PROCEDURE FOR FENCING WORKS

20.08.07

Anuj

Vijay

GSB

REV. NO.

DATE

DRN. BY

CHKD.BY

APPV.BY

Approved (IOCL)

Page 2 of 3

PROCEDURE FOR FENCING WORKS

CONTACT NO: -

17614132 dated 28-07-2007 for combined Civil, Mechanical,


Electrical, & Instrumentation works at Kohand, Nabha and
Jalandhar stations of PJPL project.

PROCEDURE NO: - INDCON-PJPL-STN-PNP-CIVIL-19

Barbed Wire Fencing:The barbed wire shall be of G.I. wire and in general conform to IS-278-1962. Line
wire and point wire shall be of 2.5 mm, 2.24 mm diameter respectively. Distance
between the barbs shall be 75 mm nominal.
The barb shall have a length not less than 13 mm and points shall be sharp and
well pointed. The barbs shall carry four points and shall be formed by twisting two
point wires. Each two turns, lightly round the wire making altogether 4 complete
turns.
The barbs shall be so finished that the 4 points are set and locked at right angles
to each other.
The line wire shall be in continuous length and shall be generally free from welds.
The barbed wire shall be formed by twisting two line wires.
The barbed wire shall be stretched tight and fixed in the manner (horizontal &
diagonal) and fitted in slots of angle iron post and held by binding with G.I.
binding wires or with G.I. staple in case of R.C.C posts.
Turn buckles and straining bolts shall be used at the end posts.

Page 3 of 3

INSPECTION & TEST PLAN FOR FENCING WORK


Project
: Panipat Jalandhar Pipeline Project.
Client
: M/S. INDIAN OIL COPRN. LTD. ( Pipeline Division, NRPL )
Contractor : M/s. Indcon Projects & Equipment Ltd., New Delhi.
Doc. No.: INDCON-PJPL-STN-PNP-CIVIL-19
S.N
O.
1.
2.
3.
4.

Activity Description
Layout, lines and levels
Visual check of fencing materials
Installation of fencing
Final inspection post installation

W
RM
R

Inspection by
INDCON

Verification by
IOCL

W
W
W
W

R
RM
RM
W

Records to be
maintained
by INDCON
Register
Register
Register
Register

- Witness
- Random Check
- Review Documents

07.09.07

Rev.

Date

For review &


Approval
Description

Prepared by
(INDCON)

Checked by
(INDCON)

Approved
by
(INDCON)

Reviewed &
approved by IOCL