydrocarbon handling area requiring fire detection, an appropriate grade (A, B, or C)
should be set. Specification of each grade should include:
a.

Fire detection sensitivity (refer to recommended defaults in Table 4).

b.

Response time from the moment the condition occurs until the correct output signal is
given.

c.

Availability, which is the probability that the fire will be detected and the correct output
given. This probability accounts for random equipment failure, design limitations (such as
incomplete coverage), and operational failures (such as lockout or maintenance).

d.

Requirement for manual or automatic control actions that the system should promote (for
example, alarms and plant shutdowns).

Page 14 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

Table 4 - Fire detection sensitivity recommended defaults


Sensitivity required - RHO in kW
Fire risk category
Category 1

Category 2
voted

Category 2
nonvoted

6.5.3.

Area grade

For alarm

For automatic control action

Grade A

50

Not required

Grade B

100

Not required

Grade C

500

Not required

Grade A

10

10

Grade B

10

50

Grade C

100

250

Grade A

10

10

Grade B

50

50

Grade C

100

100

Definition of grades in nonhydrocarbon handling areas

For each nonhydrocarbon handling area requiring fire detection, an appropriate grade (D, E, F)
should be set. The specification should include:
a.

Conformance to an industry standard level of performance, if feasible. Table 5 lists typical


performance requireents.

b.

Availability, which is the probability that the fire will be detected and the correct output
given. This accounts for random equipment failure, design limitations such as incomplete
coverage, and operational failures such as lockout or maintenance.

c.

The need for manual or automatic control actions that the system should promote (for
example, alarms and plant shutdowns).
Table 5 - Typical performance requirements
Grade
D (Life protection)
E (Equipment protection)
F (General)

Required performance
Designed to comply with test requirements defined in Annex B.
Designed to comply with test requirements defined in Annex B.
Designed to comply with requirements of the local fire detection
standards (for example, NFPA72 or BSI BS 5839 Part 1 for
Class P2 systems). If no national standards are available, then the
latest version of NFPA 72 should be used.

6.6.

Assigning grades to hydrocarbon handling areas

6.6.1.

Method

The basic steps in assigning fire detection grades to hydrocarbon handling areas are:
a.

Initially, assign all hydrocarbon handling areas as Grade B. Grade B zones should extend
either a minimum of 2 m (6 ft) from any facility that is protected by the zone, or to the area
boundaries if any are within 4 m (13 ft) of the facility.

b.

Identify any portions of Grade B areas where better detection is required, and assign them
as Grade A. Grade A zones should extend a minimum of 1 m (3 ft) from the applicable
area, and should be segregated from Grade C areas by a further 2 m (6 ft) of Grade B
areas.

c.

Review all remaining Grade B areas for places where detection requirements are
excessive, and assign them as Grade C. Grade C zones should not be within 2 m (6 ft) of a
hydrocarbon handling facility from which there is potential source of release (for example,
flanges or compression fittings).

Page 15 of 45

29 January 2003

6.6.2.

6.7.

GP 30-85
Guidance on Practice for Fire and Gas Detection

Grade usage

a.

Grade A should be used for places in hydrocarbon handling areas where small fires could
cause significant damage in a short period of time. Such fires might be due to the fuel
source (for example, high-pressure gas from a compressor) or from the areas inherent
sensitivity to fire (for example, small bore pipework and pump seals). Such risks normally
have well-defined risk reduction measures (control actions), some of which may be active
and may need to be triggered by automatic fire detection.

b.

Grade B is the normal level of fire detection in hydrocarbon risk areas. It should be used
if another grade is not more appropriate.

c.

Grade C should be used if the Grade B level of detection is excessive, and a reduced
performance grade is appropriate.

d.

The extensions to Grade A and Grade B areas (refer to paragraphs 6.6.1.1.a and 6.6.1.1.b)
may be revised because of site-specific detection targets. The criteria quoted above should
be regarded as the minimum.

Assigning grades to nonhydrocarbon handling areas


a.

The basic steps in assigning fire detection grades to nonhydrocarbon risk areas are:
1.

Initially, assign Grade F to nonhydrocarbon risk areas.

2.

Review Grade F areas for life protection risks and reassign these as Grade D.

3.

Review remaining Grade F areas for special equipment protection requirements, and
reassign these as Grade E detection.

4.

Review remaining Grade F areas for places where detection is not required.
Document reasons that fire detection is not required, and note that future changes
may invalidate the decision.

b.

Grade D should be assigned to rooms that contain a bed (including medical areas) and to
escape routes. This performance level protects a sleeping person from a fire in the same
cabin or in an adjacent space. If the ventilation system can transfer smoke (either directly
or by induction) into escape routes or sleeping areas, these areas should also be Grade D.

c.

Grade E should be assigned to rooms that contain electrical or mechanical safety


equipment or other high-value equipment (for example, ESD cabinets, emergency power
supplies, communication systems, and incident control centres).

d.

Grade F should be assigned to all other nonhydrocarbon areas that require fire detection.
This should include public areas (common rooms, offices, etc.), utility spaces (voids, etc.),
and areas that contain less valuable equipment (storage rooms for flammable materials,
etc.).

6.8.

Assigning grade to special areas

6.8.1.

General

The basic steps in assigning grades to special areas are:


a.

Identify turbine and similar machinery enclosures where early detection of an internal fire
is required. Assign Grade T and clarify the performance requirements for such areas with
the facility management. Table 6 lists typical requirements.

b.

Identify air intakes that require fire detection and assign them Grade V. Establish the
nature of the hazard and establish agreement with the facility management on the role of
detection in achieving the required protection.

c.

Inevitably, there are places in the facility where detection requirements do not fall into one
of the other eight grades. Identify such areas and assign them Grade S. Special

Page 16 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

requirements for each Grade S area should be established in conjunction with facility
management.
Table 6 - Typical requirements for Grade T and Grade V
Grade
T

6.8.2.

Function

Sensitivity

To detect oil mist or vapour from fuel or lubrication system releases in the
enclosure, or smoke arising from combustion of these fuels.
To detect excessive air temperature in the enclosure and in the ventilation air
outlet.
An alarm from either form of detection should automatically cause alarm at the
control point. Alarms from the temperature detection should cause automatic
control actions.
To detect a smoke plume from an oil or gas fire at the limit of breatheability
for an exposure time determined by site-specific fire analysis.
To prevent smoke at the stated limit from reaching any room of the protected
space.

1 dB/m
Ambient +40C
(+72F)

Determined by
analysis

Grade T fire detection

Grade T should be assigned to:


a.

Turbine enclosures.

b.

Other machinery enclosures that require early fire detection. Early fire detection is
required if one of the following conditions is present:
1.

Fire in the enclosure would be difficult or dangerous to control.

2.

Fire could rapidly cause unacceptable damage or loss.


Unacceptable damage or loss can be caused by fires that are particularly
aggressive (for example, high pressure fuel or lubricating oil fires).

3.

Equipment in the enclosure is easily damaged and is critical.


Examples of such equipment include fire pumps or analyser houses.

6.8.3.

Grade V fire detection

a.

Grade V should be used in air intakes if the incoming air needs to be monitored for
personnel or equipment protection in the area served by the air supply.

b.

Types of smoke or toxic gas to monitor shall be specified.

c.

Supplied air used to pressurise living space volumes and dilute or prevent leaks of higher
smoke concentrations from doors, drains, and other penetrations shall be categorized
breatheable.
Breatheable air is different from uncontaminated air. In many cases the
supplied air is normally used to pressurise living space volumes and dilute or
prevent leaks of higher smoke or toxic gas concentrations from doors, drains and
other penetrations. If pressurisation is lost at an early stage of a major incident (for
example, in response to very sensitive detection) then the resulting leaks can quickly
lead to fatality of the occupants.

d.

