6. Mounting hole of the expansion unit

13. DC power input

7. Nameplate

14. Expansion port

RS-485
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
CR
Register name
parameter Latched
#
Reserved
CH4
CH3
CH2
CH1
address
#15 H400F R present value of CH4 input signal
#18 H4012
R/W To adjust OFFSET value of CH1 Offset setting of CH1 ~ CH4.
#19 H4013
R/W To adjust OFFSET value of CH2 Factory setting is K0 and unit is LSB.
#20 H4014
R/W To adjust OFFSET value of CH3 Voltage input: setting range is K-4,000 ~ K4,000.
#21 H 4015
R/W To adjust OFFSET value of CH4 Current input: setting range is K-4,000 ~ K4,000.
#24 H4018
R/W To adjust GAIN value of CH1
GAIN setting of CH1 ~ CH4. Factory setting is K4,000 and
#25 H4019
R/W To adjust GAIN value of CH2
unit is LSB.
Voltage input: setting range is K-3,200 ~ K16,000.
#26 H401A
R/W To adjust GAIN value of CH3
Current input: setting range is K-3,200 ~ K10,400.
#27 H401B
R/W To adjust GAIN value of CH4
CR#18~CR#27: Please be noticed that GAIN value OFFSET value=+800 LSB ~ +12,000LSB (voltage) or +800 LSB ~
+6,400 LSB (current). If the value difference comes up small (within range), the output signal resolution is then slim and the
variation is definitely larger. On the contrast, if the value difference exceeds the range, the output signal resolution
becomes larger and the variation is definitely smaller.
It is the data register to save all error status.
#30 H401E R Error status
Please refer to error code chart for detail.

External Wiring
Voltage
-10V ~ +10V

5011671003-AD44

104.7K

CH1
V+
5

I+

250
104.7K

COM
FG

Isolation Wire 1

V+
I+
COM
FG
V+
I+
COM
FG

AG

~
~

Current Input

104.7K

CH4

-20mA ~ +20mA

V+
I+

CH4

250

V+
I+
COM
FG
V+
I+
COM
FG

104.7K

COM
FG

Isolation Wire 1

AG

terminal of
power module

DVP04AD-S

CH1

24+

DC/DC

System
Grounding

24-

Converter

+15V

Note 1: Please isolate analog input and other power wiring.


Note 2: If current signal is connected, please short out V+ and I+ terminals.
Note 3: If noise is significant, please connect FG to grounding.
Note 4: Please connect
terminal of power module and
terminal of analog input module to system earth point
and make system earth point be grounding or connects to machine cover.
Note 5: If noise interferes from loaded input wiring terminal is significant, please connect a capacitor with 0.1 ~ 0.47F
25V for noise filtering.
Warning: DO NOT wire to the No function terminal .

Specifications
Functions

Isolation method
Absolute input range
Digital data format
Average function
Self diagnose function
Communication mode
(RS-485)
Connect to DVP-PLC MPU
in series

Warning

ENGLISH

EN DVP04AD-S is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity,
electric shock and vibration. To prevent non-maintenance staff from operating DVP04AD-S, or to prevent an
accident from damaging DVP04AD-S, the control cabinet in which DVP04AD-S is installed should be equipped
with a safeguard. For example, the control cabinet in which DVP04AD-S is installed can be unlocked with a
special tool or key.
EN DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring
again before DVP04AD-S is powered up. After DVP04AD-S is disconnected, Do NOT touch any terminals in a
on DVP04AD-S is correctly grounded in order to prevent
minute. Make sure that the ground terminal
electromagnetic interference.
FR DVP04AD-S est un module OUVERT. Il doit tre install que dans une enceinte protectrice (boitier, armoire, etc.)
saine, dpourvue de poussire, dhumidit, de vibrations et hors datteinte des chocs lectriques. La protection
doit viter que les personnes non habilites la maintenance puissent accder lappareil (par exemple, une cl
ou un outil doivent tre ncessaire pour ouvrir a protection).
FR Ne pas appliquer la tension secteur sur les bornes dentres/Sorties, ou lappareil DVP04AD-S pourra tre
endommag. Merci de vrifier encore une fois le cblage avant la mise sous tension du DVP04AD-S. Lors de la
dconnection de lappareil, ne pas toucher les connecteurs dans la minute suivante. Vrifier que la terre est bien
afin dviter toute interfrence lectromagntique.
relie au connecteur de terre

