Sie sind auf Seite 1von 149

SOLAR PHOTOVOLTAIC ENERGY GENERATION AND CONVERSION

FROM DEVICES TO GRID INTEGRATION

by
HUIYING ZHENG
SHUHUI LI, COMMITTEE CHAIR
TIM A. HASKEW
JABER ABU QAHOUQ
DAWEN LI
MIN SUN

A DISSERTATION

Submitted in partial fulfillment of the requirements


for the degree of Doctor of Philosophy
in the Department of Electrical & Computer Engineering
in the Graduate School of
The University of Alabama

TUSCALOOSA, ALABAMA

2013

Copyright Huiying Zheng 2013


ALL RIGHTS RESERVED

ABSTRACT

Solar photovoltaic (PV) energy is becoming an increasingly important part of the worlds
renewable energy. In order for effective energy extraction from a solar PV system, this research
investigates solar PV energy generation and conversion from devices to grid integration.
First of all, this dissertation focuses on IV and PV characteristics of PV modules and
arrays, especially under uneven shading conditions, and considers both the physics and electrical
characteristics of a solar PV system in the model development. The dissertation examines how
different bypass diode arrangements could affect maximum power extraction characteristics of a
solar PV module or array. Secondly, in order to develop competent technology for efficient
energy extraction from a solar PV system, this research investigates typical maximum power
point tracking (MPPT) control strategies used in solar PV industry, and proposes an adaptive and
close-loop MPPT strategy for fast and reliable extraction of solar PV power. The research
focuses especially on how conventional and proposed MPPT methods behave under highly
variable weather conditions in a digital control environment. A computational experiment system
is developed by using MatLab SimPowerSystems and Opal-RT (real-time) simulation
technology for fast and accurate investigations of the maximum power extraction under high
frequency switching conditions of power converters. A hardware experiment system is built to
compare and validate the conventional and the proposed MPPT methods in a more practical
condition. Advantages, disadvantages and properties of different MPPT techniques are studied,

ii

evaluated, and compared. Thirdly, in order to develop efficient and reliable energy conversion
technologies, this dissertation compares the energy extraction characteristics of a PV system for
different converter configurations. A detailed comparison study is conducted to investigate what
enhancements and impacts can be made by using different bypass diode schemes. It is found that
compared to micro-converter based PV systems, the central converter scheme with effective
bypass diode connections could be a simple and economic solution to significantly enhance PV
system efficiency, reliability and performance. Lastly, the development of coordinated control
tools for next-generation PV installations, along with energy storage units (ESU), provides
flexibility to distribution system operators. The objective of the control of this hybrid PV and
energy storage system is to supply the desired active and reactive power to the grid and at the
same time to maintain the stability of the dc-link voltage of the PV and energy storage system
through coordinated control of power electronic converters. This research investigates three
different coordinated control structures and approaches for grid integration of PV array, battery
storage, and supercapacitor (SC). In addition, other applications including single-phase DirectQuadrature (DQ) control and ramp rate limit control are presented in this dissertation.

Index Terms solar photovoltaic, semiconductor physics, IV characteristics, PV


characteristics, bypassing diodes, uneven shading, power electronic converters, maximum power
point tracking, digital control, computational and hardware-based experiments, battery and
supercapacitor, control coordination, single-phase DQ control, and ramp rate control.

iii

DEDICATION

This dissertation is dedicated to everyone who helped me and guided me through the
trials and tribulations of creating this research. In particular, the graduate school of the
University of Alabama and some knowledgeable and up-lifting professors in ECE department
who stood by me throughout the time taken to complete this research.

iv

LIST OF ABBREVIATIONS AND SYMBOLS

ID

Diffusion current

IS

Drift current

IL

Photogenerated current

Rp

Parallel resistance accounting for current leakage through the solar cell

Rs

Series resistance which causes an extra voltage drop between the junction voltage
and the terminal voltage of the solar cell

I0

Diode reverse saturation current

Diode ideality factor

Elementary charge

Absolute temperature

Boltzmann's constant

Ic

Output current of a solar device

Ps

Shading factor that the shaded cell is relevant to the unshaded cell

Vd

P-n junction diode voltages

Vc

Output voltage of a solar device

Pc

Generated power of a solar device

N D

Net doping concentration in n-type region

N A

Net doping concentration in p-type region

Approximate constant with respect to temperature


v

Eg

Band-gap energy of the semiconductor (eV)

Ratio of the present solar irradiation over the nominal irradiation of 1000W/m2

IMPP

Current at the maximum power point

ISC

Short-circuit current of a PV array

ksc

Ratio of current at the maximum power point to the short-circuit current

VMPP

Voltage at the maximum power point

VOC

Open-circuit voltage of a PV array

Koc

Ratio of voltage at the maximum power point to the open-circuit voltage

I a Va

Instant conductance

I a Va Incremental conductance

tanh() Hyperbolic function


SOC

State of charge of battery

ib_ref

Battery reference current

isc_ref

Supercapacitor reference current

Vdc_ref

Dc-link capacitor reference voltage

psto_ref

Storage units reference power

pdc_ref

Dc-link capacitor reference power

pg_ref

Grid reference power

ppv

PV system generated power

pf

Power losses in grid filter

id

Grid d-axis current

iq

Grid q-axis current

Rf

Resistance of grid filter

vi

XR

Peak value of sinusoidal waveform

XI

Corresponding imaginary orthogonal of XR

Initial phase

Fundamental frequency

Transformation matrix from stationary frame to rotating frame

T-1

Transformation matrix from rotating frame to stationary frame

P(t)

Instantaneous reactive power

vii

ACKNOWLEDGMENTS

I am pleased to have this opportunity to thank those who gave me an enormous amount of
help and guidance for this research project. My supervisor, Dr. Shuhui Li, has steered me from
the early stages of problem formulation to the clarification and careful presentation of ideas in
this dissertation. He has kept me on the right track while forcing me to discover the hard
problems for myself. His enthusiasm for my research topic and tremendous expertise is very
much appreciated and he has always made time to review my experimental objectives and
conclusions and give excellent guidance, despite his busy schedule.
I would also like to thank all of my committee members, Dr. Tim. A. Haskew, Jaber Abu
Qahouq, Dawen Li and Min Sun for their invaluable input, inspiring questions, and support of
both the dissertation and my academic progress. I would like to thank Dean David Francko and
Dr. Haskew for their assistance at the most difficult time of this journey.
In addition, I would like to thank Dr. Bharat Balasubramanian for opening up a
transformative cooperative program with practical industrials, which provided me with a
wonderful opportunity to apply knowledge to the work in Mercedes- Benz U. S. International,
Inc., Vance, Alabama.
In my long journey through the University of Alabama, the graduate school has been
supporting me all the way to my graduation. With Graduate Council Fellowship, I accumulated
professional knowledge of industrial electrical engineering and adapted myself to the colorful
campus life. With the support of Graduate Student Research and Travel Support, I was able to
viii

present my work at international conferences, which is an excellent way to enhance knowledge


about latest technological advancements in the field of electric power engineering, to learn about
the culture of different host countries and cities, to show my work to all the professional
researchers, and most importantly, to represent UA and the graduate program to the world!
Finally, I would like to thank my parents for instilling in me a love of learning and
encouraging my curiosity. There was never anything I needed that they did not try to provide.
They have made me the person I am today.
Thanks to all of you.

ix

CONTENTS

ABSTRACT .......................................................................................................... ii
DEDICATION ..................................................................................................... iv
LIST OF ABBREVIATIONS AND SYMBOLS ...................................................v
ACKNOWLEDGMENTS .................................................................................. viii
LIST OF TABLES ............................................................................................. xiv
LIST OF FIGURES ..............................................................................................xv
LIST OF ILLUSTRATIONS ............................................................................. xix
CHAPTER 1 - INTRODUCTION .........................................................................1
CHAPTER 2- ENERGY EXTRACTION CHRACTERISTIC STUDY OF
SOLAR PHOTOVOLTAIC CELLS, MODULES AND ARRAYS ......................6
2.1 Semiconductor Characteristics and Equivalent Model of a Solar Cell ............6
2.1.1 Silicon Solar Cell...........................................................................................6
2.1.2 Photogenerated Current and Voltage ............................................................8
2.1.3 Equivalent Model of a Solar Cell ..................................................................9
2.2 Energy Extraction Characteristics of PV cells under Uneven Shading
Conditions.............................................................................................................11
2.2.1 Two Series PV Cells under Uneven Shading Condition .............................11
2.2.2 PV Module under Uneven Shading Condition ............................................16
2.2.3 Model Validation .........................................................................................21
2.3 Bypassing Diode Impact to the Characteristics of Solar PV Cells................22
x

2.4 Energy Extraction Characteristics of PV Arrays under Uneven Shading .....26


2.5 Virtual Transient Experiment ........................................................................30
2.6 Conclusions ...................................................................................................33
CHAPTER 3 - A FAST AND RELIABLE APPROACH FOR MAXIMUM
POWER POINT TRACKING..............................................................................35
3.1 Extracted Power Characteristics of a PV System ...........................................36
3.1.1 The Effect of Temperature ..........................................................................37
3.1.2 The Effect of Illumination Intensity ............................................................39
3.2 Conventional Fixed-step MPPT Methods ......................................................40
3.2.1 Short-Circuit Current Method .....................................................................41
3.2.2 Open-Circuit Voltage Method .....................................................................42
3.2.3 Perturb & Observe Method .........................................................................43
3.2.4 Incremental Conductance Method...............................................................44
3.3 Adaptive MPPT Strategies .............................................................................45
3.3.1 Traditional Adaptive MPPT Methods .........................................................46
3.3.2 Proposed Hyperbolic -PI (H-PI) Adaptive MPPT Method .........................47
3.4 Computational Experiment.............................................................................49
3.4.1 MPPT under Step and Ramp Changes of Solar Irradiation.........................51
3.4.2 Sampling Rate Impact .................................................................................55
3.4.3 MPPT under Variable Solar Irradiation Condition .....................................57
3.5 Hardware Experiment and Comparison .........................................................58
3.5.1 Laboratory Setup and Design ......................................................................58
3.5.2 Experiment Analysis and Comparison ........................................................59
3.6 Conclusions ....................................................................................................61

xi

CHAPTER 4 - PV ENERGY EXTRACTION CHARACTERISTICS STUDY


UNDER SHADING CONDITIONS FOR DIFFERENT CONVERTER
CONFIGURATIONS ...........................................................................................63
4.1 Configurations of Grid-connected Solar PV Systems ....................................63
4.2 Power Converters Architecture of PV Arrays ................................................64
4.2.1 Central Dc/ac and Dc/dc Converters ...........................................................65
4.2.2 Central Dc/ac Inverter and String Dc/dc Converters...................................66
4.2.3 Dc/dc Optimizers .........................................................................................66
4.2.4 Detached Microinverters .............................................................................67
4.2.5 Central and String Inverters ........................................................................69
4.3 PV Array Models for Different Converter Configurations ............................70
4.4 PV System Energy Extraction Characteristics without Bypass Diodes .........71
4.4.1 Central Converter Configuration .................................................................71
4.4.2 String Converter Configuration ...................................................................73
4.4.3 Micro-inverter Configuration ......................................................................74
4.5 PV System Energy Extraction Characteristics with Bypass Diodes ..............76
4.5.1 Central Converter Configuration .................................................................77
4.5.2 String Converter Configuration ...................................................................79
4.5.3 Comparison of Maximum Power Using Central, String and Micro
Converter Configuration.......................................................................................80
4.6 Conclusion ......................................................................................................83
CHAPTER 5 - COORDINATED CONTROL FOR GRID INTEGRATION
OF PV ARRAY, BATTERY STORAGE, AND SUPERCAPACITOR WITH
RELATED ISSUES......84
5.1 Grid-connected PV and Energy Storage System ............................................85
5.1.1 Photovoltaic Arrays .....................................................................................86
xii

5.1.2 Rechargeable battery ...................................................................................86


5.1.3 Supercapacitor .............................................................................................86
5.1.4 Grid-Connected Converter ..........................................................................87
5.1.5 Integrated Control System ...........................................................................87
5.2 Coordinate PV Array, ESU and GCC Control ...............................................88
5.2.1 Control of Bi-directional Dc/dc Converters for ESUs ................................88
5.2.2 Direct-Current Vector Control of GCC .......................................................90
5.3 Coordinated Control Mechanisms for Grid Integration .................................93
5.3.1 Dc-link Voltage Control through ESUs ......................................................93
5.3.2 Power Balancing Control of ESUs ..............................................................94
5.3.3 Dc-link Voltage Control through GCC .......................................................95
5.4 Coordinated Control Evaluation and Comparison .........................................96
5.5 Other Applications of Coordinated Control .................................................103
5.5.1 Coordinated Control in Single-phase System ...........................................103
5.5.2 Coordinated Control Considering about Ramp Rate Limit .......................108
5.6 Conclusion ....................................................................................................115
CHAPTER 6 - CONCLUSIONS AND FUTURE WORK ................................117
6.1 Contributions of the Dissertation .................................................................117
6.2 Limitations and Future Work .......................................................................118
REFERENCES ...................................................................................................120

xiii

LIST OF TABLES

3.1 Comparison of MPPT methods......................................................................62


4.1 Comparison of maximum power extraction without bypass diodes for
different converter configurations..................................................................76
4.2 Comparison of maximum power extraction under 50% shading factor 82
4.3 Comparison of maximum power extraction under 100% shading factor...82
5.1 Parameters of electrical components in grid-integrated PV system .............98
5.2 Comparison of ramp rate value before and after designed ramp rate
control in two scenarios ...............................................................................114

xiv

LIST OF FIGURES

2.1. Diffusion current, drift current, and depletion zone of a p-n junction ...........7
2.2. Illustration of drift current as well as photogenerated current and voltage ....8
2.3. Solar cell equivalent circuit model .................................................................9
2.4. Solar cell I-V and P-V characteristics ...........................................................11
2.5. Two series PV cells with uneven shading.....................................................12
2.6. Characteristics of two series solar cells ........................................................14
2.7. A PV module connected to an external circuit .............................................18
2.8. Characteristics of PV module (one cell shaded) ...........................................19
2.9. Characteristics of PV module (18 cells shaded) ...........................................20
2.10. Schematics of a PV module connected with bypassing diodes, created
by NI Multisim..............................................................................................24
2.11. Characteristics of a PV module (3 cells with a bypass diode) ......................25
2.12. Characteristics of a PV module (9 cells with a bypass diode) ......................25
2.13. Characteristics of a PV module (18 cells with a bypass diode) ....................25
2.14. Bypass and blocking diodes in a solar PV generator ....................................27
2.15. PV array characteristics (without bypass diode) ...........................................30
2.16. PV array characteristics (one module with a diode) .....................................30
2.17. PV array characteristics (each cell with a bypass diode) ..............................30
2.18. Solar PV generator under an open-loop controlled dc/dc power converter.. 31
xv

2.19. Transient simulation results of a PV array relevant to the 100%


shading condition applied in Fig. 2.16 .........................................................32
3.1. Configuration of grid-connected solar PV system ........................................36
3.2. Typical daily temperature and irradiation plots ............................................37
3.3. P-V characteristics of a PV array vs. temperature and voltage.....................38
3.4. Derivative of power over terminal voltage under different temperatures.....38
3.5. P-V characteristics of a PV array vs. irradiation and voltage .......................40
3.6. Derivative of power over terminal voltage under different irradiations ......40
3.7. Graphic relation of IMPP over ISC and VMPP over VOC ....................................41
3.8. Conventional MPPT methods of SCC and OCV ..........................................42
3.9. Flowchart of the fixed step P&O algorithm ..................................................44
3.10. Flowchart of the incremental conductance algorithm ...................................45
3.11. PI based MPPT control loop diagram of the PV system ..............................47
3.12. A tangent sigmoid function for adaptive MPPT ...........................................48
3.13. Control loop diagram of proposed adaptive MPPT ......................................48
3.14. Solar PV generator with the MPPT and grid-integration using SPS and
Opal-RT RT-LAB .........................................................................................49
3.15. MPPT digital control module........................................................................50
3.16. Step and ramp changes of irradiation............................................................52
3.17. Comparison of MPPT under step and ramp changes of solar irradiation
levels .............................................................................................................52
3.18. Dc-link voltage .............................................................................................54
3.19. Three-phase grid-side currents ......................................................................54
3.20. Dc/ac inverter power at the grid side ............................................................54
3.21. MPPT comparison under different sampling rates ......................................56

xvi

3.22. MPPT comparison of under variable solar irradiation condition..................57


3.23. Hardware experiment setup for evaluation of MPPT algorithms ................59
3.24. Hardware experiment of captured maximum power using conventional
and proposed MPPT algorithms....................................................................61
4.1. PV array with central dc/ac and dc/dc converter structure ...........................65
4.2. PV array with central dc/ac inverter and string dc/dc converters .................66
4.3. Dc/dc optimizers per module and a central inverter .....................................67
4.4. Detached microinverter PV system ..............................................................68
4.5. PV array with central and string inverters ....................................................69
4.6. Characteristics of PV array with central converter .......................................72
4.7. Characteristics of series PV strings with shaded cells ..................................73
4.8. Characteristics of PV module under shading conditions ..............................75
4.9. Characteristics of PV array under shading conditions ..................................78
4.10. Characteristics of PV array for different bypass diode schemes ..................79
4.11. Characteristics of series PV strings...............................................................81
5.1. Configuration of grid-connected PV system with ESUs ..............................85
5.2. Block diagram of nested-loop battery control strategy .................................89
5.3. GCC converter schematic .............................................................................90
5.4. GCC direct-current vector control structure .................................................92
5.5. Control of dc-link voltage through ESUs .....................................................94
5.6. Power balance control structure of ESUs .....................................................95
5.7. Energy storage units connected converters control structure .......................96
5.8. Solar PV generator under the control of a dc/dc power converter using
SPS and Oparl-RT RT-LAB .........................................................................97
5.9. Solar PV array characteristics used in simulation.........................................98
xvii