For areas that require breathable air, the F&G system should detect concentrations of
smoke or toxic gas at the upper limit of breatheability.

e.

Upper limit of breatheability shall depend on how long personnel are expected to remain in
the volume.

f.

Specification should refer to the Smoke and Gas Ingress Analysis, if available.

Page 17 of 45

29 January 2003

6.8.4.

6.8.5.

GP 30-85
Guidance on Practice for Fire and Gas Detection

Grade S fire detection

a.

Grade S should be assigned if the default grades are not appropriate.

b.

Specification of detection for Grade S areas shall be based on:


1.

Type of fire and its fuel (the hazard).

2.

Risk to be mitigated.

3.

Planned actions, including response time (the role).

4.

Required sensitivity (in RHO).

5.

Required system outputs (the function).

6.

Worst acceptable failure on demand rate for detection elements (the availability).

Control actions from fire detection

a.

Automatic control actions from fire detection should be targeted for the hazard they are
protecting against on an area-by-area basis.

b.

Manual response to fire alarms that can be demonstrated to be sufficiently effective are
preferred to automatic systems.
It is important that automatic control actions from fire detection are targeted,
rather than taking a blanket approach for the facility. For example, in a facility that
contains both office and process facilities, it makes no sense to shut down the
process on detection of an office fire. In fact, this increases the probability of
hazard in the process facility.
Higher performance detection can provide earlier warnings, allowing manual
action to be taken in preference to automatic control action.

6.9.

Fire detection voting

6.9.1.

General

Voting logic should be used for automatic control actions where the anticipated loss from
unwanted response (false control action) from the detection equipment is unacceptable.
6.9.2.

Grade A, Grade B, and Grade C

a.

For Grade A, Grade B, and Grade C areas where automatic control actions cause process
or plant shutdown or activation of fire protection systems, 2ooN voting logic (two of the
detectors or circuits in the voting group in alarm) should be employed for all electrical and
electronic detection systems.

b.

Pneumatic fire detection systems may be used in Grade A, Grade B, and Grade C areas
without voting if care is taken in their design and installation to minimise unwanted
actions that result in production losses.
There are at present no optical flame detection systems that have sufficient history
to justify their being used in a nonvoting mode for automatic control actions in the
majority of BP applications. When deciding on the requirement for voting detectors,
consideration should be given to the cost of adding the necessary number of
detectors to achieve the performance targets versus the cost of unwanted production
shutdowns.

6.9.3.

Grades D, Grade E, and Grade F

For Grade D, Grade E, and Grade F areas, unwanted automatic control actions are unlikely to
cause significant losses, so detectors should not normally be voted.

Page 18 of 45

29 January 2003

6.9.4.

GP 30-85
Guidance on Practice for Fire and Gas Detection

Grade S

For Grade S areas, detector voting requirements should be assessed on a case-by-case basis.
6.9.5.

Grade T

For Grade T areas, detectors used to automatically shut down the machine and initiate the fire
protection system should be voted in a 2ooN configuration.
6.9.6.

Grade V

For Grade V areas, unwanted automatic control actions are unlikely to cause significant losses,
so detectors should not normally be voted.
6.10.

Manual fire alarm stations


Manual fire alarm stations (also called manual alarm callpoints) are for personnel
to raise alarms.

7.
7.1.

a.

Manual fire alarm station devices should be located at exits on designated escape routes.

b.

Maximum personnel travel distance on designated escape routes between the exited area to
the nearest station shall be determined by national standards, but shall not exceed 60 m
(200 ft). If the travel distance between exits exceeds the maximum limit, additional manual
fire alarm stations shall be positioned throughout the designated escape routes.

c.

The role of manual fire alarms should be clearly defined and personnel properly trained in
their use.

d.

The use of alarms on some facilities for events other than fire (for example, man
overboard) should be considered.

e.

If manual fire stations are to be used to raise alarms for events other than fire, additional
stations shall be required to allow for these extra functions.

Flammable gas detection performance


General
The method described below is based on many years experience gained at many
facilities. The method tailors detection requirements to the type of hazard and levels
of risk on a site, and is strongly linked to workforce expectations and major risk
reduction requirements. The process is summarised in Figure 2.
a.

Flammable gas detection requirements shall be determined using the process defined in
Figure 2.

b.

Initially, any legislative requirements for automatic gas detection should be determined.

c.

Next, each area should be assessed for risks from gas explosion.

d.

Gas detection should be required for an area if any of the following apply:
1.

Areas that are classified as hazardous in accordance with either GP 12-60 or with the
recognised national standard shall require gas detection. Exceptions are areas that are
too small to contain a gas cloud large enough to be an explosion hazard.

2.

Areas that are nonhazardous into which gas could feasibly be transported, either by
mechanical ventilation systems, differential pressures, or air movement) require gas
detection. The penetrations through which gas can be transported include air supply
ducts and single-door accessways coming from classified hazardous areas.
Exceptions are self-closing extract ducts, airlocked entrances, or single emergency
doors that are not often used.

Page 19 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

3.

Areas in which large volumes of gas could be released and transported to other areas
where an explosion hazard could be formed.
A nontoxic flammable gas release is not normally hazardous unless ignited. If the
gas is ignited the result can be a flash fire, a sustained fire, or an explosion. If fire
detection is provided in accordance with this GP, it is assumed that all risks
associated with sustained fires are addressed.
Current technology does not allow gas detection to reliably detect all leaks. The
best that can be reliably achieved is the detection of a gas cloud with size and
concentration to make it a sufficient threat to require action. Obviously, some leaks
will be detected. Gas detection would not usually be fitted in areas where gas at
hazardous concentrations is normally present.

7.2.

Risk volume assessment

7.2.1.

General

7.2.2.

a.

Flammable gas detection shall be provided in areas (risk volumes) where ignited gas
clouds could cause damage from explosion overpressure.

b.

In these areas, the smallest gas cloud that has the potential to cause such damage shall be
specified as the detection target.

Small enclosed volumes

a.

Small volumes shall be defined as less than 1 000 m3 (35 000 ft3).
These areas can be either naturally ventilated or force ventilated.

b.

Small volumes that are naturally ventilated shall require detection of a spherical gas cloud
4 m (13 ft) in diameter anywhere in the volume.

c.

Small volumes that are mechanically ventilated may have gas detection at the ventilation
air outlet instead of inside the volume if the volume has the following characteristics:

d.

7.2.3.

7.2.4.

1.

Contains a source of release.

2.

Has normal air change rate greater than 60 air changes per hour.

In very small enclosures, defined as less than 100 m3 (3 500 ft3), the minimum number of
detectors may be set by either of the following:
1.

Special automatic action requirements.

2.

Voting philosophy for the facility.

Large fully enclosed volumes

a.

Large fully enclosed volumes shall be defined as greater than 1 000 m3 (35 000 ft3).

b.

Large fully enclosed volumes may have explosion protection in the form of inerting
systems.

c.

If explosion protection is installed, detection shall be required of a spherical gas cloud 5 m


(16 ft) in diameter anywhere in the volume.

d.

If explosion protection is not installed, detection shall be required of a spherical gas cloud
4 m (13 ft) in diameter anywhere in the volume.

Large partially enclosed volumes

a.

Large partially enclosed volumes shall be defined as:


1.

Greater than 1 000 m3 (35 000 ft3).