Introduction
Model Explanation & Peripherals
Thank you for choosing DELTA PLC DVP Series. The analog input module receives external 4-point analog

Operation/storage
Vibration/shock immunity

DIN Rail Installation

Wiring

DVP04AD-S series can read/write the data of analog input module by using instructions FROM/TO via
< 1.5mm

DVP-PLC SS/SA/SX/SC/SV Series MPU program. There are 49 CR (Control Register, each register has
The software version of DVP04AD-S analog input module can be updated via RS-485 communication.
Users can select input from voltage or current via wiring. Voltage input range is 10VDC (resolution is

1.25mV). Current input range is 20mA (resolution is 5A).

Product Profile & Outline


4
1

3.00

25.20

5
60.0
0

V+
C
I+
H
COM 1
FG
V+
C
H
COM 2

3.4

6
7

11

3.00

10

12

FG

V+
C
I+
H
COM 3

14

13

FG
V+
C
I+
H
COM 4

FG

4.00

Unit: mm
1. Status indicator (POWER, RUN and ERROR)

8. Expansion port

2. Model name

9. Expansion unit clip

3. DIN rail clip

10. DIN rail (35mm)

4. I/O terminals

11. RS-485 communication port

5. I/O point indicator

12. Mounting rail of the expansion unit

90.00

#4
#5
#6
#7
#8
#9
#12
#13
#14

H4004
H4005
H4006
H4007
H4008
H4009
H400C
H400D
H400E

R/W
R/W

R
R
R
R
R
R
R

RS-485
CR
parameter Latched
#
address
Symbols:

Register name

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0


Reserved

CH4

CH3

CH2

CH1


14 DVP-PLC SS/SA/SX/SC/SV FROM/TO
49 CR (Control Register) 16 bits
DVP04AD-S RS-485

10VDC ( 1.25mV)
20mA ( 5A)


4
1

3.00

25.20

0
-10 V -6V

6V
GAIN

FG

-8,0 00

Voltage input

Reserved

CH4

CH3

CH2

CH1

90.00

V+
C
I+
H
COM 3

OFFSET:

Voltage input value when digital output is 0.


Setting range: -4,000LSB ~ +4,000LSB.

GAINOFFSET: Setting range is +800LSB ~ +12,000LSB.

Mode 3 of CR#1: GAIN=20mA (4,000LSB), OFFSET=0mA (0LSB).


GAIN:

0
4mA
OFFSET

20mA
GAIN

OFFSET:
-4,000

14

13

90.00

FG
V+

C
I+
H
COM 4

FG

4.00

mm

1.

8. /

2.

9. /

3. DIN

10. DIN (35mm)

4.

11. RS-485

5.

12. /

6. /

13.

7.

14. /

-10V ~ +10V

104.7K

CH1
V+

FG
CH4

-20mA ~ +20mA

AG

~
~

104.7K

V+

CH4

250

I+

V+
I+
COM
FG
V+
I+
COM
FG

104.7K

COM
FG

V+
I+
COM
FG
V+
I+
COM
FG

104.7K

COM

DVP04AD-S

CH1

250

I+

AG

24+

DC/DC

24-

+15V
AG
-15V

(100 )

2V+ I+

Voltage input value when digital output is 4,000.


Setting range is -3,200LSB ~ +16,000LSB.