5.10. Simulation results of the control scheme in Section 5.3.1 ............................99


5.11. Simulation results of the control scheme in Section 5.3.2 ............................99
5.12. Simulation results of the control scheme in Section 5.3.3 ............................99
5.13. Solar irradiation over the nominal irradiation of 1000W/m2 ......................100
5.14. Three-phase grid-side currents ....................................................................102
5.15. Single-phase grid connected solar PV generator under the control of a
dc/dc power converter using SPS and Opal-RT RT-LAB .........................105
5.16. Simulation result of the proposed method applications in single-phase
inverter .......................................................................................................106
5.17. Energy storage units connected converters control structure .....................110
5.18. Hourly solar radiation data of two random days in Adair Casey ................110
5.19. Simulation results of scenario 1 ..................................................................111
5.20. Simulation results of scenario 2 ..................................................................111
5.21. Dc-link voltages of two solar irradiation scenarios ....................................114

xviii

LIST OF ILLUSTRATIONS

4.1 Configuration of grid-connected solar PV system ...........................................64


5.1 Measured solar irradiance profiles for each day in August 2012 ..................109

xix

CHAPTER 1
INTRODUCTION

Investment in solar photovoltaic (PV) energy is rapidly increasing worldwide [1]. A gridconnected solar PV system consists of a PV generator that produces electricity from sunlight and
power converters for energy extraction and grid interface control [2, 3]. The smallest unit of a
PV generator is a solar cell and a large PV generator is built by many solar cells that are
connected together through certain series and parallel connections [4].
Although in most power-generating systems, the main source of energy (the fuel) can be
manipulated, this is not true for solar energies [5]. Industry must overcome a number of technical
issues to deliver renewable energy in significant quantities. Control is one of the major enabling
technologies for the deployment of renewable energy systems. Photovoltaic power requires
effective use of advanced control techniques. In all, safe and effective integration of PV system
cannot be achieved without extensive use of control technologies at all levels.
Firstly, unlike a solar thermal panel which can tolerate some shading, PV modules are
very sensitive to shading. Many brands of PV modules can be affected considerably even by
shading of the branch of a leafless tree. If enough cells are hard shaded, a module will not
convert any energy and will, in fact, become a tiny drain of energy on the entire system [2, 6]. In
existing research, most shading studies of a PV system focus mainly on how the I-V and P-V
characteristics of an entire PV system are affected [7-12]. Different from the conventional
approaches, Chapter 2 investigates the characteristics of shaded PV cells, modules, and arrays by
integrating the semiconductor physics characteristics of PV cells and the electrical characteristics
1

of the PV generators together and by investigating characteristic evaluation of unshaded cells,


shaded cells, and PV modules of a PV system. The chapter first introduces the semiconductor
characteristics and model of a solar PV cell in Section 2.1. Section 2.2 presents a characteristic
study of PV modules under uneven shading conditions and a strategy for validation of models
and algorithms developed by using National Instruments (NI) Multisim software, a PSpice-based
circuit simulation tool. Section 2.3 investigates how bypassing diodes affect and improve the
characteristics and performance of shaded cells, unshaded cells, and a PV module. Section 2.4
presents how the shading affects the performance of a PV array. Section 2.5 compares a transient
study of a PV array under an open-loop control condition through power electronic converters.
Finally, Section 2.6 concludes with the summary of main points.
Secondly, operation and control of a grid-connected solar PV system is important
because the conversion efficiency of PV power generation is low (9-17%) [13], especially under
low irradiation conditions; the amount of electric power generated by a solar array changes
continuously with weather conditions. The power delivered by a PV system of one or more
photovoltaic cells is dependent on the irradiance, temperature, and the current drawn from the
cells. In general, there is a unique point on the I-V or P-V curve, called the maximum power
point (MPP), at which the entire PV system operates with maximum efficiency and produces its
maximum output power. The location of the MPP is not known, but can be located, either
through calculation models or by searching algorithms. To maximize the output power of a PV
system, continuously tracking the MPP of the system is necessary. The primary challenges for
maximum power point tracking of a solar PV array include: 1) how to get to a MPP quickly, 2)
how to stabilize at a MPP, and 3) how to make a smooth transition from one MPP to another
under sharply changing weather conditions. In general, a fast and reliable MPPT is critical for

power generation from a solar PV system. In order for effective design and development of solar
PV systems in electric power systems, it is important to investigate and compare operating
principles, performance, and advantages or disadvantages of conventional MPPT techniques
used in the solar PV industry, and develop new competent technology for fast and reliable
extraction of solar PV power. In Chapter 3, the dissertation first presents an analysis of PV array
characteristics and the impacts of temperature and solar irradiance on PV array characteristics in
Section 3.1. Section 3.2 investigates conventional fixed-step MPPT techniques used in solar PV
industry. Section 3.3 presents traditional adaptive MPPT techniques, and a proposed
proportionalintegral (PI) based adaptive MPPT approach for fast and reliable tracking of PV
array maximum power. Section 3.4 gives performance evaluation of the conventional and
proposed MPPT methods under stable and variable weather conditions through a computational
experiment strategy. Section 3.5 shows a hardware experiment evaluation of the conventional
and proposed MPPT methods under more practical conditions in a dSPACE-based digital control
environment. Finally, Section 3.6 concludes with the summary of main points.
Thirdly, to make a PV system more efficient and economic, it is necessary to analyze
different converter configurations. Many different converter structures have been developed and
used in a solar PV system. Typical configurations include a central dc/dc/ac converter [14], a
central dc/ac inverter [15, 16], multi-string dc/dc converters plus a central dc/ac inverter [14, 17],
string inverters [15, 16], dc/dc optimizers [16, 17] and microinverters [15, 17, 18]. For all the
different converter structures, the energy extraction characteristics and maximum power capture
capability for all the converter schemes under even solar irradiation are very similar. However,
under shading conditions, the energy extraction depends strongly on what converter structure is
used in a PV system. Therefore, it is important to understand what the differences of energy

extraction characteristics are when using different converter schemes. In [17, 19], it is pointed
out that the string converter system has the advantage in capturing the maximum power of each
string of PV modules separately. In [15, 17], it is commented that micro converter PV system is
effective to overcome shading impact and enhance PV system efficiency. But, no detailed
comparison studies have been conducted previously on PV array performance using different
converter structures. This research first introduces configurations of grid-connected solar PV
system in Section 4.1 and typical PV power converter architectures in Section 4.2 respectively.
PV array models for different converter configurations are discussed in Section 4.3.Section 4.4
and 4.5 investigate PV system energy extraction characteristics with and without bypass diodes,
respectively, for different converter schemes. Finally, Section 4.6 concludes with the summary of
main points.
Last but not least, the control of energy storage is a key component in improving energy
efficiency, security and reliability, which allows the desired active and reactive power delivered
to the grid and at the same time to maintain the stability of the dc-link voltage of the PV and
energy storage system through coordinated control of power electronic converters. Batteries are
the technological solution most commonly employed to help make a PV power smooth and
dispatchable [20]. A battery stores electrical energy in the form of chemical energy. Normally,
batteries perform three main functions in a grid-connected PV system: storing energy into the
batteries when the PV production is high and the grid demand is low, releasing energy to the grid
when the PV production is low or during grid peak demand intervals, and preventing large
voltage fluctuations. Except for batteries, supercapacitor (SC) is usually used in conjunction with
batteries to form an advanced PV energy storage system [20, 21]. However, unlike batteries,
where the voltage remains relatively even over most of the batterys remaining charge levels, a

SCs voltage scales linearly with the remaining energy. This means additional circuitry is
required to make the SC energy usable. In order for effective design, development, and analysis
of integrated PV and Energy storage units (ESU) systems, it is important to investigate operating
principles, performance, and disadvantages and advantages of typical coordinated control
techniques used in the PV and ESU systems. In chapter 5, this research first introduces gridconnected PV and ESU system in Section 5.1. Section 5.2 evaluates control technologies
associated with each individual PV system components. Section 5.3 investigates coordinated
control methods for the integrated PV system. Section 5.4 gives performance evaluation for
coordinated control of PV array and ESU integration with the grid. Other applications including
single-phase DQ control and ramp rate limit control are illustrated in Section5.5. Finally, chapter
5 concludes with the summary of main points in Section 5.6.
Taken as a whole, this research demonstrates some issues of PV energy generation and
conversion from devices to gird integration.

CHAPTER 2
ENERGY EXTRACTION CHRACTERISTIC STUDY OF SOLAR PHOTOVOLTAIC CELLS,
MODULES AND ARRAYS

To begin with any research in PV system, it is important to know the characteristics of


solar cells, modules, and arrays in order to operate the design, energy extraction and grid
integration of a solar PV generator.

2.1 Semiconductor Characteristics and Equivalent Model of a Solar Cell

In most of solar cells, the absorption of photons takes place in semiconductor materials,
resulting in the generation of the charge carriers and the subsequent separation of the photogenerated charge carries. Therefore, semiconductor layers are the most important parts of a solar
cell.

2.1.1 Silicon Solar Cell

A solar cell is a device that converts the energy of sunlight directly into electricity by the
photovoltaic effect [2]. Although there are many kinds of solar cells developed by using different
semiconductor materials, the operating principle is very similar. The most commonly known
solar cell is configured as a large-area p-n junction made from silicon. When a piece of p-type
silicon is placed in intimate contact with a piece of n-type silicon, a diffusion of electrons occurs

from the region of high electron concentration (the n-type side) into the region of low electron
concentration (p-type side). Similarly, holes flow in the opposite direction by diffusion. This
forms a diffusion current ID from the p side to the n side (Fig. 2.1a). When the electrons diffuse
across the p-n junction, they recombine with holes on the p-type side. The diffusion of carriers
does not happen indefinitely because of an electric field which is created by the imbalance of
charge immediately on either side of the junction which this diffusion creates. The electric field
established across the p-n junction generates a diode that promotes charge flow, known as drift
current IS, that opposes and eventually balances out the diffusion current ID. The region where
electrons and holes have diffused across the junction is called the depletion zone (Fig.2.1b).

(a) Diffusion current ID from the p side to the n side

(b) Drift current IS from the n side to the p side and the depletion zone
Fig. 2.1. Diffusion current, drift current, and depletion zone of a p-n junction

2.1.2 Photogenerated Current and Voltage

When a visible light photon with energy above the band-gap energy strikes a solar cell
and is absorbed by the solar cell, it excites an electron from the valence band. With this
newfound energy transferred from the photon, the electron escapes from its normal position
associated with its atom, leaving a localized "hole" behind [2]. When those mobile charge
carriers reach the vicinity of the depletion zone, the electric field sweeps the holes into the p-side
and pushes the electrons into the n-side, creating a photogenerated drift current. Thus, the p-side
accumulates holes and the n-side accumulates electrons (Fig. 2.2), which creates a voltage that
can be used to deliver the photogenerated current to a load. At the same time, the voltage built up
through the photovoltaic effect shrinks the size of the depletion region of the p-n junction diode
resulting in an increased diffusion current through the depletion zone. Hence, if the solar cell is
not connected to an external circuit (switch in the open position in Fig. 2.2), the rise of the
photogenerated voltage eventually causes the diffusion current ID balancing out the drift current
IS until a new equilibrium state is reached inside a solar cell.

Fig. 2.2. Illustration of drift current as well as photogenerated current and voltage
8

2.1.3 Equivalent Model of a Solar Cell

When a solar cell is connected to an external circuit (i.e., switch in the close position in
Fig. 2.2), the photogenerated current then travels from the p-type semiconductor-metal contact,
through the wire, powers the load, and continues through the wire until it reaches the n-type
semiconductor-metal contact. Under a certain sunlight illumination, the current passed to the
load from a solar cell depends on the external voltage applied to the solar cell normally through a
power electronic converter for a grid-connected PV system. If the applied external voltage is
low, only a low photogenerated voltage is needed to make the current flow from the solar cell to
the external system. Nevertheless, if the external voltage is high, a high photogenerated voltage
must be built up to push the current flowing from the solar cell to the external system. This high
voltage also increases the diffusion current as shown in Section 2.1.2 so that the net output
current of the solar cell is reduced.

Fig. 2.3. Solar cell equivalent circuit model

To analyze the behavior of a solar cell, it is useful to create a model which is electrically
equivalent. According to Section 2.1.2, an ideal solar cell can be modeled by a current source,
representing the photogenerated current IL, in parallel with a diode, representing the p-n junction
of a solar cell. In a real solar cell, there exist other effects, not accounted for by the ideal model.
9

Those effects influence the external behavior of a solar cell, which is particularly critical for
integrated solar array study. Two of these extrinsic effects include: 1) current leaks proportional
to the terminal voltage of a solar cell and 2) losses of semiconductor itself and of the metal
contacts with the semiconductor. The first is characterized by a parallel resistance Rp accounting
for current leakage through the cell, around the edge of the device, and between contacts of
different polarity (Fig. 2.3). The second is characterized by a series resistance Rs, which causes
an extra voltage drop between the junction voltage and the terminal voltage of the solar cell for
the same flow of current.
The mathematical model of a solar cell is described by

qVd
V
I c I L I 0 e mkT 1 d ,

Rp

Vc Vd I c Rs

(2.1)

where IL is proportional to the sunlight illumination intensity, m is the diode ideality factor (1 for
an ideal diode), the diode reverse saturation current I0 depends on temperature, q is the
elementary charge, k is the Boltzmann's constant, and T is the absolute temperature [22]. For all
the studies presented in this dissertation, IL=6A, I0=610-6A, RP=6.6, RS=0.005, and T=25

which represents full sun condition used in [23]. Thus, characteristics of a solar cell can either be
simulated using a circuit simulation tool based on the equivalent circuit model or computed
directly by using MatLab based on (2.1). Important characteristics for a solar cell consist of
output current Ic and power Pc versus output voltage Vc characteristics. Figure 2.4 shows typical
I-V and P-V characteristics of a solar cell under ideal condition and with the consideration of
parallel and series resistance obtained by using a Spice simulation tool. As it can be seen from
the figure, if the external voltage applied to the solar cell is low, the net output current of the
solar cell, depending primarily on the photogenerated current, is almost constant. Therefore, as
the external voltage increases, more power is outputted from the solar cell. But, if the external
10

voltage is around the forward conduction voltage of the p-n junction diode, the net output current
drops significantly and the output power reduces.

a) I-V characteristics

b) P-V characteristics

Fig. 2.4. Solar cell I-V and P-V characteristics


(T = 25C, I0 = 6 10-10A, IL = 6A, Rp =6.6 and Rs = 0.005)

2.2 Energy Extraction Characteristics of PV cells under Uneven Shading Conditions

In most conventional studies of a solar PV system, it is usually assumed that all the PV
cells and modules making up a solar PV generator are identical and work under the same
condition [24- 26]. However, in reality, the characteristics of the cells and modules are subject to
some variations. This may happen when uneven sunlight is applied to solar cells, unclean PV
cells, variation and inconsistence of the cell parameters to be expected from manufacturing
process, or other conditions [2, 4].

2.2.1 Two Series PV Cells under Uneven Shading Condition

Figure 2.5 shows the configuration of two series connected PV cells. If both cells are
identical and operate at the same condition, then, the concentration of the photon-excited charge
11

carriers are the same in both cells. Thus, the photogenerated current in one cell can flow through
the second cell continuously and then to the external system, and the output voltage of the two
cells is the summation of the photogenerated voltage of both cells.