Page 20 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

2.
b.
7.2.5.

Having a blockage ratio greater than 0,3.

Large partially enclosed volumes shall have detection of a spherical gas cloud 5 m (16 ft)
in diameter anywhere in the volume.

Open volumes

a.

For large open volumes with congested parts having a blockage ratio less than 0,3,
detection of a spherical gas cloud 10 m (33 ft) in diameter anywhere in the volume shall be
required.

b.

For large open areas that contain pockets with a blockage ratio greater than 0,3, detection
of a spherical gas cloud of 5 m (16 ft) in diameter anywhere within the pocket shall be
required.

c.

Perimeter detection may be used in place of volumetric detection for large open volumes if
the following conditions are present:
1.

The volume has no congested parts with a blockage ratio greater than 0,3.

2.

The hazard of concern is migration of gas to other areas.


Perimeter detection would normally be used in onshore facilities such as gas
terminals or oil refineries. Perimeter detection would not normally be used in
offshore installations because migration of gas from the installation is not usually a
hazard.

d.
7.2.6.

If the flammable gas is also toxic, more local detection may be required at onshore
facilities.

Liquid phase releases

a.

Low-level detectors (for heavy gas hazards) should be installed in areas that contain
inventories of process fluids, which if released to atmosphere, would remain in liquid state
for a significant period.

b.

Low-level detectors shall be installed at no more than 0,5 m (1,6 ft) above local deck or
grade.

c.

Low-level detectors should be arranged on a 5 m (16 ft) triangular grid around potential
heavy gas release points.
A liquefied gas release can behave very differently from a vapour phase release.
First, less mixing occurs with the air. Second, the heat required to evaporate the gas
is often more than available from the surroundings, so released fluids remain liquid
for some time. The local gas cloud is therefore relatively dense and cold. This gas
or vapour tends to slump, especially in low air movement areas. Throughout the
length of the plume, gas at the outer edges is entrained into and carried away by
local air movement. At some point downwind, the whole plume may have warmed
sufficiently to "lift off" and be entrained in the ambient flow field.

7.2.7.

Leak detection

a.

Detection systems designed for detection of gas clouds large enough to potentially cause
damage from explosion overpressure shall not be relied upon for leak detection.
The gas detection requirements previously discussed in this section relate to
detection of gas clouds of a size that have the potential to cause damage from
explosion overpressure.

b.

A leak detection system may be installed in addition to, and not to replace in whole or in
part, a volumetric gas detection system where the fluid that could be released is in the
gaseous phase, and is at pressure of 10 barg (150 psig) or greater.

Page 21 of 45

29 January 2003

7.2.8.

7.3.

GP 30-85
Guidance on Practice for Fire and Gas Detection

Air intakes

a.

Enclosed volumes with no source of release, but which contain sources of ignition (for
example, accommodation blocks or electrical equipment rooms) shall require fast-response
gas detection at the air inlets to ensure that gas is prevented from entering an area
containing an ignition source. The passage of gas in the ducts should be stopped before it
crosses the boundary of the protected space.

b.

Total response time of detectors, control systems, and dampers should be:
1.

Shorter than the time needed for gas to reach the area boundary after passing the gas
detector.

2.

Verified by site measurement.

Gas detection control actions


a.

Automatic control actions from gas detection should be targeted for the hazard they are
protecting against in each area.

b.

Manual response to gas alarms that can be demonstrated to be sufficiently effective is


preferred to automatic systems.
It is important to target automatic control actions from gas detection, rather than to
use a blanket approach for the facility. For example, detection of gas at a
ventilation air intake to a building cannot be used to infer the formation of an
explosion hazard in adjacent process areas.

7.4.

Gas detection voting


a.

If anticipated loss from unwanted response by detection equipment (false control action) is
unacceptable, voting logic should be used for automatic control actions.

b.

If detectors on BP facilities have had satisfactory reliability for a number of years, then
they need not be voted.

c.

Infrared gas detectors may be used in 1ooN, 1oo2d, or 2ooN voting configurations.

d.

Detectors in 1ooN mode should:

e.

1.

Alarm if any single device reaches 20% of scale.

2.

Prompt automatic control actions at 60% of scale.

Detectors in 1oo2d mode should:


1.

Alarm if any single device reaches 20% of scale.

2.

Prompt automatic control actions if two devices reach 20% of scale.

f.

If any detectors in the 1oo2d voting group are in fault (including beam block), this detector
shall count as one device at 20% of scale in terms of voting logic.

g.

Detectors in 2ooN mode should:


1.

Alarm if any single device reaches 20% of scale.

2.

Prompt automatic control actions if two devices reach 20% of scale.

h.

Detector faults shall not be included in voting logic for automatic control actions in 2ooN
configurations.

i.

Whether to use 1oo2d or 2ooN voting logic should be determined by the availability
requirements of the system.
For open path gas detectors, little benefit is gained in having two levels of alarm,
because their range is usually limited to a small band of 0 LELmetres to

Page 22 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

5 LELmetres, and gas can be present up to 100% by volume. The difference between
20% and 60% of scale is roughly the difference of 2% by volume for the gases
commonly encountered at BP facilities. Two levels of alarm should be retained on
1ooN systems as a preliminary alarm that may be used to announce the onset of
detector failure.

8.
8.1.

Toxic gas detection performance


General
a.

Safe working practices constitute the primary protection of personnel from toxic gases.

b.

The threat to personnel from toxic gas shall be clearly identified and recorded along with
the working practices for keeping personnel safe.

c.

If toxic gas detectors are installed, their role and performance shall also be documented to
ensure that personnel do not rely on these devices for overall safety.
This is because some toxic gas detection devices are suitable for detecting leaks in
lethal service chemicals, but are not sensitive enough to detect the lower exposure
limit concentrations for personnel protection.

d.

Table 7 summaries exposure limits for the more common toxic gases encountered at BP
facilities in the UK and USA. The table should be a guide for other locations unless stricter
national requirements apply.
Table 7 - Exposure limits for common toxic gases
COSHH (UK)
Toxic gas

STEL (ppm)

OSHA (USA)

TWA (ppm)

STEL (ppm)

TWA (ppm)

CO

200

30

400

35

CO2

15 000

5 000

30 000

10 000

H2 S

15

10

15

HCN
HF

4.7
3

N/A

10
N/A
3

Note:
STEL Short-term exposure level.
TWA Time-weighted average.

8.2.

8.3.

Carbon monoxide
a.

Fixed carbon monoxide (CO) detectors may be installed in enclosed spaces where
personnel are present and there is a threat to them from machinery exhaust fumes
inadvertently being leaked into the area.

b.

Detectors should be placed where personnel are present during normal operations
(designated entrances, exits, and walkways).

c.

Detectors should alarm at the TWA (time-weighted average) threshold defined by local
legislation or guidance.

d.

The rationale for detector placement shall be clearly documented to allow system audits.

e.

Use of carbon monoxide detectors shall not detract from the need for formal working
practices to protect personnel from CO hazard.

Carbon dioxide
a.

If the threat to personnel is from machinery exhaust fumes, CO detectors should be used
rather than CO2 detectors, because CO is the primary toxin.

Page 23 of 45

29 January 2003

8.4.

8.5.

8.6.

9.

GP 30-85
Guidance on Practice for Fire and Gas Detection

b.

If CO2 may be a threat to personnel without CO being present, CO 2 detectors may be used.

c.

Detectors should be placed where personnel are present during normal operations
(designated entrances, exits, and walkways).

d.

Detectors should alarm at the TWA threshold defined by local legislation or guidance.

e.