Mode 2 of CR#1: GAIN=20mA (4,000LSB), OFFSET=4mA (800LSB).


Mode 2

Digital
output
-20mA -12mA

12

3 FG
4
DVP04AD-S

5 0.1 ~ 0.47F 25V


Mode 3

+4,000

10

FG

GAIN:

60.0
0

3.00

V+
C
I+
H
COM 2

Mode 0 of CR#1: GAIN=5V (4,000LSB), OFFSET=0V (0LSB).

10V

-4,000

11

C
H
COM 1

Mode 1 of CR#1: GAIN=6V (4,800LSB), OFFSET=2V (1,600LSB).


Mode 1
5V
2V

V+

Adjust A/D Conversion Characteristic Curve


Mode 0

3.4

I+

Explanation:

A. Communication baud rate: 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps.
B. Communication format: ASCII mode is 7 bits, even bit, 1 stop bit (7, E, 1), while RTU mode is 8 bits,
even bit, 1 stop bit (8, E, 1).
C. Function code: 03H - read data from register. 06H - write one word into register. 10H - write multiple
words into register.

5
60.0
0

W means can write data by using TO instruction or RS-485.


LSB (Least Significant Bit): 1. Voltage input: 1LSB =10V/8,000=2.5mV.
2. Current input: 1LSB =20mA/4,000=5A.

+4 ,000

means latched. means not latched. R means can read data by using FROM instruction or RS-485.

Current input mode:

Model type

CH3 average times


CH4 average times
Average value of CH1 input signal
Average value of CH2 input signal
Average value of CH3 input signal
Average value of CH4 input signal
present value of CH1 input signal
present value of CH2 input signal
present value of CH3 input signal

Communication address setting

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

I+

90.00

60.0

H4000

Digital
output

System used, data length is 8 bits (b7 ~ b0). DVP04AD-S


model code= H88. User can read the data from program to
check if there is expansion module.
Input mode setting: factory setting is H0000.
Mode 0: input voltage mode (-10V ~ +10V).
Mode 1: input voltage mode (-6V ~ +10V).
#1
H4001
R/W Input mode setting
Mode 2: input current mode (-12mA ~ +20mA).
Mode 3: input current mode (-20mA ~ +20mA).
Mode 4: none use.
CR#1: CR#1 is used to set 4 internal channels working mode of analog input module. Every channel has four modes to
set that can be set individually. For example: if set CH1 to mode 0 (b2 ~ b0 = 000), CH2 to mode 1 (b5 ~ b3 = 001), CH3:
mode 2 (b8 ~ b6 = 010), CH4: mode 3 (b11 ~ b9 = 011). Then CR#1 is set to H0688 and the upper bit (b12 ~ b15) will
reserved. The factory setting of CR#1 is H0000.
#2
H4002
R/W CH1 average times
Average times setting of channel CH1 ~ CH2.
Setting range is K1 ~ K4,096 and factory setting is K10.
#3
H4003
R/W CH2 average times
#0

R/W

b6
b5
b4
b3
b2
b1
b0
0
0
0
0
0
0
1
0
0
0
0
1
0
0
0
0
0
1
0
0
0
0
0
1
0
0
0
0
0
1
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
errors may happen at the same time. 0 means

Setting RS-485 communication address.