Rs1
Rp1
IL1
Vs
Rs2
Rp2
IL2
Fig. 2.5. Two series PV cells with uneven shading

Nevertheless, if the two cells operate at different conditions, such as one cell is at the full
sun while the other is shaded, then, the photon-excited charge carriers in the unshaded cell are
more than the photon-excited charge carriers in the shaded cell. Thus, the photocurrent of the
unshaded cell cannot completely flow through the shaded cell due to the insufficient charge
carriers, causing the rest of the photon-excited charge carriers to be accumulated on the p- and nside of the unshaded cell. Then, the output voltage of the unshaded cell rises, which causes (a)
more diffusion current through the p-n junction of the unshaded cell (Fig. 2.2) and (b) some of
the photogenerated current of the unshaded cell being pushed through the parallel resistance of
the shaded cell until an equilibrium state is reached.
If assuming that the parameters of the two cells are identical, the mathematical model of
the series PV cells under the shading condition is described by

12

qVd 1
V
I c I L I 0 e mkT 1 d 1 , Vc1 Vd 1 I c Rs

Rp

(2.2)

d2
qV
V
mkT
1 d 2 , Vc 2 Vd 2 I c Rs
I c (1 ps ) I L I 0 e

Rp

(2.3)

Vs Vc1 Vc 2

(2.4)

where ps stands for the shading factor that the shaded cell is relevant to the unshaded cell, and IL
represents the photogenerated current of unshaded cell under the full sun condition, Vd1 and Vd2
and Vc1 and Vc2 represent p-n junction diode voltages and output voltages of the unshaded and
shaded cells, respectively. Based on (2.2) to (2.4), a system of nonlinear equations can be
developed as

f1 Vd 1 , Vd 2 0

f 2 Vd 1 , Vd 2 0

(2.5)

Then, for a given voltage applied to the PV cells, voltage Vd1 and Vd2 can be solved
numerically by using Newton-Raphson algorithm in the following steps:
a)

Initial estimation:

Vd0 Vd01 ,Vd02


b)

(2.6)

Compute Jacobian matrix:

f1 Vdk1 f1 Vdk2
J
k
k
f 2 Vd 1 f 2 Vd 2
c)

(2.7)

Compute correction Vdk and update PV cell voltage Vdk 1 :

Vdk 1 Vdk Vdk


d)

(2.8)

Error calculation:
err

f1 Vd k 1 f 2 Vd k 1
2

13

(2.9)

e)

Repeat steps b) to d) until a stop criterion is reached, such as |err| < ( is a

predefined threshold).

a) I-V characteristics of two cells

b) P-V characteristics of two cells

c) Unshaded cell terminal voltage characteristics

d) Unshaded cell P-V characteristics

e) Shaded cell terminal voltage characteristics

f) Shaded cell P-V characteristics

Fig. 2.6. Characteristics of two series solar cells

For detailed study under shading condition, the I-V and P-V characteristics of the series
PV cells can be obtained through either simulation of Fig. 2.5 or the numerical computation
shown above. Although simulation of Fig. 2.5 is convenient to implement by using a circuit
simulation tool, numerical computation approach is more practical for a large solar PV system

14

that contains thousands of solar cells. It is necessary to point out that the study based on both
approaches can provide a cross validation mechanism.
Figure 2.6 shows the I-V and P-V characteristics under three shading conditions. The
shading factors are 0%, 50%, and 100%, where 0% represents the unshaded condition and 100%
stands for the completely shaded condition. This shading representation is applicable to the rest
of this research. Usually, the power dissipated by a shadowed cell increases cell temperature,
which changes the solar cell electrical properties by varying the values of I0 and IL slightly.
However, detailed temperature change, involving complicated heat transfer issues, is very hard
to calculate. Therefore, the temperature change caused by the power dissipation of a shadowed
cell is not considered here. According to Fig. 2.6 as well as other results, the following remarks
are obtained.
1)

When both cells operate at the same condition and under the same illumination

intensity, the photogenerated voltages are the same (Figs. 2.6c and 2.6e) and the P-V
characteristics are identical for both cells (Figs. 2.6d and 2.6f). Compared to a single cell, the
output voltage and power at the maximum power point are increased.
2)

If one cell is 100% shaded while the other is in full sun, the photogenerated current

of the unshaded cell has to pass through the parallel resistor of the shaded cell. Moreover, to
push the current through the high parallel resistance, the photogenerated voltage of the unshaded
cell must be high (Fig. 2.6c), which increases the diode drift current of the unshaded cell and
reduces the net output current significantly so that the actual output power is very low (Figs. 2.6b
and 2.6d).
3)

If one cell is partially shaded while the other is in full sun, the unshaded cell has

more photon-excited charge carriers than the shaded one. Therefore, part of the photon-excited

15

charge carriers of the unshaded cell passes through the shaded cell and part of charge carriers of
the unshaded cell has to pass through the parallel resistor of the shaded cell so that the terminal
voltage of the shaded cell is reversed. Thus, the unshaded cell generates power while the shaded
cell absorbs power (Figs. 2.6d and 2.6f), depending on the external voltage applied to the two
series solar cells. Similarly, to push the current through the high parallel resistance, the
accumulated photogenerated voltage of the unshaded cell must be high (Fig. 2.6c), which
increases the diode diffusion current of the unshaded cell so that the net current actually passing
through the parallel resistor of the shaded cell is very low (Fig. 2.6a).
4)

Under partial shading conditions, the power absorbed by the shaded cell is

influenced by the applied external voltage. The higher the external voltage, the less the current is
pushed through the parallel resistor of the shaded cell by the unshaded cell, the less the reverse
terminal voltage of the shaded cell and the less the shaded cell absorbs power. When the external
voltage is higher than the diode forward conduction voltage of the unshaded cell, the shaded cell
basically starts to generate power (Fig. 2.6f). In other words, increasing external voltage applied
to the two series of cells could prevent the shaded cell from becoming a hot spot under an uneven
shading condition. But, this special regularity cannot be seen effectively by just looking at the
overall P-V characteristics as shown by Fig. 2.6b.

2.2.2 PV Module under Uneven Shading Condition

Normally, solar cells are connected in series to form a module that gives a standard dc
voltage. A module typically contains 28 to 36 cells in series (Fig. 2.7), to generate a dc output
voltage of 12V in standard illumination condition. The 12V module can be used singly or

16

connected in series and parallel into an array with a large voltage and current output, according
to the power demand by an application.
The I-V and P-V characteristics of a PV module under a shading condition are more
complicated, depending on how many cells are shaded and what the shading factor of each cell
is. Assume there are N cells in a PV module and the shading factor of the ith PV cell in the
module is pi. Then, the mathematical model of a PV module under a shading condition is
described by:

qVdi
V
I c (1 pi ) I L I 0 e mkT 1 di , Vci Vdi I c Rs

Rp

(2.10)

Vs Vc1 Vc 2 Vc ( n 1) VcN

(2.11)

where pi stands for the shading factor of the ith cell relevant to the full sun condition, IL
represents the full sun photogenerated current, and Vdi and Vci are the p-n junction diode voltages
and output voltages of the ith PV cell. Similar to Section 2.2.1, a system of N nonlinear equations
can be developed as shown by (2.12).

f1 Vd 1 , , VdN 0

f N Vd 1 , , VdN 0

(2.12)

Then, for a given voltage applied to a PV module, voltage Vd1, Vd2, VdN can be solved
numerically by using Newton-Raphson algorithm in the following steps: 1) obtaining initial
estimation values of PV cell voltages, 2) computing the Jacobian matrix, 3) computing the
correction and updating PV cell voltages, 4) calculating the error, and 5) repeating steps (2) to
(4) until a stop criterion is reached [27]. After the completion of the iteration, solutions of Vd1,

Vd2, VdN for all PV cells are available for both shaded and unshaded cells. It is necessary to
point out that the initial estimation is vital for the stability and convergence of the NewtonRaphson algorithm, which is achieved based on the knowledge and estimation of a common

17

voltage range for a shaded or unshaded PV cell. In addition, before the iteration process, PV cells
with the same shading factor are regrouped together, which can greatly reduce the number of the
nonlinear equations and accelerate the numerical computation. It is worth noting that the
Bishops numerical program based on an equivalent PVNet is another approach that was
developed and used to investigate the electrical behavior of solar cell interconnection circuits as
presented in [28].

Shade

Vs

Fig. 2.7. A PV module connected to an external circuit

The I-V and P-V characteristics of the PV module can be obtained through either
numerical computation or simulation of Fig. 2.7. Figure 2.8 shows the characteristics of a PV
module when the shading factors of one cell are 0%, 50%, and 100%, respectively, while the
other cells are in full sun.

18

a) I-V characteristics of PV module

b) P-V characteristics of PV module

c) Unshaded cell voltage characteristics

d) Unshaded cell P-V characteristics

e) Shaded cell terminal voltage characteristics

f) Shaded cell P-V characteristics

Fig. 2.8. Characteristics of PV module (one cell shaded)

As it can be seen from the figure, if all the cells are in full sun irradiation and have the
same operating condition, the current from each cell is the same, and the output voltage and
power of the PV module are enhanced significantly due to the fact that more cells are connected
in series. But, this situation is completely different even when only one cell is shaded (Fig. 2.8a
and 2.8b). Due to the shading of one cell, part of charge carriers of the unshaded cells must go
through the parallel resistor of the shaded cell so that the terminal voltage of the shaded cell is
reversed (Fig. 2.8e).Thus, the unshaded cells generate power while the shaded cell absorbs

19

power (Fig. 2.8d and 8f). Similarly, to push the current through the high parallel resistance of the
shaded cell, the accumulated photogenerated voltage of each unshaded cell must be high (Fig.
2.8c) so that the net series voltage of all unshaded cells causes a high current through the parallel
resistor of the shaded cell (Fig. 2.8a) and a high reverse terminal voltage on the shaded cell (Fig.
2.8e), which results in a high absorbing power by the shaded cell especially when the external
voltage applied to the PV module is low (Fig. 2.8f). This high absorbing power may damage the
shaded PV cell.

a) I-V characteristics of PV module

b) P-V characteristics of PV module

c) Unshaded cell voltage characteristics

d) Unshaded cell P-V characteristics

e) Shaded cell terminal voltage characteristics

f) Shaded cell P-V characteristics

Fig. 2.9. Characteristics of PV module (18 cells shaded)

20

Figure 2.9 shows the characteristics of the PV module when 18 out of the 36 cells are
shaded. The shading factor, identical for all the 18 shaded cells, is 100%, 50% and none.
Compared to Fig. 2.8, when there are more cells shaded in a PV module, the net output voltage
of the unshaded cells is smaller and is applied to the shaded cells in a distributed manner. Hence,
the reverse voltage applied to the parallel resistor of each shaded cell is lower (Fig. 2.9e) and the
absorbing power by each shaded cell is decreased (Fig. 2.9f). Compared to Fig. 2.8f, the chance
for a shaded cell to become a hot spot is reduced, implying that a single shaded cell condition is
more hazardous to affect proper function of a PV module.

2.2.3 Model Validation

The fundamental unit of a PV generator is a PV cell. For a PV array model, parameters


associated with a PV cell, such as Rp and Rs, must be identified first. These can be obtained
through parameter extraction, such as the procedure shown in [29, 30]. The parameter extraction
is not a focus of this paper. It is assumed that parameters of PV cells are available [31, 32]. Thus,
the model validation focuses mainly on whether accurate current, voltage and power relations for
PV cells, modules and array can be obtained via the Newton-Raphson algorithm. However,
model validation through hardware experiments presents a big challenge for PV cells under
uneven shading conditions. This is due to the fact that that existing commercial available PV
modules are not built in such a way that current or voltage of each individual cell can be
measured. To overcome the challenge, this dissertation uses NI Multisim, a well-developed
PSpice-based industry standard circuit simulation tool [33-35], to validate models and the
Newton-Raphson algorithm application in Section 2.2.2, which provides an accurate and fast
approach for model validation. Using the NI Multisim, a PV cell equivalent circuit is very
21

convenient to build by using professionally developed circuit components. The procedure for the
PSpice-based simulation includes: 1) drawing circuit schematics, as illustrated by Figs. 2.3, 2.5
and 2.7; 2) setting up circuit parameters of the PV system; 3) simulating the circuit; 4) plotting
the results. According to Fig. 2.3, each PV cell has four components, including two resistors, one
diode, and one ideal current source. For a PV module containing 36 cells, there would be 144
components.
The model validation involves the development of computer program using the NewtonRaphson algorithm and the building of the PV simulation system using NI Multisim. For the
PSpice-based simulation, each circuit component of a PV cell is treated as a different simulation
element. Therefore, solar PV system simulation using NI Multisim is extremely expensive in
terms of computing speed and memory requirements. However, for the computer program
especially developed for the PV system study, the PV cells having the same operating conditions
are first regrouped automatically before the simulation. Therefore, both the computing speed and
memory requirement are much more efficient, particularly for a large PV array. The results
generated using the two different approaches are compared for different case studies, including
PV cells (Fig. 2.6), PV modules (Figs. 2.8 and 2.9), and small-scale PV arrays. The comparisons
always show the same results generated by both approaches (Figs. 2.6, 2.8, 2.9, 2.11, 2.12 and
2.13), demonstrating that it is effective and accurate to use the models and algorithm developed
in this chapter for small- and large-scale PV system studies (Section 2.4).

2.3 Bypassing Diode Impact to the Characteristics of Solar PV Cells

In photovoltaic industry, external bypass diodes in parallel with a series string of cells are
normally utilized to mitigate the impacts of shading on P-V curves. The polarity of the bypass
22

diode is reversed with respect to the PV cells [2]. Consequently, reverse bias of the cells
corresponds to the direct bias of the bypass diode which provides a bypass for the current
generated by other cells. With bypass diodes, the I-V and P-V characteristics of a PV module are
more complicated [36].
Normally, a bypass diode is applied to a PV module or a group of series PV modules [712]. For research purpose, however, different bypass diode schemes within a PV module will be
studied in this dissertation. Figure 2.10 shows a bypass diode arrangement, in which a bypass
diode is applied to each three series PV cells. For a general case, it is assumed that there are M
bypass diodes with each bypass diode being applied to L=N/M series PV cells. Then, the current
and voltage relations of the PV cells connected with the ith bypass diode and overall system
current and voltage are described by

I ci (1 pij ) I L I 0 e

qVdij

mkT

1 Vdij Rp

V pdi Vci1 Vci 2 Vci ( n 1) VciL , Vcij Vdij I ci Rs

I s I ci I 0 e

qV pdi

mkT

1 , Vs Vpd 1 Vpd 2 Vpd ( M 1) VpdM

(2.13)

(2.14)
(2.15)

where pij stands for the shading factor relevant to the full sun condition for the jth PV cell within
the ith bypass diode group, Vdij and Vcij represent p-n junction diode voltage and PV cell output
voltages of the jth PV cell within the ith bypass diode group, Ici is the output current of the series
PV cells within the ith bypass diode group, and Vpdi represents the voltage applied to the ith
bypass diode.
Then, similar to (2.12), a system of N nonlinear equations can be developed and voltage
Vd1 to VdN can be solved numerically by using Newton-Raphson algorithm for a given external

23

voltage Vs applied to the PV module. If some of the PV cells within the PV module operate at the
same condition, the numerical computation could be simplified considerably.

Fig. 2.10. Schematics of a PV module connected with bypassing diodes, created by NI Multisim

Figures 2.11- 2.13 show the characteristic of the PV module when one PV cell in the
module is shaded for three different bypass diode arrangement schemes: three series cells with a
bypass diode, nine series cells with a bypass diode, and eighteen series cells with a bypass diode.
From the figures, other case studies, and comparison with Section 2.2, it is concluded that:
1)

When a PV cell is shaded, there are two possible paths for the current generated by

other unshaded cells to pass through. One is through the shaded cell and parallel resistor of the
shaded cell; the other is through the bypass diode. The condition for the current passing through
the bypass diode is that the resultant reverse voltage of the series cells in parallel with the bypass
diode must be larger than the forward conduction voltage of the bypass diode.
24

a) I-V characteristics of PV

a) I-V characteristics of PV

a) I-V characteristics of PV

module

module

module

b) P-V characteristics of PV

b) P-V characteristics of PV

b) P-V characteristics of PV

module

module

module

c) Shaded cell terminal voltage c) Shaded cell terminal voltage c) Shaded cell terminal voltage

d) Shaded cell P-V

d) Shaded cell P-V

d) Shaded cell P-V

characteristics

characteristics

characteristics

Fig. 2.11.Characteristics of

Fig. 2.12. Characteristics of

Fig. 2.13. Characteristics of

a PV module

a PV module

a PV module

(3 cells with a bypass diode)

(9 cells with a bypass diode)

(18 cells with a bypass diode)

25

2)

When the bypass diode turns on, the voltage applied to the shaded cell equals to the

photogenerated voltages of the unshaded cells within the bypassing cell group plus the bypass
diode forward conduction voltage. Therefore, the less the PV cells within a bypassing cell group,
the smaller the reverse voltage which is applied to a shaded cell (Figs. 2.11c, 2.12c, and 2.13c)
and the less the shaded cell absorbs power (Figs. 2.11d, 2.12d, and 2.13d). In other words, to
prevent a shaded cell from becoming a hot spot, the number of series PV cell within a bypassing
cell group should be properly designed.
3)

With bypass diodes, the I-V and P-V characteristics of a PV module is more

complicated and different from the traditional understanding of the photovoltaic I-V and P-V
characteristics. An important issue, as it can be seen from Figs. 2.11b, 2.12b, and 2.13b, is that
the P-V characteristics of a PV module may contain multiple peaks. Hence, using traditional
maximum power point tracking approaches, one may get into a local peak point so that the
efficiency of the PV module would be reduced greatly.
By comparing Figs. 2.8 and 2.9 with Figs. 2.11-2.13, it can be been that bypass diodes of
a PV module can reduce absorbing power of shaded cells within the PV module and improve the
performance of PV system.