The rationale for detector placement shall be clearly documented to allow system audits.

f.

Use of these detectors shall not detract from the need for formal working practices to
protect personnel from CO and CO2 hazard.

Hydrogen sulphide
a.

If flammable gas detection using infrared technology is installed, it may be used to infer
H2S concentration if the hydrocarbon gas content in any release is at least 1 000 times the
H2S content.

b.

Detectors should be placed where personnel may be present during normal operations
(designated entrances, exits, and walkways).

c.

Detectors should alarm at the TWA threshold defined by local legislation or guidance.

d.

The rationale for detector placement shall be clearly documented to allow system audits.

e.

Use of detectors shall not detract from the need for formal working practices to protect
personnel from H2S hazard.

Hydrogen cyanide
a.

Fixed hydrogen cyanide (HCN) detectors should be installed in enclosed spaces where
there is a threat to personnel and personnel are present.

b.

Detectors should also be placed where personnel may be present during normal operations
(designated entrances, exits, and walkways).

c.

Detectors should alarm at the TWA threshold defined by local legislation or guidance.

d.

The rationale for detector placement shall be clearly documented to allow system audits.

e.

Use of these detectors shall not detract from the need for formal working practices to
protect personnel from HCN gas hazard.

Hydrogen fluoride
a.

Fixed hydrogen fluoride (HF) detectors should be installed in enclosed spaces where there
is a threat to personnel and personnel are normally present.

b.

Detectors should also be placed where personnel may be present during normal operations
(designated entrances, exits, and walkways).

c.

Detectors should alarm at the TWA threshold defined by local legislation or guidance.

d.

The rationale for detector placement shall be clearly documented to allow system audits.

e.

Use of these detectors shall not detract from the need for formal working practices to
protect personnel from HF gas hazard.

Safe havens
a.

Safe havens (also called temporary refuges) shall be defined as areas where personnel
muster in an emergency.
Safe havens have special detection requirements.

Page 24 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

b.

The time that personnel are required to stay in these areas shall be based on the type of
emergency.

c.

In terms of F&G detection, performance targets shall be specific to the conditions of the
facility and shall consider the time that personnel are expected to remain within the safe
haven.

d.

Performance targets should be set in accordance with the BP smoke and gas ingress
analysis procedure, if available.

10. Detector type selection


10.1.

General
a.

Detectors shall be selected to detect the appropriate hazard.

b.

Detectors shall be capable of detecting hazards as they occur on the site especially
considering onsite sources that will affect device detection performance.
Detector performance can be adversely affected by common contaminants on a site
or by radiation sources, such as a hot process plant.

c.

Consideration shall be given to sources on the site that could cause the detector to false
alarm.

d.

Detector types and use shall comply with GIS 30-851.

10.2.

Flame

10.2.1.

General

10.2.2.

a.

The preferred method of fire detection shall be optical flame detection in the majority of
hydrocarbon fire risk applications (Grade A, Grade B, and Grade C).

b.

Equipment should detect fires specific for the fuel types that are located in the areas
detection is covering.

c.

Facility-specific contaminants and interfering sources that can affect the detectors ability
to see the fire or affect detector false alarm immunity shall be considered.

d.

Selection process should be formally documented to allow future audits.

Closed circuit television

a.

Closed circuit television (CCTV) flame detectors may be used at facilities that process
hydrocarbon gas or liquids.

b.

In applications where other optical flame detection systems do not perform satisfactorily
due to excessive false alarms from reflections of process flares (for example, top deck
process areas on offshore platforms), CCTV systems may be used.
CCTV systems, developed for these situations, continually and automatically
process video signals, testing for a suspected fire. On detection, the system
automatically alarms and displays a video image of the area in the control room.

10.2.3.

c.

CCTV devices may be used for detection of gas and liquid hydrocarbon fires.

d.

CCTV devices should not be used for invisible fires from methanol or hydrogen.

Infrared

a.

Infrared (IR) flame detectors may be used on facilities that process hydrocarbon gas or
liquids.

Page 25 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

b.

Preferred infrared devices shall be single frequency with advanced signal processing
operating in the middle IR region of the spectrum (4,3 microns), rather than
multiwavelength devices.

c.

IR detectors should not be used in areas where flare radiation can be seen, either directly or
reflected.
Infrared flame detectors are suitable for all gas and liquid hydrocarbon fires. Fires
of other fuels (such as hydrogen) may be impossible for the sensors to see. Other
fuels, such as methanol, may be seen but very poorly. All IR flame detectors are
affected to some extent by background blackbody radiation sources in their field
of view (hot plant site, people, the sun, etc.). Some detectors suffer reduced
sensitivity while others give false alarms, especially if the source appears to flicker.

10.2.4.

Ultraviolet

a.

Ultraviolet (UV) flame detectors may be used at facilities where the only fuel sources are
hydrogen or hydrocarbon gas.

b.

UV detectors are unsuitable for detection of hydrocarbon liquid fires and shall not be used
for such applications.

c.

UV detectors shall not be used in areas where flare radiation can be seen, either directly or
reflected.
UV detectors can see clean burning gas fires, including hydrogen fires. If clean
burning fire is the only hazard in the area, UV detectors may be used, but they are
best located well below roof level in case smoke is given off from other materials
(for example, paint or cables). Using UV detectors with hydrocarbon liquid fires
presents two problems: the fires can emit very little UV, and smoke absorbs UV.

10.2.5.

Combined ultraviolet and infrared

Combined UV/IR detectors are not recommended for general use.


Combined UV/IR devices operate in two modes: UV and IR, or UV or IR. The
UV and IR mode requires detection of both wavebands before a shutdown signal
is given. Some devices give a preliminary alarm on detection of only one waveband.
The purpose is to reject unwanted alarms, because few sources emit as strongly as
clean fires in both spectral regions. Such devices may be beneficial if fires can only
be clean burning, if they emit IR and UV, and if the windows of the detectors can be
kept scrupulously clean.
10.3.

Gas

10.3.1.

General

a.

Unless infrared is not suitable for the gas types to be detected, the infrared detectors shall
be preferred for detecting gas.

b.

Infrared gas detectors should not be used to detect gases that have no infrared absorption
characteristics (for example, hydrogen).
Infrared gas detectors are suitable for detection of a large range of gases, including
alkanes that are commonly found in BP facilities. However, gases that have no
infrared absorption characteristics (for example, hydrogen) are also found in BP
facilities.
Be aware that any plastic obstructions in the beam path are seen by infrared
detectors as hydrocarbons.

Page 26 of 45

29 January 2003

10.3.2.

GP 30-85
Guidance on Practice for Fire and Gas Detection

c.

The preferred gas detection method for applications where clear paths exist shall be open
path gas detectors, rather than point gas detectors.

d.

Open path gas detectors based on infrared absorption should be used for:
1.

Detection of gas clouds with explosion potential.

2.

Perimeter monitoring of large onshore facilities.

Catalytic bead

a.

Catalytic bead gas detectors should not be used for general use. They should be used only
in applications where other technologies do not detect the target gases.
Catalytic bead gas detectors have poor availability and response time. These
devices have many undetected failure modes, such as catalyst poisoning and
blockage of the sintered flame arrester.

b.
10.3.3.

Catalytic bead gas devices are suitable for use in clean areas where hydrogen detection is
required.

Electrochemical cell

a.

Electrochemical cell devices may be used for the detection of toxic gases.

b.

Due to the poor availability and undetected failures, electrochemical cell devices shall not
be relied upon for personnel safety.
At this time, there are no practical optical toxic gas detectors available for use in
the intended range of applications.