Setting range is 01 ~ 254 and factory setting is K1.
It is used to set communication baud rate (4,800, 9,600,
19,200, 38,400, 57,600, 115,200 bps). Communication
format: ASCII mode is 7 bits, even bit, 1 stop bit (7, E, 1),
while RTU mode is 8 bits, even bit, 1 stop bit (8, E, 1).
b0: 4,800 bps (bit/sec). b1: 9,600 bps (factory setting).
#32 H4020
R/W Communication baud rate setting
b2: 19,200 bps (bit/sec). b3: 38,400 bps (bit/sec).
b4: 57,600 bps (bit/sec). b5: 115,200 bps (bit/sec).
b6 ~ b13: reserved.
b14: exchange low and high byte of CRC check code (only
for RTU mode). b15: ASCII/RTU mode selection.
Factory setting is H0000.
Give CH1 setting for example:
1. When b0=0, user can set OFFSET and GAIN value of
CH1 (CR#18, CR#24). When b0=1, inhibit user to adjust
Reset to factory setting and set
#33 H4021
R/W
OFFSET and GAIN value of CH1 (CR#18, CR#24).
characteristics adjustable priority
2. b1 means if characteristic register is latched. b1=0
(factory setting, latched), b1=1 (not latched).
3. When b2 is set to 1, all settings will be reset to factory
setting.
CR#33 is used to set the internal function priority. For example: characteristic register. Output latched function will save
output setting in the internal memory before power loss.
In hexadecimal to display software version.
R Firmware version
#34 H4022
For example: H010A means 1.0A.
System used
#35 ~ #48
H401F

+8 ,00 0

1. Use 22-16AWG (1.5mm) single or multiple core wire on I/O wiring terminals. The
specification of the terminal is shown in the figure on the left hand side. The PLC
terminal screws shall be tightened to 1.95kg-cm (1.7 in-lbs).
2. DO NOT place the I/O signal wires and power supply wire in the same wiring duct.
3. Use 60/75C copper wires only.

Register name

Voltage input mode:

CR (Control Register)
RS-485
CR
parameter Latched
#
address

Power unit and module are separate. Size is small and easy to install.

For heat dissipation. Make


sure to provide a minimum
clearance of 50mm between
the unit and all sides of the
cabinet. (shown as below)

The DVP-PLC can be secured to a cabinet by using the


DIN rail that is 35mm high with a depth of 7.5mm. When
mounting the PLC on the DIN rail, be sure to use the end
bracket to stop any side-to-side motion of the PLC, thus
to reduce the chance of the wires being pulled loose. On
the bottom of the PLC is a small retaining clip. To secure
the PLC to the DIN rail, place it onto the rail and gently
push up on the clip. To remove it, pull down on the
retaining clip and gently pull the PLC away from the DIN
rail. Please see the figure on the right:

(OPEN TYPE) /
(: )

The corresponding parameters address H 4000 ~ H4022 of CR#0 ~ CR#34 are provided for user to read/
write data via RS-485.

Mounting Arrangements and Wiring Notes

signal input (voltage or current) and converts it into 14 bits digital signal. The analog input module of

Power specification
24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%), 2W, supply from external power.
Environment condition
1. Operation: 0C ~ 55C (temperature), 50 ~ 95% (humidity), pollution degree 2
2. Storage: -25C ~ 70C (temperature), 5 ~ 95% (humidity)
Standard: IEC61131-2, IEC68-2-6 (TEST Fc)/IEC61131-2 & IEC68-2-27 (TEST Ea)

Installation and Wiring

22-16AWG

16-bit) in each module.

Voltage input
Current input
24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)
4 channel/each module
10V
20mA
8,000
4,000
14 bits (1LSB=1.25mV)
13 bits (1LSB=5A)
> 200K
250
0.5% of full scale of 25C (77F). 1% of full scale during 0 ~ 55C (32 ~ 131F)
3ms channels
It has isolation between digital area and analog area. There is no isolation among
channels.
15V
32mA
2s complementary of 16-bit, 13 significant bits
Yes (CR#2 ~ CR#5 can be set and setting range is K1 ~ K4,096)
Upper and lower bound detection/channels
Modbus ASCII/RTU Mode. Communication baud rate of 4,800/9,600/19,200/
38,400/57,600/115,200. For ASCII mode, date format is 7 bits, even, 1 stop bit (7,
E, 1), while RTU mode, date format is 8 bits, even, 1 stop bit (8, E, 1). The RS-485
is disabled when the DVP04AD-S is connected in series with MPU.
If DVP04AD-S modules are connected to MPU, the modules are numbered from
0 7. 0 is the closest and 7 is the furthest to the MPU. 8 modules is the max and
they do not occupy any digital I/O points of the MPU.