2.4 Energy Extraction Characteristics of PV Arrays under Uneven Shading

There are generally two ways to connect PV modules into an array. The first approach
connects modules in series into strings and then in parallel into an array. The second approach
first wires modules together in parallel then combines those units in series. Both connections are
equivalent if all the cells and modules are identical and work at the same condition. But, if
sunlight is applied unevenly to different PV cells as well as shading or other impacts, the second
26

connection approach could cause many very bothersome problems [2]. Figure 2.14 shows a
series-parallel PV array connection with a dc/ac power converter, in which the converter handles
both maximum power point tracking (MPPT) and grid interface control of the PV array [24]. At
the top of each string in Fig. 2.14, a blocking diode is used to prevent a shaded or malfunctioning
string from withdrawing current from the rest strings that are wired together in parallel.

Fig. 2.14. Bypass and blocking diodes in a solar PV generator

For the series-parallel connected PV array, the voltage applied to each string of the PV
modules is the same. However, the P-V and I-V characteristics of each string could be different
depending on how many cells in a string are shaded and how much the shading factors are. For
each string, the mathematical procedure to obtain P-V and I-V characteristics is very similar to
Section 2.3 except that the external voltage applied to each string equals to the sum of
photogenerated voltages of all series connected PV modules. Then, with the consideration that

27

the output current of the PV array is the sum of currents of all parallel strings, characteristics of
the PV array can be achieved quickly through numerical computation. It is necessary to point out
that for any PV cells having the same operating condition within a string, combining those PV
cells into one mathematical equation could significantly accelerate the numerical computation
speed.
Figures 2.15 to 2.17 show a comparative study of PV array characteristics for three
different bypass diode conditions, i.e., no bypass diode employed, one bypass diode for each PV
module, and one bypass diode for each PV cell. The PV array has a configuration of 10 parallel
strings with each string containing 20 modules. Assume there are 19 shaded modules in the 1st
string, 17 in the 2nd string, 15 in the 3rd string and 1 in the last string. In each shaded module,
there is one shaded cell only, which is the worst condition that would damage a PV cell
according to Section 2.2. The shading factors are 0%, 50% and 100%, respectively. From the
figures, other case studies, and comparison with Section 2.3, the following properties are
obtained:
1) If no bypass diodes are applied, the PV array characteristics can be shifted
significantly by shaded cells (Fig. 2.15a and Fig. 2.15b). The degree of the shift depends on how
many strings contain shaded cells, how many shaded cells are in each string and how much the
shading factors are. When there is only one shaded cell in a string, all the photogenerated
voltages of the unshaded cells in that string are applied to the shaded cell (Fig. 2.15c), which
would cause a high risk to damage the shaded cell due to the high absorbing power of the shaded
cell (Fig. 2.15d).
2) If each PV module has one bypass diode, it is found that there is an improvement in
the PV array characteristics under shading conditions depending on the distribution of the shaded

28

cells in the PV array. For each string if the number of the shaded cells is the same, the best
situation is that all the shaded cells appear in one module. However, if the shaded cells are
distributed evenly in different modules in a string, the enhancement of the PV array
characteristics is trivial (Figs. 2.16a and 2.16b). If there is only one shaded cell in a module,
then, all the photogenerated voltages of the unshaded cells in that module are applied to the
shaded cell (Fig. 2.16c). Compared to Fig. 2.15d, the absorbing power of the shaded cell under
100% shading condition is reduced a lot but changes very little for 50% shading condition.
Another impact of the bypass diodes is that multiple peaks would result in the P-V characteristics
of the PV array. The extent of the multiple peaks depends on the distribution of the shaded cells
in the PV array as well as the number of parallel strings and the number of series modules in
each string. For Fig. 2.16b, multiple peak impact can be seen clearly when the figure is enlarged.
Hence, using traditional MPPT approaches [37-40], one may get into a local peak power point so
that the efficiency of the PV module would be reduced greatly.
3) If each PV cell has a bypass diode, the influence of the shaded cells to the PV array
characteristics is significantly reduced. Compared to both Figs. 2.15d and 2.16d, the absorbing
power of the shaded cell is very small (Fig. 2.17d). Under the condition that the number of the
shaded cells is significantly less than that of the unshaded cells, the P-V characteristics of the PV
array is very close to the unshaded condition no matter how the shaded cells are distributed in the
PV array (Fig. 2.17b). Therefore, with a bypass diode for each PV cell, it is more convenient to
manage the MPPT control of the PV array even under shading conditions, implying that a new
solar PV cell design with a bypass diode would be a significant benefit for extraction and
management of solar PV energy.

29

None
50%
100%

20

100

200

300

400

40
None
50%
100%

20
0

500

Current (A)

Current (A)

Current (A)

40

60

60

60

100

200

300

400

40
None
50%
100%

20
0

500

100

200

Vs (V)

Vs (V)

300

400

500

Vs (V)

a) PV array I-V characteristics a) PV array I-V characteristics a) PV array I-V characteristics

10
5

10
5
0

100

200

300

400

None
50%
100%

15

500

100

200

300

400

None
50%
100%

15

Power (kW)

Power (kW)

Power (kW)

None
50%
100%

15

20

20

20

10
5
0

500

100

200

Vs (V)

Vs (V)

300

400

500

Vs (V)

b) PV array P-V characteristics b) PV array P-V characteristics b) PV array P-V characteristics


10

Voltage (V)

Voltage (V)

0
-10
-20

None
50%
100%

-30
-40

100

200

300

400

-20

500

None
50%
100%

0.5

-10

-30
0

None
50%
100%

Voltage (V)

10

-0.5

100

200

300

400

500

100

200

300

400

500

Vs (V)

Vs (V)

Vs (V)

c) Shaded cell terminal voltage c) Shaded cell terminal voltage c) Shaded cell terminal voltage
characteristics of the last string characteristics of the last string characteristics of the last string
100

-100
None
50%
100%

-200

0
-50
-100
-150

100

200

300

400

500

Vs (V)

d) Shaded cell P-V


characteristics of last string

None
50%
100%

Power (W)

Power (W)

Power (W)

-300

50

0
-2
-4

100

200

300

400

500

Vs (V)

d) Shaded cell P-V


characteristics of last string

None
50%
100%

100

200

300

400

500

Vs (V)

d) Shaded cell P-V


characteristics of last string

Fig. 2.15. PV array

Fig. 2.16. PV array

Fig. 2.17. PV array

characteristics

characteristics

characteristics

(without bypass diode)

(one module with a diode)

(each cell with a bypass diode)

2.5 Virtual Transient Experiment


30

The behavior of the solar PV system is further examined under more realistic transient
conditions through a virtual experiment by using MatLab SimPowerSystens, which includes: 1)
actual circuit connection of the solar PV array, 2) open-loop controlled power converter
including inductors and capacitors, and 3) losses of the system. Figure 2.18 shows the transient
simulation system. The dc voltage source stands for the dc-link voltage between the dc/dc
converter and the dc/ac inverter (Fig. 2.14). The dc/dc converter is a boost converter, i.e., power
flows from the PV array to the dc voltage source. The PV array is represented by a subsystem
containing all the PV modules in series and parallel. At each time instant, the Newton-Raphson
algorithm is used to find the current and voltage of each solar cell. The parameters of the solar
PV system are the same as those used in the characteristic study (Figs. 2.15-17). The number of
series and parallel PV modules are 20 and 10, respectively. Major measurements include current,
voltage and power of PV cells, modules, and array under test. For power measurement, generator
sign convention is used, i.e., power generated by a PV cell, module, or array to the dc source is
positive.

Fig. 2.18. Solar PV generator under an open-loop controlled dc/dc


power converter using SimPowerSystems
31

600

200

Voltage (V)

300

-25

Power

-10

-50

-15

-75

-20

-100

-25

-125

100
0

-5

Power

400

Power (kW)

Voltage (V)

500

0
Voltage

Power (W)

Voltage

4
Time(s)

0
8

a) PV array terminal voltage and power

-30

4
Time(s)

-150
8

b) Shaded cell terminal voltage and power of the

last string
Fig. 2.19. Transient simulation results of a PV array relevant to
the 100% shading condition applied in Fig. 2.16

In Fig. 2.18, the average power converter model [41] is used, in which the duty ratio is a
ramp function of time, which causes the voltage applied to the PV array increases with the time
until the full dc source voltage is reached. Figure 2.19 shows the transient results corresponding
to the 100% shading condition used in Fig. 2.16. The dc source voltage is 500V. As it can be
seen from Fig. 2.19a, the voltage applied to the PV array increases with time. The output power
of the PV array increase, reaches maximum output power, and then decreases, a phenomenon
similar to Fig. 2.16b. The terminal voltage of the shaded cell is around -20V before the bypass
diode turns on (Fig. 2.19b) and the absorbing power of the shaded cell is about 120W (Fig.
2.19b), which is consistent with the steady-state characteristics shown in Fig. 2.16d. Under the
uneven shading condition and a bypass diode for each PV module, the output power of the PV
array also shows the multiple peaks (Fig. 2.19a) in the transient environment, which is consistent
with Fig. 2.16b. For all the other conditions, the results obtained through the transient simulation
experiment agree with stead-state characteristic results, demonstrating that the models and

32

Newton-Raphson algorithm are suitable for transient analysis of power converter controlled solar
PV systems.

2.6 Conclusions

This chapter investigates IV and PV characteristics of solar PV cells, modules and


arrays and it focuses specifically on IV and PV characteristics of a solar PV system operated
under uneven shading and dissimilar conditions.
Under uneven shading conditions, the charge carriers of the unshaded cells have to go
through parallel resistors of the shaded cells. To push the current through the parallel resistor, the
accumulated photogenerated voltage of each unshaded cell must be high. The net photogenerated
voltage of all the unshaded cells causes: (1) a high current through the parallel resistors of the
shaded cells, (2) a high-reverse terminal voltage on each shaded cell, and (3) a high absorbing
power by each shaded cell, especially when the voltage applied to the PV cells is low. Thus, the
unshaded cells generate power, while the shaded cells absorb power, depending on the external
voltage applied to PV cells or modules.
Using bypass diodes, the voltage applied to the shaded cells equals the photogenerated
voltages of the unshaded cells within the bypass diode group plus the bypass diode forward
conduction voltage. Thus, the less the PV cells within a bypass diode group, the smaller the
reverse voltage over shaded cells, and the less the shaded cells absorb power. To prevent shaded
cells from becoming hot spots, the number of series PV cell within a bypassing diode group
should be properly designed.
For a solar PV array, if no bypass diodes are applied, the PV array characteristics can be
shifted considerably by shaded cells depending on how many strings contain shaded cells and
33

how many shaded cells are in each string. If there is only one shaded cell in a string, the shaded
cell would be in the worst condition due to its high absorbing power. If each PV module has one
bypass diode, the improvement of the PV array characteristics depends on the distribution of the
shaded cells in the PV array. The best situation is that all the shaded cells appear in one module.
However, if the shaded cells are distributed evenly in different modules in a string, the
enhancement of the PV array characteristics is trivial. If each PV cell has a bypass diode, the
influence of the shaded cells on the PV array characteristics is significantly reduced in various
aspects no matter how the shaded cells are distributed in the PV array, implying that a new solar
PV cell design with a bypass diode would be a significant benefit for energy extraction and
management of solar PV energy (Chapter 4).
The models developed in this chapter as well as the NewtonRaphson algorithm
applications are suitable for transient analysis of power converter-controlled solar PV systems,
making it possible to develop and test advanced MPPT control strategies for solar PV systems
under shading conditions through virtual computer experiments.

34

CHAPTER 3
A FAST AND RELIABLE APPROACH FOR MAXIMUM POWER POINT TRACKING

PV generation systems have two major problems: the conversion efficiency of electric
power generation is very low (9-17%) [42], especially under low irradiation conditions; the
amount of electric power generated by solar arrays changes continuously with weather
conditions. The power delivered by a PV system of one or more photovoltaic cells is dependent
on the irradiance, temperature, and the current drawn from the cells. In general, there is a unique
point on the I-V and P-V curve, called the maximum power point (MPP), at which the entire PV
system operates with maximum efficiency and produces its maximum output power. The
location of the MPP is not known, but can be located, either through calculation models or by
searching algorithms. To maximize the output power of a PV system, continuously tracking the
maximum power point of the system is necessary.
There are many different approaches to maximizing the power from a PV system. These
range from using simple voltage relationships, to more intelligent and adaptive based algorithms.
Typical MPPT techniques that have been proposed in the literature include the Short-Circuit
Current method [43], Open-Circuit Voltage method[44], Perturb and Observe (P&O) methods
[45, 46], Incremental Conductance (IC) methods [47, 48, 49], and Adaptive P&O method [50,
51], and Intelligent and Fuzzy Logic methods [52, 53]. These techniques vary between each
other in many aspects, including simplicity, convergence speed, system stability, and MPP
tracking effectiveness. The primary challenges for maximum power point tracking of a solar PV
array include: 1) how to get to a MPP quickly, 2) how to stabilize at a MPP, and 3) how to
35

smoothly transition from one MPP to another for sharply changing weather conditions. In
general, a fast and reliable MPPT is critical for power generation from a solar PV system.

3.1 Extracted Power Characteristics of a PV System

A grid-connected solar PV system consists of three parts (Fig. 3.1): an array of solar
cells, power electronic converters, and an integrated control system [44, 45]. The control system
of a solar PV array contains two parts: one for MPPT and the other for grid interface control [4952]. Both control functions are achieved through power electronic converters. In general, the
dc/dc converter implements the MPPT function while the dc/ac converter performs the gridinterface control.

Fig. 3.1. Configuration of grid-connected solar PV system

The power extracted from a PV array Pa is determined by the terminal voltage Va and
output current Ia of the array. The terminal voltage Va depends on the control of the dc/dc
converter while the output current Ia depends on temperature, irradiation level, and the PV array
36

terminal voltage. During a day, solar irradiation and temperature fluctuates over time [54] (Fig.
3.2), causing the MPP of the PV array changes continuously. Consequently, the PV system

90

Temp

1000

Irra

800

80

600

70

400

60

200

50

12
Time (Hour)

16

20

Solar Irradiation(W/m2)

Temperature (F)

operating point must be adjusted constantly to maximize the energy produced.

0
24

Fig. 3.2. Typical daily temperature and irradiation plots [54]

3.1.1 The Effect of Temperature

Temperature affects solar cell characteristics primarily in the following two ways:
directly via T in the exponential term in (3.1) and indirectly via its effect on the reverse-diode
saturation current I0 and the photo-generated current IL. The dependence of the reverse-diode
saturation current I0 on temperature for a silicon solar cell is:

I0 K T e
3

q Eg
mk T

(3.1)

where K is the approximate constant with respect to temperature, Eg is the band-gap energy of
the semiconductor (eV), m is the diode ideality constant, k is Boltzmann constant, and T (K) is
the temperature of the pn junction. The photo-generated current IL is also influenced by the
temperature too as the following:
37

I L ( I L,n K I T )

E
En

(3.2)

where IL,n is the photo-generated current at the nominal condition, T is the difference between
actual temperature T and nominal temperature Tn (25C), respectively, E is the irradiation on the
device surface (W/m2), and En is the nominal irradiation (1000 W/m2).