10.3.4.

Point infrared

Point infrared gas detectors may be used:

10.3.5.

1.

Space or congestion prohibits the use of open path gas detectors.

2.

Detection of spot flammability at a particular location is required.

Open path

a.

Open path detection systems using separate transmitters and receivers shall be preferred to
combined transmitters/receivers using reflector panels.

b.

Open path devices with diagnostics that prevent poorly installed and commissioned
systems from going online should be used.
The main role of such instruments is to monitor the level of gas hazard in an area.
Their integrating method of measurement makes them more suited to indicate the
presence of explosion hazards than point devices that only measure local
flammability.

10.3.6.

Sensitivity

Gas detector specification should ensure that gas detection is such that a hazard is never
underestimated. This objective requires a detailed knowledge of:

10.3.7.

a.

Gas mixtures that may be released.

b.

Limits of flammability of the gases.

c.

Response characteristics of the selected detector technology.

Ultrasonic

a.

Ultrasonic gas leak detection shall be used only in addition to a volumetric gas detection
system.
Page 27 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

b.

Ultrasonic gas leak detection shall not replace a volumetric gas detection system in whole
or in part.

c.

Use of time delays should be minimised and should never exceed 30 seconds.

d.

Background ultrasonic levels within the detection area should be mapped to determine:
1.

Alarm threshold.

2.

Number and spacing of detectors.

10.4.

Heat

10.4.1.

General

Heat detection may be used if one of the following conditions is present:


1.

Other forms of detection are not suited to detection of the hazards.

2.

Other forms of detection would have unacceptable false alarm rates.


Heat detectors are less sensitive than other fire detection technologies, and on this
basis their use is generally discouraged. There are some applications (for example,
turbine enclosures) that have a relatively small volume to be protected, where heat
detectors are acceptable.

10.4.2.

Pneumatic

a.

b.

Pneumatic tube, frangible bulb, and fusible plug systems may be used for either of the
following applications:
1.

If direct control of firewater deluge valves is required to cover specific areas of the
facility.

2.

General area coverage.

If used as a backup to flame detectors, the sensitivity of the system may be an order of
magnitude less than the automatic control action threshold set for the flame detection
system.
Pneumatic systems are pressurised so that if the fire detecting element is ruptured,
the pressure quickly falls, causing the deluge valve to open and the transmitter to
alarm and possibly take control action. Instrument air is supplied through a filter
regulator and a small, variable restriction orifice. Flow of makeup air into the tube
is just sufficient to maintain a pressure transmitter above its alarm setting and to
compensate for minor leakage from fittings. Tube and bulb systems suffer false
alarms from mechanical damage.

10.4.3.

Electrical linear

Electrical linear heat detection may be used for either of the following applications:
a.

If coverage of specific areas of the facility is required.

b.

General area coverage.


Electrical linear heat detectors have two types: those that respond to an average
temperature along their length, and those that respond to the highest temperature at
a point along their length. Both types have a factory preset response threshold and
produce an alarm-only output. These systems have not generally been used at BP
hydrocarbon handling facilities.

10.4.4.

Optical linear

Optical linear heat detection may be used for either of the following applications:

Page 28 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

a.

If coverage of specific areas of the facility is required.

b.

General area coverage.


Optical linear heat detection uses a property (Ramman scattering) of a type of
optical fibre that changes with temperature. A sophisticated control system can
monitor the temperature at any point along the fibre. Available versions shield the
fibre for most of its length, removing the shielding at specific points where a heat
collector is coupled to the fibre. This effectively turns the system into a string of
point heat detectors. These systems offer the advantage of continuous analogue
readings from a large number of points, but have little practical value in most BP
applications where the requirement is usually to detect the presence of fire, rather
than absolute temperature measurement.

10.4.5.

Point devices

a.

Point heat detection should only be used in special applications where flame or smoke
detection is not appropriate.

b.

Bimetallic strips may be used in situations such as turbine enclosures or ventilation ducts
for turbines.n bnb

c.

Electronic types (thermistors) may be used where aesthetics is a primary consideration (for
example, in accommodation areas).
Several types of point heat detector are available, based on technologies like
bimetallic strips, IR sensors, and thermistors. Bimetallic devices can respond at a
factory set temperature and can incorporate an additional trip on a high rate of rise
in temperature, again preset by the manufacturer. The electronic types (thermistors,
etc.) are generally less reliable, more expensive, and more complex. They are
generally used only if aesthetics is a primary consideration.

10.5.

Oil mist
a.

Oil mist detectors should be used in areas where the fire may be preceded by a release of
high-pressure flammable liquid, such as diesel or lubrication oil.

b.

Oil mist detectors should be used in machinery spaces or turbine exhaust ducts.
Oil mist detectors are essentially optical obscuration instruments operating on
principles similar to open path smoke detectors. They are particularly useful in
engine enclosures for indicating the release of high-pressure fuel or lubrication oil,
which can lead to particularly aggressive and damaging fires. If the oil mist ignites,
the instrument doubles as an optical smoke detector.

10.6.

Smoke

10.6.1.

General

The following shall be considered in the selection of smoke detection equipment:


a.

Smoke detection technologies fall into two categories:


1.

The more frequently used devices designed to comply with the sensitivity levels set
out in national and international standards.

2.

Other devices designed to operate outside this sensitivity band.


A number of smoke detection technologies are available.

b.

High-sensitivity smoke detectors are of two basic types:


1.

Aspirated optical systems.

2.

Addressable point optical systems.


Page 29 of 45

29 January 2003

c.
10.6.2.

GP 30-85
Guidance on Practice for Fire and Gas Detection

Less sensitive smoke detection systems are available for special applications. These smoke
detection systems are tuned to the level of smoke that affects human life.

Aspirating systems

a.

High-sensitivity aspirating smoke detectors should be used in Grade E areas.


One type of high-sensitivity aspirating smoke detector is known as VESDA.
VESDA stands for Very Early Smoke Detection Apparatus, and is a registered
trademark of Vision Systems. Mention of the VESDA name in this GP should not be
inferred as a preference for this product over other similar aspirating type systems
(for example, Kidde Analazer).

b.

High-sensitivity aspirating type smoke detector systems should be designed to function


both with and without the HVAC system running.
High-sensitivity aspirating type smoke detectors are normally used to monitor
extracted air from rooms containing high-criticality electrical or electronic
equipment. Their sensitivity is adjustable, and at maximum is far higher than BP
requires.

c.

The efficiency of the system is dependent on the design of the sampling system and should
be checked on commissioning, using a standard test. Thereafter, testing, calibration, and
maintenance shall be performed onsite.

d.

Point-type devices should not be used in Grade E areas.


Point-type devices are discouraged because they are generally more difficult to
engineer and can be significantly affected by local environment variations. Their
overall cost of installation and ownership is generally higher.

10.6.3.

Closed circuit television

Closed circuit television (CCTV) may be considered in areas that are normally unattended and
where manual response would take too long to prevent losses or allow facility restart.
CCTV smoke detectors require good lighting to see smoke. These devices are not as
sensitive as aspirating systems, because they operate by detecting visible smoke.
10.6.4.

Ionisation

a.

Ionisation smoke detectors may be used in Grade F or Grade V areas, if the concern is
property protection.

b.

Ionisation smoke detectors shall not be used in sleeping areas.


