CoolingFormulas
CONVERSION
1Ton=12000Btu/hr
COOLINGLOADREQUIREMENT
TotalCoolingLoad(Btu/hr)=4.5xCFMx(H1H2)
Where:
CFM=AirflowinCubicFeetPerMinute
H1=EnteringAirEnthalpy(Btu/lbmdryair)
H2=LeavingAirEnthalpy(Btu/lbmdryair)
Or
TotalCoolingLoad(Btu/hr)=SensibleCoolingLoad(Btu/hr)+LatentCoolingLoad(Btu/hr)
Where:
SensibleCoolingLoad(Btu/hr)=CFMxDensityFactorx(T1T2)
LatentCoolingLoad(Btu/hr)=CFMx0.69143x(G1G2)
Where:
CFM=AirflowinCubicFeetPerMinute
(70BlowerTemp)*.024
DensityFactor=1.08+
10
T1=EnteringAirDrybulbTemperature(F)
T2=LeavingAirDrybulbTemperature(F)
G1=GrainsofMoistureofEnteringAir=7000xhumidityratio(lbmmoisture/lbmofdryair)
G2=GrainsofMoistureofLeavingAir=7000xhumidityratio(lbmmoisture/lbmofdryair)
EFFICIENCYCALCULATION
SEER=BTU/Whr
COSTOFCOOLING:
Costofcooling=BTU/hrxhrsofoperationxelectricitycost($/kwhr)/(SEERx1000)
https://www.captiveaire.com/catalogcontent/coils/formulas.asp