25
20

P(kW)

15
10
5
0
100
75
50
25
0

T ( oC)

100

200

300
Vs (V)

400

500

700

600

Fig.3.3. P-V characteristics of a PV array vs. temperature and voltage


(Nc=36, Ns=30, Np=10, Rp=6.6and Rs=0.005)

0.1
T=0
T=20
T=40
T=60
T=80
T=100

dP/dV (kW/V)

0.08
0.06
0.04
0.02
0
-0.02
-0.04

100

200

300
400
Vs (V)

500

600

700

Fig.3.4. Derivative of power over terminal voltage under different temperatures

Then, based on (3.1) and (3.2), characteristics of a PV array versus the PV cell
temperature and the terminal voltage of the array can be obtained as shown by Fig.3.3.
38

According to Fig. 3.3, as the temperature increases, the maximum power production of the PV
array drops greatly and the MPP voltage reduces, indicating that PV arrays perform better on
cold days than hot ones. Figure 3.4 shows the derivative of the output power versus PV array
terminal voltage for several constant temperatures. For each constant temperature, the voltage
corresponding to the zero derivative represents the required voltage for MPP. The derivative has
a stable positive value before reaching the MPP, and then drops sharply around the MPP. As
temperature increases, the zero derivative point shifts to the left.

3.1.2 The Effect of Illumination Intensity

The photo-generated current is affected by the irradiance intensity. First, without


consideration of temperature impact by the irradiance levels, the short-circuit current of a solar
cell is directly proportional to the irradiance intensity over a wide operating range. Assume that S
stands for the ratio of the present solar irradiation over the nominal irradiation of 1000W/m2 and
the short-circuit current of the solar cell at 1000W/m2 is defined by IL1. Then, the short-circuit
current under S is IL = SIL1. Second, the impact of irradiation to the temperature of solar cells is
determined by:
T Tn E En

(3.3)

where is a constant value between a range of 25-35.


Figure 3.5 shows the characteristics of the PV array as the irradiance intensity changes
from 0W/m2 to 1000W/m2. It can be seen from Fig. 3.5 that there is a peak power production
corresponding to each solar irradiation. As the irradiance level increases, the maximum power
increases greatly and the MPP voltage drops slightly due to the temperature rise according to

39

(3.3). Figure 3.6 shows the derivative of PV array power versus terminal voltage of the PV array
for several constant irradiation levels. Compared to Fig. 3.4, as the irradiation level changes, the

P (kW)

shift of the terminal voltage corresponding to zero derivatives is much smaller.

25
20
15
10
5
0
700

0
0.25
0.5
600

500

400

300

0.75
200

100

Vs (V)

Fig.3.5.P-V characteristics of a PV array vs. irradiation and voltage

0.08
s=0.2
s=0.4
s=0.6
s=0.8
s=1

dP/dV (kW/V)

0.06
0.04
0.02
0
-0.02
-0.04

100

200

300
400
Vs (V)

500

600

700

Fig.3.6. Derivative of power over terminal voltage under different irradiation

3.2 Conventional Fixed-step MPPT Methods

There have been reported many traditional MPPT methods for solar PV generators. In
general, the MPPT control is achieved by varying the terminal voltage applied to the PV
generator. Typical MPPT techniques include fixed-step MPPT: Short-Circuit Current method
40

[43], Open-Circuit Voltage method[44], Perturb and Observe (P&O) methods [45, 46],
Incremental Conductance (IC) methods [47, 48, 49].

3.2.1 Short-Circuit Current Method

The SCC method is based on the observation that IMPP is about linearly proportional to
ISC of a PV array (Fig. 3.7a) , i.e.,

I MPP ( S ) k SC I SC ( S )

(3.4)

where kSC is a constant. According to (3.4), the SCC controller (Fig. 3.8a) generates a control
signal to the dc/dc converter based on the error signal between the actual current of the PV array
Ia and the IMPP calculated from (3.4).

IMPP(A)

60
40
20
0

10

20

30

40

50

60

70

ISC (A)

a) Graphic relation of IMPP over ISC

VMPP (V)

600
500
400
300
200
300

350

400

450

500
VOC (V)

550

600

650

700

b) Graphic relation of VMPP over VOC


Fig. 3.7. Graphic relation of IMPP over ISC and VMPP over VOC
41

This method requires measurements of ISC. Therefore, a static switch in parallel with the PV
array is needed in order to create the short-circuit condition for each solar irradiation level
change, which could cause a large oscillation of PV array output power. Another disadvantage is
that the computation of IMPP is very sensitive to kSC, and the relation between IMPP and ISC is not
100% linear. Thus, a small deviation of IMPP, calculated by (3.4), can easily reduce the output
power of the PV array greatly.

I SC

k SC

*
I MPP

ia

a) Control scheme of SCC

VOC

*
VMPP

kOC

va

b) Control scheme of OCV


Fig. 3.8. Conventional MPPT methods of SCC and OCV

3.2.2 Open-Circuit Voltage Method

The OCV method is based on the observation that VMPP is about linearly proportional to
VOC of a PV array (Fig. 3.7b), i.e.,
V MPP ( S ) k OC VOC ( S )

42

(3.5)

where kOC is a constant. Based on (3.5), a close-loop control scheme is developed to bring the PV
array voltage to VMPP calculated from (3.5) (Fig. 3.8b). Similar to the SCC method, the OCV
method requires measurements of VOC. Thus, a static switch in series with the PV array is
necessary in order to create the open-circuit state for each weather condition change, which
would also cause a large oscillation of PV array output power. In addition, since VOC varies with
temperature and other factors and the relation of VMPP and VOC is affected by shading, actual
VMPP for a practical PV application is difficult to get.

3.2.3 Perturb & Observe Method

The P&O method is the most commonly used MPPT technique for PV arrays. It operates
by periodically perturbing the array terminal voltage or current and comparing the PV output
power with that of the previous perturbation cycle.
In general, if an increased perturbation of PV array operating voltage causes an increase
of output power, the control system moves the operating point in the same direction; otherwise
the perturbation is changed to the opposite direction. The process continues until the MPP is
reached [55-57]. There are many different P&O methods available in the literature. In the classic
P&O technique [41] (Fig. 3.9), the perturbations of the array operating point have a fixed
magnitude. In the optimized P&O technique [55, 56], an average of several samples of the array
power is used to adjust the perturbation magnitude.

43

Va (k ) & I a (k )

Va (k ) & I a (k )
Va (k 1) & I a (k 1)

Pa (k ) Va (k ) I a ( k )
Pa (k 1) Va (k 1) I a (k 1)
Pa Pa (k ) Pa (k 1)
Va Va (k ) Va (k 1)

Pa 0?
Va 0?

Va 0?

Vref

Vref

Vref

Vref

Fig.3.9. Flowchart of the fixed step P&O algorithm

3.2.4 Incremental Conductance Method

The IC method is based on the principle that ideally the following equation holds at the
MPP [47, 51]:
I a Va I a Va 0

(3.6)

Also, when the operating point in the P-V plane is to the right of the MPP,
I a Va I a Va 0 ; when the operating point is to the left of the MPP, Ia Va I a Va 0. Thus,

the direction in which the MPP operating point must be perturbed can be determined by
comparing the instant conductance I a Va to the incremental conductance I a Va . Using the IC

44

method (Fig. 3.10), it is theoretically possible to know when the MPP is reached and when the
perturbation should be stopped.

Va (k ) & I a (k )

Va (k ) & I a (k )
Va (k 1) & I a (k 1)

I a I a (k ) I a (k 1)
Va Va (k ) Va (k 1)
Va 0?

Vref

I a Va I a / Va ?

I a 0?

I a Va I a / Va ?

I a 0?

Vref

Vref

Vref

Fig.3.10. Flowchart of the incremental conductance algorithm

3.3 Adaptive MPPT Strategies

In a PV system, the maximum power point tracking speed and tracking accuracy are the
key factors for a MPPT control algorithm. These factors directly relate to the duty ratio
adjustment of the dc/dc converter. When the PV system operating point is away from the MPP,
the tracking speed must be accelerated, i.e., the regulation of the duty ratio should be large.
When the operating point is around the MPP, the regulation of the duty ratio must be small to

45

avoid system oscillation. However, conventional fixed-step MPPT algorithms as shown by


Section 3.2 are unable to meet those MPPT requirements [58, 59], resulting in many
disadvantages such as instability, oscillations near MPP, poor adaptability to the external
environment, and low system robustness. Thus, adaptive MPPT approaches have been proposed
recently, including M-factor adaptive-step MPPT, fuzzy logic based MPPT [52, 53], neural
networks MPPT [60, 61] and ripple correlation control (RCC) MPPT [62, 63], etc. However,
some of them may still be inappropriate in respective of suppleness in applications and accuracy
at different occasions. For example, RCC lacks the mathematical foundation and careful stability
analysis that is attractive for control design. RCC is limited to first-order high-pass filters, which
approximate the derivative at low frequencies [63].
The proposed method is developed based on observations obtained from Figs. 3.4 and
3.6: 1) on the left side of the MPP, dPa dVa is positive; 2) On the right side of the MPP, dPa dVa
is negative; 3) Around the MPP, the | dPa dVa | drops sharply so that the adjustment of the duty
ratio of the dc/dc converter should be small; 4) At the MPP, dPa dVa =0 and therefore the duty
ratio should remain unchanged.

3.3.1 Traditional Adaptive MPPT Methods

In conventional adaptive MPPT methods, the perturbation value changes during the hill
climbing process [50, 55]. Typical adaptive P&O methods use power derivative information to
determine the next perturbation operation. It is based on the observation that the derivative is
positive on the left side of the MPP, zero at the MPP, and negative on the right side of the MPP
(Fig. 3.4 and 3.6). Thus, a scaling factor (SF) perturbation strategy is developed as shown by

46

(3.7), in which M is a constant coefficient and the multiplication of M with the derivative
determines an adaptive adjustment of the duty ratio in the next perturbation cycle [55]. Hence,
the duty ratio adjustment is scalable rather than fixed. Similar to the IC method, the perturbation
stops theoretically when the MPP is reached.
d (k ) d (k 1) M

dPa
dVa

(3.7)

Another conventional adaptive duty ratio strategy is based on a proportional-integral (PI)


control mechanism (Fig. 3.11). The error signal to the controller is generated by comparing
dPa dVa with a zero power derivative reference value. The duty ratio of the dc/dc converter is

regulated continuously until the MPP is reached, i.e., dPa dVa 0.

Va
Ia

dPa
dVa

D
0

Fig.3.11. PI based MPPT control loop diagram of the PV system

3.3.2 Proposed Hyperbolic -PI (H-PI) Adaptive MPPT Method

The proposed adaptive MPPT strategy has adopted the advantage of the inner close-loop
control mechanism for the duty-ratio regulation. But, it introduces a hyperbolic function (3.8)
into the MPPT design.

47

y tanh k dPa dVa

(3.8)

where k is a constant value which is tuned to meet a fast and reliable MPPT requirement for a
typical solar PV array. The output of the sigmoid function (Fig. 3.12) is close to 1 if |dPa /dVa| is
large while around dPa dVa =0, the output reduces greatly. This hyperbolic function enables a
more accurate and stable, and much faster tracking properties under dynamic condition. The
control diagram of the proposed H-PI method is shown by Fig. 3.13, the measured voltage and
current are first processed through a low-pass filter. Then, the power over voltage derivative is
processed by a hyperbolic function and the adjustment amount of the duty-ratio is determined by
a PI controller. Finally, a new duty-ratio computed from this block is applied to the power

y=tanh(4*x)

converter for the next control cycle.

1
0.5
0
-0.5
-1
-1

-0.5

0
x

0.5

Fig.3.12. A tangent sigmoid function for adaptive MPPT

Va
Ia

dPa
dVa

tanh(k

dPa
)
dVa

D
0

Fig.3.13. Control loop diagram of proposed adaptive MPPT

48

One issue for the proposed MPPT is the computation associated with the tanh()
function. In general, the tanh() can be calculated very quickly in a digital control system.
According to a large number of experiments performed over a 2GHz PC, the average
computation time of tanh() in MatLab is about 10ns. Compared to the controller sampling time,
the computation time of tanh() is much smaller and ignorable. For tanh() implementation in a
DSP chip, the additional computational effort is even more insignificant.

3.4 Computational Experiment

To evaluate and compare different MPPT approaches, a computational experiment


platform of the integrated PV array and power converter system is developed. The experiment
system mainly includes three parts: a PV array module, a power converter module, and a control
module.

Fig.3.14. Solar PV generator with the MPPT and grid-integration using


SimPowerSystems (SPS) and Opal-RT RT-LAB

49

The PV array module has a series-parallel PV panel connection configuration. An


external bypass diode in parallel with each PV panel is also considered [23]. In addition,
blocking diodes are included at the top of each string [23]. The PV array module consists of 10
parallel strings with each string having 20 series panels. Each string of PV panels is represented
by a subsystem containing all the PV panels in series (Fig. 3.14). The mathematical model of a
PV panel is developed according to (2.1) and Fig. 2.3. Major measurements of the PV generator
include current and voltage of each PV panel, current and voltage of the PV array, and the output
power of the PV array. The generator sign convention is used, i.e., power transferred to the grid
is positive.
The power converter is a dc/dc boost converter. The dc voltage source shown in Fig. 3.14
represents the dc-link voltage (Fig. 3.1). For a fast and accurate simulation, the converter
modules from Opal-RT RTE-Drive toolbox are used. These converter modules can be integrated
with the RTE PWM signal generation function from the Opal-RT RT-EVENTS toolbox to
generate very fast and accurate drive pulses for a precise simulation of power converters [64].
The switching frequency is 10kHz, and losses of the power converters and the system are
considered.

fc

fc

Fig.3.15. MPPT digital control module

50

Modern MPPT algorithms are usually implemented by using the digital control
technology. The MPPT control module of this paper is developed with detailed consideration of
digital control system natures, including the sample and hold, digital signal processing, and time
delays (Fig. 3.15). The measured voltage and current signals first pass through sample and hold
blocks, which converts measured continuous signals to discrete signals. Then, a digital
filtering mechanism is applied to remove high frequency components caused by noises or rapid
switching of power converters. A time delay block is applied to account for potential delay
between digital and physical systems. The comparison in this section focuses mainly on IC fixed
step, traditional scaling factor (SF) adaptive, and the proposed hyperbolic-PI based (H-PI) MPPT
methods.

3.4.1 MPPT under Step and Ramp Changes of Solar Irradiation

The temperature during a day normally does not change sharply, but solar irradiation
levels could vary quickly from one value to another. To test and compare MPPT algorithms
under abrupt changes of solar irradiation levels, a solar irradiation curve with step and ramp
changes is generated (Fig. 3.16). The irradiation increases suddenly from 400W/m2 to 1000W/m2
at 1.5s, stays at 1000W/m2 between 1.5s to 2.2s, and drops to 600W/m2 at 2.2s. At 2.9s, there is a
ramp change of solar irradiation levels. The solar irradiance level increases gradually until it
reaches 900W/m2 at 3.2s, maintains at this value for a period of 0.6s, and drops slowly to
700W/m2 at 4s.
The PV array maximum power, along with the captured power by using IC, SF and H-PI
methods under the step and ramp changes of solar irradiation levels, is presented by Fig. 3.17a.
The sampling rate of the MPPT control module is 0.1ms.
51

Irradiation (k W /m 2)

1
0.8
0.6
0.4
1.5

2.5

3
Time (s)

3.5

4.5

Fig. 3.16. Step and ramp changes of irradiation

320

14

60
50

300

12
10

40

280

Max
1.5

2.5

IC
3
Time(s)

HPI
S-PI

SF
3.5

(HPI)

260
1.5

4.5

2.5

3
Time(s)

3.5

30
4.5

b) Current & voltage of SF & H-PI MPPT

a) PV array output power


Output Power (kW)

Output Power (kW)

16.6
16.4
16.2
16

Max
1.5

1.51

1.52

IC
1.53
Time(s)

HPI
S-PI

SF
1.54

1.55

15
14.5
14

1.56

3.14

c) A zoomed in a) at a step change


x 10

O u tp u t P o w e r(kW )

detD

0
-2
-4
IC
1.5

3.18
Time(s)

HPI
S-PI

SF
3.2

3.22

3.24

16

-6

3.16

IC

d) A zoomed in a) at an increasing slope

-3

Max

13.5

HPI
S-PI

SF
2.5

3
Time(s)

3.5

4.5

IC
SF
HPI
S-PI
PV curve (S=0.6)
PV curve (S=0.9)
Max Power Points

0
0

50

12
8

100

150

200

250

300

350

Vs (V)

e) Changes of duty ratio

f) P-V locus at the increasing slope

Fig. 3.17. Comparison of MPPT under step and ramp changes of solar irradiation levels
52

400

C u rre n t (A )

Voltage(HPI)
(S-PI)

Voltage (SF)

V o lta g e (V )

Output P ower (kW )

340
16

The current and voltage waveforms of the proposed MPPT are shown by Fig. 3.17b.
Figures 3.17c and 3.17d are the zoom-in plots of Fig. 3.17a. Figure 3.17e presents the duty-ratio
adjustment during the MPPT control. Figure 3.17f shows, for the three MPPT methods, the
power vs. voltage locus for a slope change of the solar irradiation level from 0.6kW/m2 to
0.9kW/m2 around 3sec (Fig. 3.16).
For the IC method, it is quite stable under sharp and gradient solar irradiation changes.
The primary issue of the IC method is a continuous perturbation in duty ratio (Fig. 3.17e) even
when the solar irradiance level is stable. The extent of the oscillation depends on the perturbation
step selected. The smaller the perturbation step, the smaller the oscillation. However, if the
perturbation step is too small, the MPPT speed would be affected.
For the SF method, there is a very small oscillation when the irradiation level remains at
a stable level, at which the power over the voltage derivative is close to zero (Fig. 3.17 e). But,
for changing irradiation levels, the output power of the PV array oscillates a lot as demonstrated
by time-domain waveforms (Figs. 3.17c and 3.17d) and the power vs. voltage locus plot (Fig.
3.17f). This results from a sharp change of around the MPP (Fig. 3.4 and 3.6), causing unstable
variation in duty ratio.
The proposed H-PI approach shows the best performance (Figs. 3.17a, 3.17c, 3.17d, and
3.17f). This is due to the fact that the duty ratio adjustment of the H-PI method is tuned based on
the power and voltage derivative that is preprocessed through a hyperbolic function as shown by
(3.8). As it can be seen in Fig. 3.17e, the change in duty ratio has a smoothly continuous value
during an abrupt or ramp change of solar irradiation, and is around zero when the solar
irradiation is stable.