Ionisation smoke detectors are not suited to sleeping areas, because they may not
detect a fire in time to save the lives of personnel in the room. They may be used to
detect fire in some equipment spaces (depending on the ventilation), but not for
highly critical electrical or electronic equipment. These detectors are sensitive to
gas and liquid hydrocarbon fires, but not robust enough to be used in plant areas.
They are suited to monitoring air intake ducts if their slow response time is
acceptable. They may be too sensitive for some applications.

10.6.5.

Point optical

a.

High-sensitivity point type smoke detectors should be used in Grade D areas for the
protection of sleeping personnel.

b.

High-sensitivity point type smoke detectors may be combined with other detection
techniques for the protection of sleeping personnel.

c.

Standard sensitivity point type optical smoke detectors may be used in Grade F areas.

Page 30 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

Optical smoke detectors are a less sensitive option than ionisation types for smoke
generated by electrical fires. Detectors are available in combinations of detection
technology. Generally, these devices have similar sensitivity to ionisation types for
detection of most fires, while retaining improved performance for detection of
electrical fires.
10.6.6.

Open path

Open path smoke detectors should be used in one of the following:


a.

Large open areas (Grade F) where point detectors would be difficult or expensive to
deploy,

b.

Grade V applications for personnel protection.


These are essentially obscuration monitors. Anything that reduces the intensity of
light (near IR) in the path of the beam alarms at a given level. A particularly rugged
version of the obscuration detector, developed from an exhaust stack analyser, is
used in ventilation ducts to detect when the level of smoke in the air reaches the
limit of breatheability for one hour. This is particularly valuable in safe haven
(temporary refuge) applications where the survival of personnel depends on
maintaining pressurisation of the refuge.

11. Detector deployment


11.1.

General
The following shall be considered in deploying detectors:
a.

Correct installation and orientation of detection equipment is critical to reliable


performance.

b.

Mounting arrangements should ensure correct operation even in the presence of vibration
of the supporting steelwork.

c.

Maintenance access should be considered. Flame detectors should be placed between 3 m


(10 ft) and 4 m (13 ft) above local deck or access platform.
The 3 m (10 ft) and 4 m (13 ft) distance above local deck or access platform was
determined from reviewing the practice across a number of BP facilities. In these
facilities, it has been allowable for personnel to access equipment at these
elevations from portable ladders, rather having to use temporary structures such as
scaffolding. In practice, placing the detectors lower than 3 m (10 ft) above local
deck or access platform means that they have more restricted views and therefore
more detectors are required to achieve the same level of coverage.

11.2.

11.3.

Flame
a.

Flame detector deployment should be optimised using computer-aided coverage


assessment tools.

b.

If computer-aided coverage assessment tools are not used, drawings should be required to
show the intended coverage of each detector, including overlapping voting coverage.

c.

The maximum distance from detector to the item or area requiring coverage shall be set
after considering the fire size and fuel type, and any desensitising effects from local
conditions.

Gas
a.

Gas detector deployment should be optimised using computer-aided coverage assessment


tools.

Page 31 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

b.

If computer-aided coverage assessment tools are not used, drawings should be used that
show the intended coverage of each detector, including overlapping voting coverage.

c.

If areas are assessed as having explosion potential, detectors should be installed to ensure
that a cloud of given size and concentration cannot exist without encompassing at least one
detector or detection path.

d.

Maintenance access should be considered. Gas detectors should be placed between 3 m


(10 ft) and 4 m (13 ft) above local deck or access platform.

e.

Open path gas detectors should be installed in locations where their paths will not be
interrupted by routine operations.
In practice, placing open path detectors lower than 3 m (10 ft) above local deck or
access platform will result in frequent blockage of the paths by personnel carrying
out routine operations. These interruptions cause unnecessary nuisance fault
indications at the control point.

11.4.

f.

Low-level gas detectors aimed at detecting heavy gas hazards should be located no higher
than 300 mm (1 ft) above local deck or grade.

g.

Elevation of toxic gas detectors shall be specified based on their intended role and the
nature of gases in the intended installation.

Heat
a.

Heat detectors in Grade F areas should be installed in accordance with national guidance.
If no national guidance is available, NFPA 72 should be used to determine detector
deployment.

b.

If pneumatic tubing is used in Grade A or Grade B applications, detection tubing should be


installed local to the protected facility areas, and at the required spacing for detection of
the target fire sizes.
For example, to detect a fire of 50 kW RHO, the tubing would need to be installed
so that all areas of the protected site are within 2 m (6 ft) of a detection tube.

c.
11.5.

11.6.

Pneumatic detection tube shall be protected from accidental damage (for example, with an
inverted cable tray).

Oil mist
a.

Oil mist detectors may be installed in Grade F, Grade T, or Grade V areas.

b.

In Grade F areas, they should be installed in accordance with national guidance. If no


national guidance is available, NFPA 72 should be used to determine detector deployment.

c.

In Grade T areas, oil mist detectors should be installed throughout the room on a 5 m
(16 ft) pitch along the longitudinal axis of the room, covering the main air exhaust streams,
or in areas with air change rates greater than 60 per hour, in the HVAC exhaust ducting.

d.

In Grade V areas, oil mist detectors should be installed in the air exhaust ducting.

Smoke
a.

Smoke detectors in Grade F areas should be installed in accordance with national


guidance. If no national guidance is available, NFPA 72 should be used to determine
detector deployment.

b.

Smoke detectors in Grade D or Grade E areas require special design to determine the
number and location of detectors, and detector sampling points.
The Vendor proprietary computer model should be used to establish base design.

Page 32 of 45

29 January 2003

c.

GP 30-85
Guidance on Practice for Fire and Gas Detection

In all smoke detector applications in Grade D or Grade E areas, the installed system shall
be tested using the tests specified in the grading.

12. Control and indicating equipment


a.

Detectors should be connected to suitable control and indicating equipment.

b.

Type and configuration of control and indicating equipment should be determined by


formal analysis.

c.

Control and indicating equipment shall comply with GIS 30-851.

d.

The safety integrity level (SIL) of the F&G detection functions shall be set in accordance
with GP 30-76.

e.

The SIL should be used to determine an appropriate F&G system configuration, including
interface to the shutdown system, in accordance with GP 30-80.
GP 30-80 covers requirements for choice of equipment, minimum architectures,
reliability, robustness, power supply, integration, installation, commissioning,
documentation and verification.

f.

The preferred detection systems for non-SIL-rated and SIL 1 applications shall be
addressable.

g.

Addressable detection systems should not be used at SIL 2 and above unless justified by
complying with the requirements of IEC 61508 in full as described in GP 30-80.

h.

Operator interfaces shall comply with GP 30-45.

13. Maintenance
a.

A maintenance strategy for the F&G system should be established in accordance with
GP 30-81 before commissioning the system. The strategy should define necessary
maintenance and testing based on:
1.

Location of the equipment and its environment.

2.

Failure modes.

3.

Performance targets.

b.

The strategy should include maintenance/testing frequencies for detection devices based on
Vendor recommendations or BP experience in similar applications, whichever provides the
longer period of time between service.

c.

Performance of the system should be monitored and annually reviewed for the need to
adjust the frequency of maintenance and testing routines. Maintenance shall comply with
GIS 30-851 and GP 30-81.
Logic systems with automatic testing should not normally require routine testing.
This may not be the case for higher SIL rated systems.

14. Audit and inspection


14.1.

General
a.

Systems should be audited against the agreed performance requirements and in accordance
with the verification activities in GP 30-75.

b.

As a minimum, audits should take place after any of the following:


1.

Installation of a new system.


Page 33 of 45

29 January 2003

c.

GP 30-85
Guidance on Practice for Fire and Gas Detection

2.

Major modification to a detection system.

3.