Others
Max. rated consuming power

DVP DVP04AD-S 4

Error description
Content
b15 ~ b8
b7
Power source abnormal
K1 (H1)
0
Setting mode error
K4 (H4)
0
Offset/gain error
K8 (H8)
0
Reserved
Hardware malfunction
K16 (H10)
0
Digital range error
K32 (H20)
0
Average times setting error
K64 (H40)
0
Instruction error
K128 (H80)
1
Note: Each error code will have corresponding bit (b0 ~ b7). Two or more
normal and 1 means having error.

#31

CR#30: Error status value (see the table below)

AG
-15V

Class 3 Grounding
(100 or less)

Analog/Digital (4A/D) module


Power supply voltage
Analog input channel
Analog input range
Digital conversion range
Resolution
Input impedance
Overall accuracy
Response time

Current input

Current input value when digital output is +4,000.


Setting range is -3,200LSB ~ +10,400LSB.

/ (4A/D)

24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)

Current input value when digital output value is 0.


Setting range is -4,000LSB ~ +4,000LSB.

4 /

GAINOFFSET: Setting range is +800LSB ~ +6,400LSB.

The chart above is to adjust A/D conversion characteristic curve of voltage input mode and current input mode.
Users can adjust conversion characteristic curve by changing OFFSET values (CR#18 ~ CR#21) and GAIN
values (CR#24 ~ CR#27) depend on application.

(Voltage input)

(Current input)

10V

8,000

4,000

14 bits (1LSB=1.25mV)

13 bits (1LSB=5A)

200K

250

20mA

0.5% (25C, 77F)


1% (0 ~ 55C, 32 ~ 131F)

3ms

Average times setting of channel CH3 ~ CH4.


Setting range is K1 ~ K4,096 and factory setting is K10.

16 11 bits

Display average value of CH1 ~ CH4 input signal.


For example, if CR#2 (the average times of CH1) is 10, the
average of CH1 input signal is calculated every 10 times.

(CR#2 ~ CR#5 K1 ~ K4,096)

(RS-485)

ASCII/RTU (4,800/9,600/19,200/38,400/57,600
/115,200), ASCII 7 bits1 stop bit (7, E, 1)RTU
8 bits1 stop bit (8, E, 1) PLC
RS-485

Display present value of CH1 ~ CH4 input signal.

15V

32mA

/ (4A/D)

(Voltage input)

DVP-PLC

CR

(Current input)

0 7 8 I/O


24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%), 2W,

#34

H4022

#35 ~ #48

PLC

PLC

+4,000

1
5V

0
-10V -6V

3. 60/75C

-8,000

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0


CH3

CH2

H4001

R/W

+4,000

4mA
OFFSET

20mA
GAIN

CR#1
CH1 ~ CH4 CH1 0 (b2 ~ b0=000)CH2 1 (b5 ~ b3=001)CH3 2 (b8 ~
b6=010)CH4 3 (b11 ~ b9=011) CR#1 H0688 (b12 ~ b15)

R/W
R/W

#2

H4002

#3

H4003

#4

H4004

#5

H4005

R/W
R/W

#6

H4006

CH1

#7

H4007

CH2

#8

H4008

#9

H4009

10 10 CH1 ~ CH4
CH3
CH4

#12 H400C

CH1

#13 H400D

CH2

#14 H400E

CH3

#15

H400F

CH4

#18

H4012

#19

H4013

#20

H4014

#21

H4015

#24

H4018

#25

H4019

#26 H401A
#27 H401B

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W

CH1

CH1 ~ CH2 K1 ~ K4,096


K10

CH2

CH3

CH1 ~ CH4

CH1 ~ CH4

CH1 OFFSET
CH2 OFFSET
CH3 OFFSET

CH1 ~ CH4 OFFSET K0 LSB


K-4,000 ~ K4,000

GAINOFFSET +800LSB ~ +6,400LSB

(OPEN TYPE) /
:

