Beruflich Dokumente
Kultur Dokumente
Results
Study:
800MCM-dbp-2ckts
Execution:
01-05092014-A
Date:
5/9/2014
Frequency:
60 Hz
Conductor Resistances:
Installation Type:
IEC-228
Buried Ducts
Parameter
Unit
25
C.m/W
1.5
Enabled/Disabled
Disabled
Value
Summary Results
Solution converged
Location
Load Factor
Temperature
Ampacity
Y[m]
[p.u.]
[C]
[A]
1.3
84.3
394.1
1.3
90
394.1
Cable\Cable
type no
Circuit
Phase
X[m]
1\1
1.012
2\1
0.723
3\1
0.434
1.3
89.4
394.1
4\1
-1.012
1.3
84.3
394.1
5\1
-0.723
1.3
90
394.1
6\1
-0.434
1.3
89.4
394.1