53

DC link V oltage (V )

1,250
1,225
1,200
1,175
1,150

1.5

2.5

3
Time(s)

3.5

4.5

3.58

3.6

G rid-s ide Current (A )

Fig. 3.18 Dc-link voltage

1,000
500
0
-500
-1,000
3.5

3.52

3.54
3.56
Time(s)

Grid P ower (k W )

Fig. 3.19 Three-phase grid-side currents

50
25
0
-25
-50

1.5

2.5

3
Time(s)

3.5

4.5

Fig. 3.20 Dc/ac inverter power at the grid side

The PV voltage and current oscillate continuously (Fig. 3.17b), particularly under
changing solar irradiation conditions. This causes more oscillation of the instantaneous power of
the PV array. This issue is critical and must be considered in the design of the low-pass filters
54

(Fig. 3.15) to assure fast and robust MPP tracking, particularly for the adaptive MPPT techniques
(Figs. 3.11 and 3.13). The power vs. voltage locus as shown by Fig. 3.17f illustrates more clearly
how the maximum power is tracked by using three different MPPTs approaches. As it can be
seen from the figure, the proposed adaptive MPPT is more reliable and efficient in tracking the
MPP than the conventional adaptive MPPT.
The dc-link voltage is very stable (Fig. 3.18) under the direct-current vector control
strategy applied to the dc/ac inverter, which is an important factor for the MPPT. The threephase current waveform on the grid side is shown by Fig. 3.19 and the instantaneous grid power
is shown by Fig. 3.20. As shown by Fig. 3.20, the grid power follows the captured PV power.
However, due to the existence of harmonics and unbalance in the grid three-phase currents, there
are oscillations in the grid power, which is similar to the instantaneous grid power in other
renewable energy applications [65, 66].

3.4.2 Sampling Rate Impact

When designing a digital control system, sampling rate is usually predefined. After that,
the perturbation rate for each MPPT technique should be designed independently until an
acceptable performance is obtained. Figure 3.21 shows the maximum power tracking by using
the three different MPPT techniques under the sampling rate of 1ms per sample and 10ms per
sample, respectively.
As shown by Fig. 3.21a, all the MPPT methods can track MPP when the sample time is
1ms. However, when the sample time is 10ms, there will be a big notch in the captured power by
IC and SF method (Fig. 3.21b). An examination of power vs. voltage locus (Fig. 3.21c) reveals
more detailed information about the MPP tracking using the three different MPPT approaches.
55

The figure, consistent with Fig. 3.17f, demonstrates that the proposed adaptive MPPT is more
reliable. Overall, the proposed method responds much faster and is more stable under different

Output P ower (kW)

irradiation conditions.
16
14
12
10
8

Max
1.5

IC
2.5

SF

3
Time(s)

H-PI

3.5

4.5

Output Power (kW)

a) 1ms per sample


16
14
12
10
Max

8
1.5

2.5

IC
3
Time(s)

SF
3.5

H-PI
4

4.5

b) 10ms per sample

O u tp u t P o w e r(k W )

16

IC
SF
HPI
S-PI
PV curve (S=0.6)
PV curve (S=0.9)
Max Power Points

0
0

50

12
8

100

150

200

250

300

350

400

Vs (V)
c) Power vs. voltage locus at the increasing slope change (10ms)
Fig. 3.21. MPPT comparison under different sampling rates
56

It is needed to point out that the sampling rate determines the waiting time for the next
perturbation. From this point of view, the sampling rate concept is not exactly equivalent to the
cutoff frequency notion normally used in the digital signal processing field. In a MPPT algorithm
for a PV array, the low-pass filters shown in Fig. 3.15 help to remove noises while the sampling
rate determines how fast to conduct the next perturbation. The impact of the sampling rate can be
seen from Fig. 3.21. In general, as the sampling time increases, it is slower to track the maximum
power.

3.4.3 MPPT under Variable Solar Irradiation Condition

In reality, solar irradiation level changes constantly over time [67]. Therefore, it is
important to evaluate and compare MPPT performance under variable irradiance conditions. For

20
Output P ower (kW )

Irra d ia tio n (k W /m 2 )

this purpose, a variable solar irradiation curve is generated (Fig. 3.22a).

0.8
0.6
0.4
0.2
0
0.5

1.5
Time (s)

2.5

a) Variable solar irradiation levels

Max

IC

SF

HPI
S-PI

15
10
5
0
0.5

1.5
Time(s)

2.5

b) PV array maximum and output power

Fig.3. 22. MPPT comparison under variable solar irradiation condition

Figure 3.22b compares the MPP tracking using different MPPT algorithms and the
parameters of the MPPT algorithms are the same as those used in Fig. 3.17. As shown by the

57

figure, among the three algorithms, the proposed H-PI method is the most effective to track the
MPP. For the IC method, the fixed step perturbation disables the fast changing requirement in
duty ratio to track the MPP. For the SF method, a stable adaptive adjustment based on the
derivative information is hard to obtain in tracking the MPP under fast changing weather
conditions.

3.5 Hardware Experiment and Comparison

In this chapter, not only the software simulation but also the hardware experiment has
been applied for the comparison of different MPPT schemes.

3.5.1 Laboratory Setup and Design

A hardware laboratory test system of Fig. 3.14 is built for further investigation of the
conventional and proposed MPPT algorithms. Figure 3.23 shows the testing system with the
following setups. 1) An Agilent E4360A solar simulator is used to represent an actual PV array
[68]. The solar simulator can generate real output voltage and current with relation that is
equivalent to a practical PV panel or array. By using the solar simulator, it is possible to repeat
the same solar irradiation condition to test and compare different MPPT algorithms through this
hardware experiment which is otherwise impossible. Another advantage is that the maximum
output power of the simulated PV array can be calculated based on the experiment settings so
that one can determine whether a MPPT algorithm is effective or not in a hardware experiment.
Due to these reasons, solar simulators have been widely used by many researchers around the
world for evaluation of a PV control system [69]. 2) The dc/dc converter is built by using a
58

LabVolt MOSFET power converter. 3) The capacitor connected to the output terminal of the
simulator is formed by several LabVolt capacitors in parallel. 4) A smoothing inductor is
employed for the dc/dc converter. 5) The solar simulator is controlled by a dSPACE digital
control system [70].
The control system collects output voltage and current signals of the solar simulator, and
sends a control signal to the converter based on control demands generated by different MPPT
algorithms. Although the dSPACE system is not a digital device used for practical applications,
it is a digital control system based on modern DSP chips [71]. Using the dSPACE system, a
MPPT digital controller can be quickly built and tested before converting it to a practical digital
control device.

Fig. 3.23. Hardware experiment setup for evaluation of MPPT algorithms

3.5.2 Experiment Analysis and Comparison


59

The rated values of the hardware experiment system (Fig.3.23), including the power
converter and the PV simulator, are different from those used in the computational experiment
(Fig.3.14). In general, the rating of the hardware experiment system is lower than the rating of a
practical PV array. Therefore, parameters of the MPPT controllers must be retuned. To ensure
that the controllers work properly, the retuned MPPT algorithms for both the conventional and
proposed techniques are evaluated in simulation first before the hardware experiment, where the
simulation time step for the controllers is the same as the sampling time used in the dSPACE
digital control system. Another big challenge, that is different from the simulation, is that noises
are more significant than expected. One strategy to reduce the noises is to increase the strength
of the measured signals.
Because of the noises, it is very hard to tune MPPT parameters for IC and SF algorithms,
especially for the SF algorithm. This is due to the fact that a noise can result in a high notch in
the calculated power during the next sampling time, causing a large variation in power derivative
and thus affecting the stability of the SF algorithm. However, for the proposed H-PI algorithm, a
stable MPPT algorithm is much easier to obtain. The test sequence is scheduled as the following
with t=0s as the starting point for data recording. Around t=20s, there is an increase of the solar
irradiation. A small increase of the solar irradiation appears near t=40s. Close to t=60s, there is a
large decrease of the irradiation. At about t=80s, the sequence repeats itself. The PV simulator
voltage and current are not only collected by the dSPACE system but also monitored by
oscilloscopes and/or meters. Figure 3.24 shows the captured maximum power by all the three
algorithms. Again, the proposed H-PI approach has the best performance because for the
proposed H-PI approach, the power derivative is smoothly processed before it is applied to the PI
controller. In addition, PI controller can responds much faster than an open-loop scheme.

60

10

Output Power (W)

Output Power (W)

12.2

IC
SF
S-PI

12

8
6
0

20

40

60

80

100

Time

12
11.8
11.6
11.4
11.2

IC
40

45

50

SF

S-PI

55

Time

a) Captured output power in a long time range

b) A zoom in of the captured output power

Fig. 3.24. Hardware experiment of captured maximum power using


conventional and proposed MPPT algorithms

3.6 Conclusions

This chapter proposes a fast and robust MPPT technique and compares it with typical
conventional MPPT algorithms used in solar PV industry (Table 3.1).
Among the three most popular conventional MPPT algorithms (fixed step P&O, IC and
adaptive P&O), the fixed step P&O and IC methods have continuous oscillation even when the
solar irradiance level is constant in the power converter switching environment; the adaptive
P&O method has very small oscillation if the solar irradiance level is stable. For the proposed
MPPT approach, it has the least oscillation and the highest stability.
The sampling rate affects the design of the perturbation rate. This result indicates that a
match between the sampling rate and the perturbation step is important. If the sampling rate is
too slow, a stable and reliable MPPT would be hard to achieve. Again, the proposed method is
more stable and reliable under different sampling rate conditions.
Under the variable irradiance levels, the proposed H-PI approach has better performance
than conventional methods, indicating that the power derivative information is valuable in

61

tracking and capturing maximum PV array power under changing weather conditions. The
comparison between the traditional and proposed adaptive methods shows that the hyperbolic
processing of the derivation is important for high performance of a solar PV system.

Table 3.1. Comparison of MPPT methods


Oscillation

Sensed

around MPP

Parameters

Low

No

Current

No

Low

No

Voltage

P&O

Yes

Low

Yes

V/C

IC

Yes

Medium

Yes

V/C

SF

Yes

Low

No

V/C

RCC

Yes

Low

No

V/C

Fuzzy/Neural

Yes

High

No

Varies

Proposed H-PI

Yes

Low

No

V/C

MPPT

True

Technique

MPPT

SCC

No

OCV

Complexity

In the hardware experiment, the unexpected noises would drastically influence the power
increment or power derivative calculation in the next perturbation step. Because of the noises, it
is very hard to tune the MPPT parameters for IC and SF algorithms, especially for the SF
algorithm. However, for the proposed H-PI approach, the power derivative is smoothly
processed before it is applied to the PI controller; in addition, PI controller can respond much
faster than an open-loop scheme. The comparison demonstrates that the proposed H-PI approach
is much easier to tune and has the best performance.

62

CHAPTER 4
PV ENERGY EXTRACTION CHARACTERISTICS STUDY UNDER SHADING
CONDITIONS FOR DIFFERENT CONVERTER CONFIGURATIONS

A solar PV energy conversion system requires power converters for maximum power
extraction and grid integration. At present, many different converter structures have been
developed and used in a solar PV system. For all the different converter structures, the energy
extraction characteristics and maximum power capture capability for all the converter schemes
under even solar irradiation are very similar. However, under shading conditions, the energy
extraction depends strongly on what converter structure is used in a PV system.

4.1 Configurations of Grid-connected Solar PV Systems

A grid-connected solar PV system consists of three parts: an array of solar panels, power
electronic converters, and an integrated control system [13, 72]. Normally, solar cells are
connected in series to form a module that gives a standard dc voltage. For an application,
modules are connected into an array to produce sufficient current and voltage to meet a demand
[23]. There are generally two ways to connect PV modules into an array. The first approach
connects modules in series into strings and then in parallel into an array. The second approach,
first wires modules together in parallel and then those units are combined in series. Ideally, both
series-parallel and parallel-series connections are equivalent if all the cells and modules are

63

identical and work at the same condition. But, if sunlight is applied unevenly to different PV
cells, the second connection approach could cause many very bothersome problems [23].
The control system of a solar PV system contains two parts: one for maximum power
point tracking (MPPT) and the other for grid interface control [38, 39]. Both control functions
are achieved through power electronic converters. On the dc side, MPPT optimizes the power
output by varying the closed loop system voltage. On the ac side, these inverters ensure that the
sinusoidal output is synchronized to the grid frequency (60Hz). Illustration 4.1 shows a
residential grid connected solar system.

Ill. 4.1.Configuration of grid-connected solar PV system [73]

4.2 Power Converters Architecture of PV Arrays

Power electronic converters, a critical component in a PV system, have the following


typical architectures: 1) central dc/ac and dc/dc converter structure, 2) central dc/ac converter
and string dc/dc converter structure, 3) central dc/ac converter and dc/dc optimizer structure, 4)
detached micro-inverter structure, and 5) central and string inverter structures.
64

4.2.1 Central Dc/ac and Dc/dc Converters

This PV array structure consists of a dc/dc converter for maximum power extraction of a
whole PV array, a dc/ac converter for interface of the PV array to the grid, and a dc-link between
the two converters (Fig. 4.1). The MPPT control is achieved through the regulation of the dc
voltage applied to the array and the grid interface control stabilizes the dc-link voltage and
adjusts the reactive power sent to the grid [38, 39].Hence, the control of the two converters is
decoupled. It is a cost-effective approach to develop large MW-scale solar PV systems. The
primary disadvantage of the central converter configuration is that a large power loss may occur
in the energy harvest when mismatch or varying shading happens among the PV panels within
the array. Normally, a bypass diode is applied to a PV module [23]. At the top of each string, a
blocking diode is used to prevent a shading or malfunctioning string from withdrawing current
from the rest strings that are wired together in parallel.

Fig. 4.1. PV array with central dc/ac and dc/dc converter structure

65

4.2.2 Central Dc/ac Inverter and String Dc/dc Converters

This PV array structure consists of a central dc/ac converter for interface of the PV array
to the grid and multiple dc/dc converters with each dc/dc converter responsible for MPPT of one
PV string [14, 17] (Fig. 4.2) while the dc/ac inverter stabilizes the dc-link voltage and adjusts the
reactive power sent to the grid by the whole array. The key difference between Figs. 4.1 and 4.2
is that each dc/dc converter performs MPPT of a string rather than a whole PV array. The string
converter structure is likely to provide better power harvest than a central converter structure
because each string is tracked independently. Multiple self-contained string converters may offer
some advantage by eliminating the single point of failure, but will have a higher installation cost.

Fig. 4.2. PV array with central dc/ac inverter and string dc/dc converters

4.2.3 Dc/dc Optimizers

Dc/dc optimizers place a dc/dc converter to each PV module and provide one, large
66

central inverter that aggregates the power from all optimizers [16, 17] (Fig. 4.3). The optimizers
provide MPPT at the module level while the dc/ac inverter accomplishes the same control
functions as shown in Sections 4.2.1 and 4.2.2. The dc outputs of each module are joined in
series and parallel to be collected and then converted to ac power by a central inverter. With
additional equipment to purchase and install, dc/dc optimizers add to the initial cost of a PV
system. The added module-level hardware also imposes a penalty on overall system-level
efficiency by introducing an additional stage of loss power conversion. Furthermore, some dc/dc
optimizer systems also require a separate command-and-control device to operate.