49 CR (Control Register) 16 bits


DVP04AD-S RS-485

K-3,200 ~ K10,400

10VDC ( 1.25mV)

b15 ~ b8

b7

b6

b5

b4

b3

b2

b1

b0

K4 (H4)

O/G

K8 (H8)

K16 (H10)

K32 (H20)

K64 (H40)

K128 (H80)

3.00

25.20
V+
C
I+
H
COM 1
FG
V+
C
H
COM 2

3.4

6
7

11

10

12

FG

90.00

H4020

R/W

(Baud
rate)

FG

K4 (H4)

O/G

K8 (H8)

K16 (H10)

/ (4A/D)

(Voltage input)

(Current input)

24VDC (20.4VDC ~ 26.4VDC) (-15% ~ +10%)


4 /
10V

20mA

8,000

4,000

14 bits (1LSB=1.25mV)

13 bits (1LSB=5A)

200K

250

0.5% (25C, 77F)


1% (0 ~ 55C, 32 ~ 131F)
3ms

15V

/
/

35mm DIN
PLC PLC
PLC PLC

PLC

K128 (H80)

b0 ~ b7 0 1

#31 H401F

R/W

RS-485 01 ~ 254 K1

4,800, 9,600, 19,200 bps, 38,400 bps, 57,600 bps,


115,200 bps ASCII 7 bits1 stop bit (7, E,
1)RTU 8 bits1 stop bit (8, E, 1)

R/W

(Baud
rate)

b04,800 bps (/)b19,600 bps (/) ()


b219,200 bps (/)b338,400 bps (/)
b 457,600 bps (/)b 5115,200 bps (/)
b6 ~ b13b14CRC ( RTU )
b15ASCII/RTU
CH1

#33 H4021

1. b0 1 CH1 CR#18, CR#24 b0


0 CH1 CR#18, CR#24

2. b1 b1=0 (
)b1=1 ()

R/W

3. b2 1

22-16AWG

H4000

90.00

H4001

R/W

#34 H4022

16 1.0A H010A

#35 ~ #48

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

CH4
CH3
CH2
CH1

O R FROM RS-485
W TO RS-485
LSB (Least Significant Bit) 1.1LSB =10V/8,000=1.25mV
2.1LSB =20mA/4,000=5A

+8,000

b04,800 bps (/) b19,600 bps (/) ()

3. DIN

10. DIN (35mm)

#3

H4003

b219,200 bps (/) b338,400 bps (/)

4.

11. RS-485

#4

H4004

#5

H4005

5.

12. /

#6

H4006

CH1

#7

H4007

CH2

#8

H4008

#9

H4009

CH1 ~ CH4
10 10 CH1 ~ CH4
CH3

CH4

#12 H400C

CH1 CH1 ~ CH4

CH1
CH1 ~ CH4 K1 ~ K4,096
K10

6V
10V

CR#1 1 GAIN=6V (4,800LSB), OFFSET=2V (1,600LSB).


GAIN

OFFSET GAIN

R/W
R/W
R/W
R/W

1
5V
2V

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

CH4
CH3
CH2
CH1
8 (b7 ~ b0)DVP04AD-S = H88

H0000
0 (-10V ~ +10V)
1 (-6V ~ +10V)
2 (-12mA ~ +20mA)
3 (-20mA ~ +20mA)
4

CR#1 0 GAIN=5V (4,000LSB), OFFSET=0V (0LSB).