Major modifications to the monitored area.

Periodic audits should be conducted to ensure that the system complies with performance
requirements.
Normally, small changes are made to the location of F&G detectors during
construction to avoid conflict with pipework and cable trays. This fact is one reason
for the audit after installation.

14.2.

Audit criteria
a.

An independent auditor uses performance criteria that have been set for each part of the
F&G detection system in accordance with this GP.

b.

If these criteria are not already available, they should be prepared and agreed upon with
site management before the audit.

14.3.

System design review

14.3.1.

General

The purpose of design review is to ensure a design can comply with the performance
requirements if the system is correctly installed, operated, and maintained. Review techniques
vary according to the type of detector and the area covered.
General guidance on functional safety assessment including design review is
provided in GP 30-75.
14.3.2.

Flame detection

a.

14.3.3.

14.3.4.

The proposed layout and orientation of detectors shall be assessed for the following:
1.

To ensure the coverage footprint is sufficient to provide the required hazard alarms
and control actions.

2.

To ensure detector views are not impeded by pipework, cable trays, or other
obstructions.

b.

Assessment should use computer-aided assessment software developed for this purpose.

c.

The effective range of selected detectors should consider the expected environment, with
the estimate based on test data.

d.

Manual mapping methods of flame detector coverage may be used, but these are generally
less accurate and more expensive to implement than computer-aided methods.

Heat and smoke detection

a.

Proposed layout and orientation of detectors shall be assessed to ensure that coverage is
sufficient to provide the required alarms and control actions for the specified hazards.

b.

Selection of detector types shall be checked for suitability to the hazards.

c.

Positioning of detectors shall be checked for the influence of expected air movement.

Combustible gas detection

a.

Proposed layout and orientation of detectors shall be assessed to ensure that a cloud or
plume of the specified size and concentration anywhere in the area shall be detected.

b.

Sensitivity of the instruments shall be checked to ensure that they do not underestimate
hazards arising from any mixtures of gases that may arise.

Page 34 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

14.4.

Installed equipment review

14.4.1.

General

a.

b.

The review should:


1.

Determine whether the installed F&G detection system is capable of complying with
the performance criteria.

2.

Cover selection of equipment, suitability, layout, positioning, and orientation.

Periodic checks may be required to ensure the performance criteria continue to be met.
Previously audited designs that have had no major modifications or changes in risk
should remain fit for purpose throughout the life of the site. Despite this fact,
equipment can fail to comply with performance criteria.

c.

14.4.2.

14.4.3.

Review guidelines for the review shall include the following steps:
1.

Visually inspect of the detection equipment and make a qualitative assessment of


whether detection coverage complies with design coverage requirements.

2.

Visually inspect the area of detection and control area for anything that might inhibit
the required output, or delay it beyond the required response time.

3.

If, after visual inspection, the auditor has doubts about the performance of the
detection system, tests should be performed to determine whether performance is
acceptable. Tests vary according to detector type and installation area characteristics.

Flame detection tests

a.

No practical, onsite fire tests are possible for this assessment. The audit tests shall be
inferential, as are those routinely used during maintenance.

b.

Audits should review the optical condition of detectors and their alignment.
1.

The current detector alignment view should be compared with an existing


photographic record of their optimum alignment.

2.

If a photographic record of the optimum alignment is not available, photographs


should be taken of the view from each detector. The photographs should be used to
assess coverage against performance requirements, using computer-aided assessment
software or a manual alternative.

Smoke detection tests

Smoke detectors performance depends to a great extent on their location with


respect to the sources of smoke and the air movement in the area.
If necessary to prove the performance of smoke detection systems, smoke tests should be
conducted in nonhazardous areas.
14.4.4.

Heat detection tests

Testing heat detectors arrangement onsite is not routine because of problems


associated with creating large volumes of very hot air.

14.4.5.

a.

Calibration of individual sensors may be checked by the same tests used in maintenance.

b.

Performance of the devices onsite can only be inferred from their location with respect to
their surroundings.

Combustible and toxic gas detection tests

Gas detection systems should be audited to ensure the detectors are in the required location, and
that maintenance ensures the required sensitivity.

Page 35 of 45

29 January 2003

14.5.

GP 30-85
Guidance on Practice for Fire and Gas Detection

Reliability and availability review


a.

System availability should be checked by reviewing the F&G system event log for detector
faults, inhibits, or overrides, and the maintenance history for equipment faults. This
information should be used to calculate system availability.

b.

If the F&G system has no event log, manual recording systems (for example, inhibit or
fault logs) shall be reviewed and the information should be used for input to the
availability calculations.

c.

Reliability calculations shall be performed, supported by actual record of detection


performance during testing and on real demands, to ensure that required performance is
achieved. Undetected failures should be assumed to occur half way through
maintenance/testing intervals.
GP 30-80 provides guidance in performing reliability calculations.

d.
14.6.

Appropriate actions should be taken to rectify shortfall in reliability or availability.

Personnel review
a.

Personnel working on the system (for example, technicians and control room operators)
shall be interviewed to appraise their skill, knowledge, and experience in their area of
responsibility in accordance with the requirements for competency in GP 30-75.

b.

Samples of each maintenance routine should be witnessed and checked for compliance
with the maintenance procedures.

c.

During sample maintenance routine checks, operators should be assessed for compliance
with the system operating procedures.

Page 36 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

Annex A
(Normative)

F&G detection performance record sheets

Page 37 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

Fire & Gas Detection Performance Targets Record Sheet


General Requirements
Sheet
Site:

Include name of site

Area:

of

Include name of area (can be all


areas)

Legislative Compliance

Include details of legislative requirements for F&G detection in this area.


Emergency Response

Include details of site manning levels in terms of how often personnel normally visit each area
and how long (in minutes) it takes from getting an F&G alarm to a response team reaching the
area.
Fire Detection (Hydrocarbon Handling Areas)
Assign Fire Risk Category

Carry out categorization as per section 4.3.4.3 recording the decision taken at each branch the
chart. Then assign default Grades below.
Grade

Fire Size (RHO) for Alarm

Fire Size (RHO) for Control


Action

Response Time

Include fire size in kW


RHO
Include fire size in kW
RHO
Include fire size in kW
RHO

Include fire size in kW RHO

Include in
seconds
Include in
seconds
Include in
seconds

B
C

Include fire size in kW RHO


Include fire size in kW RHO

Fire Detection (Non-Hydrocarbon Handling Areas)


Grade
D
E
F

Required Performance

Assign required performance from recognised standard for life protection.


Assign required performance from recognised standard for equipment protection.
Assign required performance from recognised standard for general areas.
Gas Detection

Gas Detection Requirements

Specify the role of the gas detection system in terms of either;


Detecting volumes of gas that could cause explosion
Detecting gas leaks.
Preventing gas ingress to non-classified areas
Detecting toxic gases.
Manual Alarm Stations
Define the role of Manual Alarm Stations.

Signature:
Prepared
By:
Date:

Signature:
Approved
By:
Date:

Page 38 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

Fire & Gas Detection Performance Targets Record Sheet


Fire Detection (Hydrocarbon Handling Areas)
Sheet
Site:

Include name of site

Area:

of

Include name of area

Hazard Description
Include discussion on fire hazards specific to this area.

Control Measures
Include discussion on fire control measures in this area including passive fire protection, active
fire protection and plant inventory isolation and depressurisation.

Grading
Grade
A

Description

List all Grade B items of plant in the area.

List all Grade C items of plant in the area.

List all Special Grade items of plant in the area.

Signature:
Prepared
By:
Date:

List all Grade A items of plant in the area.