Fig. 4.3. Dc/dc optimizers per module and a central inverter

4.2.4 Detached Microinverters

Detached microinverters involve placing a small inverter in close proximity to each PV


module (Fig 4.4). Arrays of panels are connected in parallel to each other, and then to the grid
feed. Hence, each microinverter is responsible for: 1) MPPT control of a module by regulating
67

the dc voltage applied to the module and 2) control of the reactive power sent to the grid by each
module. Similar to dc/dc optimizers, detached microinverters offer enhanced energy harvest by
performing MPPT at the module level, therefore, a single failure of panel or inverter will not take
the entire string offline. Also, they produce grid-matching power directly at the back of the
panel, and different ratings of solar panels can be added to an array even if they don't match the
original types. In addition, a micro-inverter on each module as the inverters anti-islanding
capability will shut down the module energy production when the system is disconnected, which
can significantly limit the risk to firefighters under emergency conditions according to proposals
of 2014 NEC [74].

Fig. 4.4. Detached microinverter PV system

However, the MPPT and reactive power control functions of a module are not decoupled,
which is a disadvantage for this PV system architecture because the two control requirements
may not be met at the same time as reported in [14]. Also, microinverters need to be installed
individually on the racking near each module. Todays microinverters have a five- to fifteen-year
warranty, much shorter than the life of PV modules. As such, it would be necessary to replace all
of the nonintegral microinverters at least once during the lifetime of the system.

68

4.2.5 Central and String Inverters

For both central and string inverter configurations, there is no dc/dc converter in the PV
system [15-17]. Thus, the inverters need to handle both MPPT and grid interface control
functions at the string or array level. Similar to Section 4.2.4, a disadvantage for these PV system
architectures is that the MPPT and reactive power control requirements may not be met at the
same time. In the central inverter PV structure, a single and large inverter is connected to many
PV modules wired in series to form strings with up to 600V of open-circuit voltage (1,000V in
Europe) [16] (Fig. 4.5a). In the string inverter PV structure, each string of series PV modules is
connected to one string inverter. Then, inverters for all the strings are connected in parallel
before feeding into the grid (Fig. 4.5b).

a) Central inverter

(b) String inverter

Fig. 4.5. PV array with central and string inverters

In summary, from the maximum power extraction standpoint, there are basically three
69

different configurations: 1) one dc voltage applied to the whole PV array for MPPT control
(Figs. 4.1 and 4.5a), 2) multi-independent dc voltages applied to multiple strings of series PV
modules (Figs. 4.2 and 4.5b), and 3) one independent dc voltage for each PV module (Figs. 4.3
and 4.4). For detailed evaluation of the three different configurations, it is important to be able to
assess power and voltage characteristics at individual cell, module, and array levels. However,
such a study is difficult to be conducted experimentally because the existing commercial PV
modules are not built in such a way that the current or voltage of each individual cell can be
measured. To overcome the challenge, a numerical algorithm developed in Chapter 2 for
simulation study of PV cell, module, and array characteristics under different converter schemes.
It is also important to indicate that a large PV array usually consists of thousands of cells. Thus, a
rigorous computational approach is very important.

4.3 PV Array Models for Different Converter Configurations

Detailed mathematical and simulation model of a PV cell, module and array have been
described Section 2.2. The PV Array model with consideration of different converter
configurations will especially be analyzed and validated.
For the micro inverter structure, the energy extraction characteristics of each module is
computed separately based on the PV module model (Sections 2.2.2 and 2.3) while the total
energy extraction of a PV array is the summation of energy from all the modules. For the string
converter structure, the voltage applied to each string is different (Sections 4.2.2 and 4.2.5). For
each string, the mathematical model and procedure to obtain P-V and I-V characteristics is very
similar to Sections 2.2.2 and 2.3 except that the external voltage applied to each string equals to
the sum of photogenerated voltages of all series connected PV modules. The output power of the
70

array is the sum of the output powers of all strings. For the central converter structure with the
standard series-parallel connected PV array (Section 4.2.1), the voltage applied to each string of
the PV modules is the same. However, the P-V and I-V characteristics of each string could be
different depending on how many PV cells in a string are shaded and how much. The model and
procedure for energy extraction computation of each string is similar to that of the string
converter structure while the total output current of the PV array is the sum of currents of all
parallel strings.

4.4 PV System Energy Extraction Characteristics without Bypass Diodes

Based on the analysis shown in Section 4.2, PV system characteristic studies are
conducted for the following three converter configurations, i.e., a power converter for an entire
array, for each string, and for each panel.

4.4.1 Central Converter Configuration

For a typical series-parallel connected PV array with central converter configuration, the
voltage applied to each string of the PV modules is the same. However, the P-V and I-V
characteristics of each string could be different depending on how many PV cells in a string are
shaded and how much. The mathematical procedure to obtain P-V and I-V characteristics is
based on Sections 2.2. The output current of the PV array is the sum of currents of all parallel
strings.

71

Power (kW)

20
None
50%
100%

15
10
5
0

100

200

300

400

500

Vs (V)

a)

P-V characteristics of PV array

10

Voltage (V)

0
-10
-20
None
50%
100%

-30
-40

100

200

300

400

500

Vs (V)

b) Shaded cell terminal voltage characteristics of the last string


100

Power (W)

0
-100
None
50%
100%

-200
-300

100

200

300

400

500

Vs (V)

c)

Shaded cell P-V characteristics of the last string

Fig. 4.6. Characteristics of PV array with central converter

Figure 4.6 shows the PV array characteristics. The PV array has a configuration of 10
parallel strings with each string containing 20 series modules. Assume there are 19 shaded
modules in the 1st string, 17 in the 2nd string, 15 in the 3rd string and 1 in the last string. In

72

each shaded module, there is only one shaded cell, which represents the worst condition that may
damage a PV cell [75, 76]. The shading factor is 0, 50% and 100%, respectively. From the
figures and other case studies, it is found that the PV array characteristics can be shifted
significantly under shading conditions (Fig. 4.6a). The degree of the change depends on how
many strings contain shaded cells and how many shaded cells are in each string. When there is
only one shaded cell in a string, all the photogenerated voltages of the unshaded cells in that
string are applied to the shaded cell (Fig. 4.6b), which would cause a high risk to damage the
shaded cell due to the high absorbing power of the shaded cell (Fig. 4.6c).

4.4.2 String Converter Configuration

For a PV array with the string converter configuration, the voltage applied to each string
of PV modules is different. Therefore, the P-V and I-V characteristics of each string are
independent from those of other strings. Under the MPPT control strategy, each string captures a
different power. The total output power of the array is the summation of the maximum powers
captured by all strings.

shade factor=100%

shade factor=50%
2

Average max
strings 1-10

1.5

P o w e r (k W )

P o w e r (k W )

1
0.5
0

100

200

300

400

500

Vs (V)

Average max
strings 1-10

1.5
1
0.5
0

100

200

300
Vs (V)

Fig. 4.7. Characteristics of series PV strings with shaded cells

73

400

500

Figure 4.7 shows the P-V characteristics of all strings under the same shading conditions
used in Fig. 4.6. In the figure, the constant line represents the maximum power of the PV array
divided by the number of all strings. From the figure and other analysis, the following properties
are found.
1) When there is no shaded cell in the PV array, all the strings have the same P-V
characteristics. The output power of the PV array under the MPPT control strategy is the
maximum power of one string multiplied by the number of all strings.
2) When there are shaded cells in the PV array, the P-V characteristics of each string
would be different from other strings depending on the distribution of the shaded cells and the
shading factors of shaded cells. The average maximum power lies between the maximum
captured powers of the least and the most shaded strings.
3) Similar to Fig. 4.6, the most damaging condition for a PV cell is when there is only
one shaded cell in a long string, which would cause a high risk to damage the shaded cell due to
the high absorbing power of the shaded cell.

4.4.3 Micro-inverter Configuration

For the micro-inverter configuration, each PV module is connected to the grid via its own
inverter. Hence, the P-V and I-V characteristics of each module are independent from those of
other modules. Under the MPPT control strategy, each module captures a different power. The
total output power of the PV array is the summation of the maximum powers captured by all the
PV modules.

74

P o w e r (k W )

0.1

None
50%
100%

0.075
0.05
0.025
0

10

15

20

25

Vs (V)

a) P-V characteristics of PV array


25
P ow er (W )

0
-25
None
50%
100%

-50
-75
-100

10

15

20

25

Vs (V)

b) Shaded cell terminal voltage characteristics of the last string

V oltage (V )

5
0
-5
None
50%
100%

-10
-15
-20

10

15

20

25

Vs (V)

c) Shaded cell P-V characteristics of the last string


Fig. 4.8. Characteristics of PV module under shading conditions

Figure 4.8 shows the P-V characteristics of a PV module with one shaded cell for shading
factor of 0, 50%, and 100%, respectively. As it can be seen from the figure, shading of even one
single cell could cause significant drop of PV module output power (Fig. 4.8a). Under the
shading condition, a high reverse terminal voltage would appear on the shaded cell (Fig. 4.8b),

75

which results in a high absorbing power by the shaded cell especially when the external voltage
applied to the module is low (Fig. 4.8c). Similarly, the most demanding situation is when there is
only one shaded cell in the PV module.
Table 4.1 compares maximum power that can be captured by the PV array for the three
power converter configurations under the same shading condition used in Fig. 4.6. In general, if
there is no shaded cell, the captured maximum power is the same for all the three converter
configurations. However, under shading conditions, the micro-converter configuration based PV
system has the highest energy yield while the central converter configuration one has the lowest
energy production.

Table 4.1. Comparison of maximum power extraction without bypass diodes


for different converter configurations
Shading factor
50%

100%

Central converter

13.65 kW

7.34 kW

String converter

13.79 kW

7.76 kW

Micro converter

15.71 kW

11.39 kW

Configuration

4.5 PV System Energy Extraction Characteristics with Bypass Diodes

In the PV industry, bypass diodes are normally adopted in central and string converter
configurations [38]. For the micro converter configuration, it is reasonable to assume that bypass
diodes are not used.

76

4.5.1 Central Converter Configuration

Normally, a bypass diode is applied to a PV module or a group of series PV modules


[39]. For research purpose, however, the dissertation considers different bypass diode schemes
within a PV module, such as a bypass diode for every one, two, or three series PV cells. As
discussed in Chapter 2, with bypass diodes, the I-V and P-V characteristics of a PV module is
more complicated and different from the traditional understanding of the photovoltaic I-V and PV characteristics.
Figure 4.9 compares characteristics of the PV array for different bypass diode conditions.
From the figures, other case studies, and comparison with Section 4.2.1, the following properties
are obtained:
1) If each PV module has one bypass diode, the PV array characteristics is improved
depending on the distribution of the shaded cells in the PV array. For each string, the best
situation is that all the shaded cells appear in one module. However, if the shaded cells are
distributed evenly in different modules in a string, the improvement of the PV array
characteristics is trivial (Fig. 4.9a). If there is only one shaded cell in a module, then, all the
photogenerated voltages of the unshaded cells in that module are applied to the shaded cell.
Compared to Fig. 4.6, the absorbing power of the shaded cell under 100% shading condition is
reduced a lot but changes very little for 50% shading condition. Another impact of the bypass
diodes is that multiple peaks appear in the P-V characteristics (Fig. 4.9a), making it harder for
the MPPT control of the PV array.
2) If each PV cell has a bypass diode, the influence of the shaded cells to the PV array
characteristics is significantly reduced. Compared to Fig. 4.9c, the absorbing power of the
shaded cell is very small (Fig. 4.9d). If the number of the shaded cells is significantly less than
77

the number of the unshaded cells, the P-V characteristics of the PV array is very close to the
unshaded condition no matter how the shaded cells are distributed in the PV array. In addition, it
is more convenient to manage the MPPT control of the PV array even under shading conditions
when there is a bypass diode for each PV cell.
3) As fewer cells are in parallel with a bypass diode, the peak power of the PV array
increases and the multi-peak impact to the P-V characteristics of the PV array reduces (Fig.
4.10).

20

None
50%
100%

15
10

P o w e r (k W )

P o w e r (k W )

20

5
0

100

200

300

400

10
5
0

500

None
50%
100%

15

100

200

Vs (V)

a) PV array characteristics

P o w e r (W )

P ow er (W )

-50
-100
-150

100

200

300

400

500

None
50%
100%

2
0
-2
-4

500

(one bypass diode per cell)

None
50%
100%

400

b) PV array characteristics

(one bypass diode per module)


50

300
Vs (V)

100

200

300

400

Vs (V)

Vs (V)

c) Shaded cell characteristics

d) Shaded cell characteristics

(one bypass diode per module)

(one bypass diode per cell)

Fig. 4.9. Characteristics of PV array under shading conditions

78

500

shade factor=50%
20

full-sun
n=1
n=2
n=3
4
n=6
n=9
n=12
n=18
n=36

P ow er (k W )

15

10

100

200

300

400

500

Vs (V)

a) PV array characteristics under 50% shading


shade factor=100%
20

full-sun
n=1
n=2
n=3
4
n=6
n=9
n=12
n=18
n=36

P ow er (k W )

15

10

50

100

150

200

250
Vs (V)

300

350

400

450

500

b) PV array characteristics under 100% shading


Fig. 4.10. Characteristics of PV array for different bypass diode schemes

4.5.2 String Converter Configuration

With the same bypass diode layouts, the only difference between the string and central
converter configurations is that the voltage applied to each string of series PV modules is
different. Due to the bypass diode impact, the characteristics of PV strings would be different
from Fig. 4.7. Figure 4.11 shows the P-V characteristics of all strings under the same shading

79

conditions used in Fig. 4.6 for different bypass diode schemes. Again, the constant red dot line
represents the maximum power of the PV array divided by the number of all strings.
If each module has one bypass diode, the characteristics of each string has multiple
peaks, requiring that the MPPT algorithm must be designed to be able to locate the maximum
power production of each string. If there are more bypass diodes within a module, the multiple
peaks moves from low voltage range to high voltage range in general, resulting in more power
production from each string under the same shading conditions. If one bypass diode is applied to
every one or two PV cells, the energy yield of each string is significantly increased and the peak
power of each string is closer to ideal peak power under the nonshading condition, making it
easier to develop and design MPPT algorithm.

4.5.3 Comparison of Maximum Power Using Central, String and Micro Converter Configuration

One important issue for the evaluation and comparison of the power production using
micro, string, and central converter configurations is how much power can be extracted for
different converter structures. Tables 4.2 and 4.3 compares the maximum power of the PV array
that can be captured by using different converter configurations for varying bypass diode
arrangements under the same shading condition used in Fig. 4.6. The comparison shows:
1)

When the number of PV cells of each bypass diode is small, the difference among

the maximum power extracted by using the three different converter structures is very small.
2)

The micro-converter based PV system has the highest power capture capability

while the power production of central converter based PV system is the lowest. The difference
between the highest and the lowest power is more obvious as the number of PV cells contained
in each bypass diode increases.
80

shade factor=100%
Power (kW)

Average max
strings 1-10

1.5
1
0.5
0

100

200

300

400

500

Vs (V)

a) a bypass diode per module


shade factor=100%
2

Average max
strings 1-10

Power (kW)

1.5
1
0.5
0

100

200

300

400

500

Vs (V)

b) a bypass diode per 18 cells


shade factor=100%
2

Average max
strings 1-10

Power (kW)

1.5
1
0.5
0

100

200

300

400

500

Vs (V)

c) a bypass diode per 9 cells


shade factor=100%
Power (kW)

Average max
strings 1-10

1.5
1
0.5
0

100

200

300

400

500

Vs (V)

d) a bypass diode per 6 cells


shade factor=100%
Power (kW)

Average max
strings 1-10

1.5
1
0.5
0

100

200

300

400

500

Vs (V)

e) a bypass diode per cell


Fig. 4.11. Characteristics of series PV strings
81

Table 4.2. Comparison of maximum power extraction under 50% shading factor (kW)
Configuration
Central converter

String converter

Micro converter

19.0610

19.1124

19.1127

18.7270

18.8392

18.8395

18.3700

18.5661

18.5664

17.9912

18.2929

18.2932

17.1742

17.7466

17.7470

15.8272

16.9274

16.9277

12

14.7374

16.1083

16.1087

18

13.9460

14.7711

15.7179

Table 4.3. Comparison of maximum power extraction under 100% shading factor (kW)
Configuration
Central converter String converter

Micro converter

19.0475

19.1012

19.1014

18.7120

18.8277

18.8280

18.3535

18.5543

18.5546

17.9730

18.2808

18.2811

17.1517

17.7340

17.7343

15.7945

16.9137

16.9140

12

14.3236

16.0934

16.0938

18

11.3022

14.4531

14.4535

82

3)

In reality, however, a larger number of bypass diodes is not used in micro-converter

based PV systems. Thus, when the number of PV cells of each bypass diode is small, such as 1 to
4 as shown by Tables 4.2 and 4.3, the central converter based PV system is much more efficient
than micro-converter based PV system. In addition, the reactive power compensation ability of
central-converter based PV system is higher [14, 77].