+4,000

-10V -6V

H4002

CH3

1)RTU 8 bits1 stop bit (8, E, 1)


3. (Function)03H 06H word 10H words

#2

CH2

2. Modbus ASCII /RTU ASCII 7 bits1 stop bit (7, E,

1. / 22-16AWG (1.5mm)
PLC 1.95 kg-cm (1.7Ib-in)
2.
3. 60/75C

DVP04AD-S

#0

CR RS-485

A/D

9. /

2. b1 b1=0 (

8. /

14. /

K64 (H40)

1. 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps


PLC

PLC

2.

7.

K32 (H20)

CR#0 ~ CR#34 H4000 ~ H4022 RS-485

1.

H0000 CH1

DVP04AD-S

24VDC (20.4VDC ~ 26.4VDC) (-15% ~ +10%), 2W,

1. 0C ~ 55C50 ~ 95% 2
2. -25C ~ 70C5 ~ 95%
IEC 61131-2, IEC 68-2-6 (TEST Fc) / IEC 61131-2 & IEC 68-2-27
(TEST Ea)

4,800, 9600, 19,200 bps, 38,400 bps, 57,600 bps,


115,200 bps ASCII 7 bits1 stop bit (7,
E, 1)RTU 8 bits1 stop bit ( 8, E, 1)

1. b0 0 CH1 CR#18, CR#24 b0


R/W
1 CH1 CR#18, CR#24

32mA

4.00

13.

b15 ~ b8

CR#33

#1

6. /

#32 H4020

16 13 bits
(CR#2 ~ CR#5 K1 ~ K4,096)
/
ASCII/RTU (4,800/9,600/19,200/38,400/57,600
/115,200), ASCII 7 bits1 stop bit (7, E, 1)RTU
8 bits1 stop bit (8, E, 1) PLC RS-485

0 7 8 I/O

b15ASCII/RTU

mm

b0

CR#1 CH1
~ CH4 CH1 0 (b2 ~ b0=000)CH2 1 (b5 ~ b3=001)CH3 2b8 ~ b6=010
CH4
3 (b11 ~ b9=011) CR#1 H0688 (b12 ~ b15) H0000

b 457,600 bps (/) b 5115,200 bps (/)

H4021

13

RS-485 01 ~ 254 K1

b6 ~ b13 b14CRC ( RTU )

#33

FG
V+
C
I+
H
COM 4

CR RS-485


14

CR#30

OFFSET

-4,000

-8,000

4,000
-3,200LSB ~ +16,000LSB
0
-4,000LSB ~ +4,000LSB

GAIN
OFFSET

+800LSB ~ +12,000LSB

CR#1 2

GAIN=20mA (4,000LSB), OFFSET=4mA


(800 LSB).

#32

C
H
COM 3
I+

b0 ~ b7 0 1

V+

#30 H401E

b1

3.00

I+

K-3,200 ~ K10,400

CH4 GAIN

CR

60.0
0

K-3,200 ~ K16,000

CH3 GAIN

b2

< 1.5mm

60.0
0

CH1 ~ CH4 GAIN K4,000, LSB

CH2 GAIN

CH1 GAIN

b3

20mA ( 5A)

K-4,000 ~ K4,000

CH4 OFFSET

CR#18 ~ CR#27 GAIN OFFSET =+800 LSB ~ +12,000 LSB () +800 LSB ~ +6,400 LSB ()

K1 (H1)

R/W

#26 H401A

K-4,000 ~ K4,000

DIN

14 DVP-PLC SS/SA/SX/SC/SV FROM/TO

K-3,200 ~ K16,000

H401F

AG
-15V

CH1 ~ CH4 GAIN K4,000 LSB

#31

#25 H4019

CH1 ~ CH4 OFFSET K0, LSB

b4

#24 H4018

CH3 OFFSET

DVP-PLC

#21 H4015

CH2 OFFSET

b5

(RS-485)

CR#30

0
-4,000 LSB ~ +4,000LSB

#20 H4014

CH1 OFFSET

OFFSET

#19 H4013

b6

GAIN

CH4

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W

#18 H4012

#27 H401B

+4,000
-3,200 LSB ~ +10,400LSB

CH3

GAIN=20mA (4,000LSB), OFFSET=0mA (0LSB).