Signature:
Approved
By:
Date:

Page 39 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

Fire & Gas Detection Performance Targets Record Sheet


Fire Detection (Non-Hydrocarbon Handling Areas)
Sheet
Site:

of

Include name of site

Hazard Description
Include discussion on fire hazards specific to each area.

Control Measures
Include discussion on fire control measures in this area including passive fire protection, active
fire protection and plant inventory isolation and depressurisation.

Grading
Space Description & Reference

Signature:
Prepared
By:
Date:

Fire Class

Ventilation

Grade

Signature:
Approved
By:
Date:

Page 40 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

Fire & Gas Detection Performance Targets Record Sheet


Gas Detection
Sheet
Site:

Area:

Include name of site

of

Include name of area

Hazard Description
Include discussion on fire hazards specific to this area.

Control Measures
Include discussion on fire control measures in this area including explosion suppression and
plant inventory isolation and depressurisation.

Hazardous Area Classification


Ventilation Type

Include details on any classified parts of the area


Natural or Mechanical

Area Boundary Blockage Ratios


Floor

Ceiling

North

South

East

West

Flammable Gas detection Requirements


Include target gas cloud size (s) and response time.
Specify maximum response time
Specify maximum response time
Specify leakage rate

Volumetric
Ventilation Air Intake
Ventilation Exhaust Duct
Leak Detection

CO
H2S
HCN
HF

Toxic Gas detection Requirements


Include detection aims, required sensitivity and response time.
Include detection aims, required sensitivity and response time.
Include detection aims, required sensitivity and response time.
Include detection aims, required sensitivity and response time.

Signature:
Prepared
By:
Date:

Signature:
Approved
By:
Date:

Page 41 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

Annex B
(Normative)

Test requirements for high-sensitivity smoke detection systems


B.1

General

B.1.1

Scope
This test method is suitable for the testing of high-sensitivity fire detection systems.

B.1.2

Fire simulation
To simulate the early stages of a fire, a length of wire is electrically overloaded so that smoke or
vapours are driven off.
Warning: Test produces sufficiently high temperatures to generate
small quantities of hydrogen chloride (HCl). The Threshold
Limit Value (TLV) for HCl is 5 ppm. Vapours given off by this
test shall be diluted to safe levels for personnel exposure
and safely disposed of by the ventilation system covering
the area of test. Should personnel at any time during the
test experience a burning sensation in the nose or throat,
coughing, or laboured breathing, the test should be stopped
immediately.

B.2

Test equipment
Test equipment shall include:

B.3

a.

1 m (3 ft) length of 10/0,1 mm (10/38 AWG) strands insulated with PVC to a radial
thickness of 0,3 mm (12 mils), the cross-sectional area of the conductor being 0,078 mm2
(120E6 in2).

b.

A transformer to operate on the local electricity mains supply capable of delivering at least
15A at 6V.

c.

An insulating board of noncombustible material of minimum size 600 mm (2 ft) x 600 mm


(2 ft).

d.

A stopwatch accurate to 1 s.

Test procedure
The test procedure shall consist of the following steps:
a.

Connect the wire to the 6V output terminals of the transformer.

b.

Ensure that the wire is laid on the insulating board so that there are no kinks or crossovers.

c.

Connect the mains electricity supply to the primary terminals of the transformer and switch
on follow-up period of 60 s.

d.

The detection system should respond within 120 s from the transformer being switched
off.

Page 42 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

Bibliography
[1]

BSI BS 5839 - Fire Detection and Alarm Systems for Buildings.

[2]

BSI BS 6266 - Fire Protection for Electronic Data Processing Installations.

[3]

ISO 10418 (draft 2003) - Petroleum and natural gas industries Analysis, design, installation, and
testing of basic surface process safety systems on offshore production installations Requirements
and guidelines.

[4]

ISO 13702 - Petroleum and natural gas industries Control and mitigation of fires and explosions on
offshore production installations Requirements and guidelines.

[5]

Methodology for Assessing Smoke and Gas Ingress to Accommodation and TR Volumes, by BP
Upstream Technology Group. Document Number: SPR/G/97/006, Issue 01, Issue Date: April 1997.

[6]

NFPA 30 - Flammable and Combustible Liquids Code.

[7]

Offshore Technology Report OTO 93 002 Offshore Gas Detector Siting Criterion, Investigation of
Detector Spacing (HSE, April 1993).

Page 43 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

Figure 1 - Method for setting fire detection requirements

RECORD ANY
LEGISLATIVE
REQUIREMENT FOR
FIRE DETECTION

REVIEW
OTHER
SAFETY
STUDIES

SET
DEFAULT
GRADINGS
A, B, C, D,
E, F, T, & V

NON-HC RISK
AREA

HC RISK AREA

TURBINE OR
MACHINARY
ROOM

VENTILATION
AIR INTAKE

ASSIGN GRADE B

ASSIGN GRADE F

SPECIAL RISK
Y

SUPPLY AIR TO
MANNED
AREA OR
CONTAIN
EQUIP

NO FIRE RISK
IDENTIFIED

IS GRADE B
NOT GOOD
ENOUGH

DO
PERSONNEL
SLEEP HERE

Y
IS GRADE B
Y

TOO GOOD

DOES
AREA CONTAIN
ESSENTIAL OR
HIGH VALUE
ELECTRICAL/
ELECTRONIC
EQUIP

ASSIGN GRADE A

ASSIGN GRADE C

ASSIGN GRADE E

ASSIGN GRADE T

NO FIRE DETECTION
REQUIRED
RECORD WHY NOT

LEAVE GRADE B

ASSIGN GRADE D

ASSIGN GRADE F

LEAVE GRADE V

ASSIGN GRADE S

Page 44 of 45

29 January 2003

GP 30-85
Guidance on Practice for Fire and Gas Detection

Figure 2 - Method for setting flammable gas detection requirements

RECORD ANY
LEGISLATIVE
REQUIREMENTS
FOR GAS
DETECTION

REVIEW
SAFETY
STUDIES FOR GAS
DETECTION
CLAIMS

IS AREA
CLASSIFIED
AS
HAZARDOUS

IS GAS
IS NATURAL

ANY HEAVY
GAS HAZARDS
IDENTIFIED

GAS MIGRATION
TO THIS AREA
CREDIBLE

INGRESS VIA
MECHANICAL
VENTILATION
AIR INTAKE
CREDIBLE

IS VOLUME FULLY
ENCLOSED

IS VOLUME
PARTLY
ENCLOSED

IS VOLUME
LESS THAN 1 000m3
(35 000ft3)

IS VOLUME
OPEN

IS FLOOR

IS
N

IS AIR
CHANGE RATE
MORE THAN 60
PER HOUR

EXPLOSION
SUPPRESION
FITTED

ANY CONFINED
POCKETS

NN

BASE AREA
DIMENSIONS
LESS THAN
10m (33ft)
Y

INSTALL LOW LEVEL


GAS DETECTORS ON
5m (16ft)
TRIANGULAR GRID

FIT AIR EXTRACT


GAS DETECTORS

DETECTION
REQUIREMENT
4m (13ft) DIAMETER
SPHERICAL CLOUDS

DETECTION
REQUIREMENT
5m (16ft) DIAMETER
SPHERICAL GAS
CLOUDS

DETECTION
REQUIREMENT
10m (33ft) DIAMETER
SPHERICAL GAS
CLOUDS

FIT AIR INTAKE


GAS DETECTORS

NO GAS DETECTION
REQUIRED.
RECORD WHY NOT

Page 45 of 45