CH2

b7

-4,000LSB ~ +4,000LSB

CR#1 3

#15 H400F

K1 (H1)

(800 LSB).

#14 H400E

GAIN=20mA (4,000LSB), OFFSET=4mA

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

CH4
CH3
CH2
CH1

#13 H400D

+15V

1
2V+ I+
3 FG

CH4 GAIN

24-

CR RS-485

H401E

DC/DC

10 0

4,000
-3,200LSB ~ +16,000LSB

DVP DVP04AD-S 4

CR#18 ~ CR#27 GAIN OFFSET =+800LSB ~ +12,000 LSB () +800 LSB ~ +6,400 LSB ()
()()

#30

24+

OFFSET (CR#18 ~ CR#21) GAIN (CR#24 ~ CR#27)

CH1 GAIN

CH3 GAIN

GAIN=6V (4,800LSB), OFFSET=2V (1,600LSB).

K-4,000 ~ K4,000

AG

A/D

CH4 OFFSET

CH2 GAIN

-4,000

CH3 ~ CH4 K1 ~ K4,096


K10

CH4

GAIN=5V (4,000LSB), OFFSET=0V (0LSB).

GAINOFFSET +800LSB ~ +12,000LSB

CR#1 2

V+
I+
COM
FG
V+
I+
COM
FG

104.7K

FG

-20mA -12mA

CH4

250

I+

*4

104.7K

V+

H0000
0 (-10V ~ +10V)
1 (-6V ~ +10V)
2 (-12mA ~ +20mA)
3 (-20mA ~ +20mA)
4

~
~

COM

CH1

DVP04AD-S = H88

GAIN
OFFSET

-4,000

#1

10V

CR#1 1

OFFSET GAIN

8 (b7 ~ b0)
R

6V

2V

AG

4
DVP04AD-S

5 0.1 ~ 0.47F 25V

CR#1 0

V+
I+
COM
FG
V+
I+
COM
FG

*3

A/D

H4000

CH4

DVP04AD-S

104.7K

FG

*2

#0

*1

CH1

250

COM

*2

3. (Function)03H 06H word 10H words

1. / 22-16AWG (1.5mm)
PLC 1.95 kg-cm (1.7Ib-in)

CH4

V+

-20mA ~ +20mA

CH1

R FROM RS-485

+8,000

104.7K
I+

16 1.0A H010A

CR

)b1=1 ()

3. b2 1

E, 1)RTU 8 bits1 stop bit (8, E, 1)

DVP04AD-S

-10V ~ + 10V

2.

2. Modbus ASCII /RTU ASCII 7 bits1 stop bit (7,

DIN

RS-485

CH1

1. 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps

35mm DIN
PLC PLC
PLC PLC

PLC

CR

CH2

CR#0 ~ CR#34 H 4000 ~ H4022 RS-485

< 1.5mm

CH3

2.1LSB =20mA/4,000=5A

22-16AWG

CH4

LSB(Least Significant Bit)1.1LSB =10V/8,000=1.25mV

IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27
(TEST Ea)

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

W TO RS-485

2. -25C ~ 70C5 ~ 95%

R/W

H4021

1. 0C ~ 55C50 ~ 95% 2

#33

CR#33

RS-485

+4,000

-20mA -12mA

0
4mA
OFFSET

CH4
-4,000

CR#1 3GAIN=20mA (4,000LSB), OFFSET=0mA (0LSB).


GAIN

0
-3,200LSB ~ +10,400LSB

OFFSET

+4,000
-4,000LSB ~ +4,000LSB

GAIN
OFFSET

+800LSB ~ +6,400LSB

20mA
GAIN

A/D
OFFSET (CR#18 ~ CR#21) GAIN (CR#24 ~ CR#27)