4.6 Conclusion

This chapter compares the energy extraction characteristics of a solar PV system for
different converter schemes, including central, string and micro converter configurations. The
chapter particularly focuses on how energy extraction characteristics of a PV array are affected
by uneven shadings using different converter structures. Without shading, the PV system has the
same energy yield for all the three converter schemes. Under shading and without bypass diodes,
the micro converter based PV system has the highest energy yield while the central converter
based PV system has the lowest energy production. However, the micro converter based PV
system is costly and is still unable to prevent energy loss caused by the shading within PV
panels.
It is found that with bypass diodes, the efficiency of a PV system can be improved
significantly especially when the number of PV cells within a bypass diode is small. Simulation
studies show that the difference among the maximum extracted power is trivial under shading
conditions for the three different converter structures for PV modules with large number of
bypass diodes. The study shows that the central converter based PV system with properly built-in
bypass diodes is an effective and economic approach to improve efficiency, performance, and
reliability of a PV system.
83

CHAPTER 5
COORDINATED CONTROL FOR GRID INTEGRATION OF PV ARRAY, BATTERY
STORAGE, AND SUPERCAPACITOR WITH RELATED ISSUES

The intermittent nature of PV energy and quick fluctuations of load demanding require
energy storage units (ESU) which generally consists of storage battery and supercapacitor (SC)
[78, 79]. Batteries are the technological solution most commonly employed to help make a PV
system [80-84], whose power output cannot be controlled, smooth and dispatchable. A battery
stores electrical energy in the form of chemical energy. For a PV-battery system to function
effectively the electrochemical processes must work in both directionsin other words, the
system must be rechargeable. Normally, batteries perform three main functions in a gridconnected PV system: storing energy into the batteries when the PV production is high and the
grid demand is low, releasing energy to the grid when the PV production is low or during grid
peak demand intervals, and preventing large voltage fluctuations.
Except for batteries, SC is usually used in conjunction with batteries to form an advanced
PV energy storage system [85-87]. However, unlike batteries, where the voltage remains
relatively even over most of the batterys remaining charge levels, a capacitors voltage scales
linearly with the remaining energy. This means an additional circuitry is required to make the SC
energy usable.
For the PV array, a boost converter is usually connected to the dc link to raise the input
voltage and then transfer the high voltage dc energy to ac energy through a grid-connected
converter [88]. Bidirectional dcdc converters are required to interface the ESU, including
84

batteries and SC, to the dc link for controlling the power flow. The coordinated control of the
entire system is critical. Currents and voltages of PV array, SCs, battery, dc link, and grid are
input signals used to modulate PWM signals to power electronic converters. The modulation
algorithm has to be specified for each converter control topology and has to generate control
signals to fulfill basic functions such as dc link voltage control, ESU control, grid active and
reactive power control, and MPPT control, which has resulted in many different control
strategies for the integrated PV and ESU system [87-94].

5.1 Grid-connected PV and Energy Storage System

A typical grid-connected solar PV and energy storage system consists of five parts (Fig.
5.1): an array of solar cells, battery storage, SC, power converters, and an integrated control
system.

ig

v pv

vdc

i pv

v g ig

vb

ib

vsc

isc

Fig. 5.1. Configuration of grid-connected PV system with ESUs


85

5.1.1 Photovoltaic Arrays

Normally, solar cells are connected in series to form a module that gives a standard dc
voltage. Modules are connected into an array to produce sufficient current and voltage to meet a
demand for a gird-connected application [90, 92, 95]. Usually, the PV modules are first
connected in series into strings and then in parallel into an array. The power produced by a PV
array is dependent on the irradiance and temperature. In general, there is a unique point on the PV curve of the PV array, called the maximum power point (MPP), at which the entire PV system
operates with maximum efficiency and produces its maximum output power. To maximize the
output power of a PV system, continuously tracking the MPP of the system is necessary (Chapter
3). This is accomplished through the control of the dc/dc converter connecting the PV array to
the dc-link capacitor.

5.1.2 Rechargeable battery

A rechargeable battery is one or more electrochemical cells that convert stored chemical
energy into electrical energy during a discharge process or convert electrical energy into
chemical energy during a charge process [95]. The electrical energy storage system in a PV
system is expected to be designed with adequate energy capacity and output peak power to
satisfy grid integration needs [88, 89]. In an integrated PV and battery storage system, the battery
is connected to the dc-link also through a dc/dc converter which controls the charge and
discharge of the battery.

5.1.3 Supercapacitor
86

Unlike batteries, SCs store their energy in an electrostatic field. The most significant
advantage of SCs over batteries is that they are capable of very fast charges and discharges [81,
82, 87]. Disadvantages are that their power is available only for a very short duration and their
self-discharge rate is much higher than that of batteries. Thus, SCs can supply power when there
are surges or energy bursts, while batteries can supply the bulk energy over a longer time period
[81, 82, 87].The combination of the two is crucial for diverse energy storage needs of both fast
and slow fluctuating solar power [81, 87, 89].

5.1.4 Grid-Connected Converter

The grid-connected converter (GCC) converts dc to grid compatible ac [88, 96]. In


addition, the purpose of a GCC includes: managing the active power transferred from dc to ac
side or stabilizing the dc-link voltage, and controlling the reactive power absorbed from the ac
grid, depending on the coordinated control system design (Section 5.3).

5.1.5 Integrated Control System

The control system of an integrated PV system has three levels: device level at PV array,
battery and SC, PV system central control level (PVCC), and distribution management system
(DMS) level [79, 93, 97]. At the device level, the energy is either captured from the PV array or
generated from ESUs. At the PVCC, the power production is determined based on the optimal
overall profits to operate the PV, ESUs and GCC. The central controller sends out power
references to PV, ESUs and GCC based on commends from DMS, while each individual device
control system ensures that the power reference from the PVCC is reached. At the DMS level,
87

the power production of the integrated PV system is managed to meet the overall grid demands
and stability and reliability needs.

5.2 Coordinate PV Array, ESU and GCC Control

The development of coordinated control for next-generation PV installations, along with


ESUs, provides flexibility to distribution system operators. The control objective of this hybrid
PV and energy storage system is to supply the desired active and reactive power to the grid and
at the same time to maintain the stability of the dc link voltage of the PV and energy storage
system through coordinated control of power electronic converters.
MPPT control for PV Array has been studied and investigated in Chapter 3. Hereby, the
control of bi-directional dc/dc converter for ESUs and direct-current vector control of GCC will
be discussed.

5.2.1 Control of Bi-directional Dc/dc Converters for ESUs

Unlike the PV array which requires only one-directional power flow, ESUs require bidirectional power flow. Due to its simplicity and robustness, the bi-directional buck/boost
converter is used in this dissertation to interface the SC or battery ESUs with the dc voltage bus.
In general, the dc/dc converter acts as a boost converter during ESU discharge mode and as a
buck converter during ESU charge mode.
Both constant-current and constant-voltage control schemes are developed. The two
control techniques are then integrated together to meet ESUs charge and discharge requirements.

88

Figure 5.2 shows the block diagram for battery control. Similar current control strategy is also
used to control the SC.

vb
vb _ ref

ib

ib _ ref
Fig. 5.2. Block diagram of nested-loop battery control strategy

For battery control, the switch block passes through the top input or the bottom input
based on the value of SOC in the middle. If the switch is in the upper position, the system
operates in the constant-voltage control mode. If the switch is in the bottom position, the system
operates in the constant-current control mode. The reference current can be either positive or
negative. Assume that the current flowing into the dc-link is positive. Then, if the reference
current is positive, the system implements constant-current discharging control function; if the
reference current is negative, the system implements constant-current charging control function.
SOC is the main factor to decide the battery status from current control to voltage control. When
SOC is below 70%, constant-current charging mechanism is applied; when SOC is above 70%,
the system switches to constant-voltage charging mechanism. In order for a smooth transition
from current to voltage control, the same value of reference current before transition should be
the initial value of the voltage controller. While the battery is in discharging mode, the constantcurrent control mechanism is applied and the power provided by the battery to the grid can be
regulated by adjusting the reference discharging current.

89

5.2.2 Direct-Current Vector Control of GCC

Figure 5.3 shows the schematic of the GCC, in which a dc-link capacitor is on the left,
and a three-phase voltage source, representing the voltage at the Point of Common Coupling
(PCC) of the ac system, is on the right. The following dynamic equations can be obtained:

va
ia
ia va1
d



vb R ib L dt ib vb1
vc
ic
ic vc1

(5.1)

where L and R are the inductance and resistance of the grid filter and vabc , iabc , and vabc1 are
instantaneous space vectors of the PCC voltage, line current, and converter output voltage,
respectively.

Fig. 5.3 GCC converter schematic

By using the abc-dq transformation with its d-axis aligned to the voltage vector of the
PCC, full equation in Eq. (5.1) be described in the synchronously rotating reference frame as
follows:

vd
id
iq vd1
d id

L
v
i
i s v
dt
q
q


q
id q1

90

(5.2)

where s is the angular frequency of the grid's PCC voltage, and. Using space vectors, (5.2) is
expressed by the complex equation in (5.3), in which vdq, idq and vdq1 are instantaneous space
vectors of the PCC voltage, line current, and converter output voltage, respectively. In the
steady-state condition, (5.3) becomes (5.4), where Vdq, Idq and Vdq1 stand for the steady-state
space vectors of PCC voltage, grid current, and converter output voltage, respectively.

vdq R idq L

d
idq js L idq vdq1
dt

Vdq R I dq js L I dq Vdq1

(5.3)
(5.4)

In the grid's PCC voltage-oriented frame [98-103], the instantaneous active and reactive
powers absorbed by the GCC from the grid are proportional to the grid's d- and q-axis currents,
respectively, as shown by (5.5) and (5.6):

p(t ) vd id vq iq vd id

(5.5)

q(t ) vq id vd iq vd iq

(5.6)

In terms of the steady-state condition, Vdq=Vd+j0 if the d-axis of the reference frame is
aligned along the PCC voltage position. Assuming that Vdq1=Vd1+j Vq1 and neglecting the grid
filter resistance, the current flowing between the PCC and the GCC according to (5.4) is:

I dq (Vd Vd1 ) /( jX f ) Vq1 / X f

(5.7)

Where Xf stands for the grid filter reactance.


Supposing that passive sign convention is applied, i.e., power flowing toward the GCC is
positive, the power absorbed by GCC at the PCC is:

Pconv VdVq1 / X f , Qconv Vd (Vd Vd1 ) / X f

91

(5.8)

The basic principle of the direct-current vector control is to use d- and q-axis currents
directly for active and reactive power or dc-link voltage and reactive power control of the GCC
[96]. Unlike the conventional standard vector control approach that generates a d- or q-axis
voltage from a GCC current-loop controller, the direct-current vector control structure outputs a
current signal at the d- or q-axis current-loop controller (Fig. 5.4). In other words, the output of
the controller is a d- or q-axis tuning current, while the input error signal tells the controller how
much the tuning current should be adjusted during the dynamic control process. The
development of the tuning current control strategy has adopted intelligent control concepts [104],
e.g., a control goal to minimize the absolute or root-mean-square (RMS) error between the
desired and actual d- and q-axis currents through an adaptive tuning strategy.

_
_

PI

_
_

PI

PI

PI

+_
+

PI

_
_

PI

Fig. 5.4. GCC direct-current vector control structure

Due to the nature of a voltage-source converter, the d-and q-axis tuning current signals,
id and iq, generated by the current-loop controllers must be transferred to d- and q-axis voltage
signals v*d1 and v*q1 to control the GCC. This is realized through (5.11), which is equivalent to

92

the transient d-q equation (5.2), after being processed by a low pass filter in order to reduce the
high oscillation of d and q reference voltages applied directly to the converter.

vd*1 R f id' s L f iq' vd


vq*1 R f iq' s L f id'

(5.11)

The initial values of the GCC PI current-loop controllers are tuned by minimizing the
RMS error between the reference and measured values.

5.3 Coordinated Control Mechanisms for Grid Integration

In grid integration of the integrated PV system, the PVCC receives active and reactive
power commends from the DMS and then determines how to control PV array, ESUs and GCC.
Normally, the PV array is controlled for maximum power extraction. Thus, depending on the
active power or dc-link voltage control for the GCC (Fig. 5.4), three coordinated control
strategies are implemented.

5.3.1 Dc-link Voltage Control through ESUs

In this control scheme, the GCC operates in PQ control mode by maintaining the PCC
active and reactive power output according to the grid control commend. Hence, the dc-link
voltage must be controlled via ESUs [79, 89]. In general, if the PV generated power is more than
the GCC output power, the dc-link voltage goes up so that the ESUs must operate in charging
mode to reduce the voltage; if the PV power is less than the GCC output power, the dc-link
voltage drops so that the ESUs must operate in discharging mode to increase the dc-link voltage.

93

Usually, a battery bank has a high energy density whereas it has relatively slow response
speed. On the other hand, SC has a low power density but fast response speed. Therefore, in the
control design of ESUs, SC should be responsible for fast transient energy exchange whereas
battery should take care of relatively steady-state energy charge or discharges. This results in a
control design as shown by Fig. 5.5, in which the error signal between measured and reference
dc-link voltage generates a current reference iref through a PI controller and then a low-pass filter
is applied to obtain the battery reference current ib_ref while the rest is used as the SC reference
current isc_ref . This strategy is simple but may result in unstable dc-link voltage when the SC
and/or battery reach their lower or upper energy storage limits.

Vdc _ ref

iref

ib _ ref

ib

vdc

isc _ ref

vdc

vb
vdc

1/ vdc

1/ vdc

Fig. 5.5. Control of dc-link voltage through ESUs [87]

5.3.2 Power Balancing Control of ESUs

In this control scheme, the GCC operates in PQ control mode too, requiring that the dclink voltage must be controlled by ESUs. However, different from Section 5.3.1, the reference
current signals to the battery and SC are determined through a power balance relation as shown
in Fig. 5.6. In the figure, pf represents the power losses in the grid filter which is calculated by:

94

p f R f id2 iq2

(5.12)

where, id and iq are grid d- and q-axis currents, respectively, and Rf is the resistance of grid
filter. The error signal between measured and reference dc-link voltage generates a dc-link
capacitor power reference, pdc_ref. The summation of grid reference power pg_ref, pdc_ref and ppv is
the total instantaneous generated power in the power system. By subtracting loss power from the
filter pf , the charging or discharging power to ESUs is obtained. Similarly, through a low-pass
filter, the battery reference current ib_ref is obtained while the rest is used as the SC reference
current isc_ref.
The primary issues associated with this scheme is that the variation of system parameters,
such as Rf, or the inaccuracy of the power balance calculation, such as neglect of power
converter losses, could affect control effectiveness of the dc-link voltage. In addition, the slow
response speed of the power balance computation and the lower or upper energy storage limits of
the SC and/or battery could affect the dc-link voltage control too.

Vdc _ refdc
pg _ ref

pdc _ ref

pf

v pv
i pv

psto _ ref

pb _ ref

vb

vsc

p pv

psc _ ref

Fig. 5.6. Power balance control structure of ESUs [89]

5.3.3 Dc-link Voltage Control through GCC

95

ib _ ref
isc _ ref

In this control scheme, the GCC is responsible for dc-link voltage control and the grid
reactive power or bus voltage control. Although this GCC control strategy can maintain a very
stable dc-link voltage, power management of ESUs must be determined through power balance
computation. Similar to the ESU control method described in Section 5.3.1, the summation of
grid reference power pg_ref with pf and actual dc-link capacitor power pdc is the power that should
be outputted by the combined PV array and ESUs before the dc-link capacitor (Fig. 5.7). Then,
the SC and battery reference currents can be obtained in the same way as described in Section
5.3.2. Due to the variation of system parameters and the inaccuracy of the power balance
calculation, the actual output power at PCC could be slightly different from the grid reference
power pg_ref by using this control scheme.

pg _ ref

pf

v pv
i pv

p dc

psto _ ref

pb _ ref b

ib _ ref

vsc

p pv

psc _ ref isc _ ref

Fig. 5.7. Energy storage units connected converters control structure

5.4 Coordinated Control Evaluation and Comparison

To evaluate different control schemes, a computational experiment platform of the gridintegrated PV system with ESUs is developed. The experiment system mainly includes: a PV
array module, a battery bank, a SC, four power converter modules, and four corresponding

96

control modules for these converters (Fig. 5.8). The parameters used in the simulation study are
shown in Table 5.1.
The PV array has a series-parallel connection configuration having 10 parallel strings
with each string consisting of 50 series panels. The converter modules are from Opal-RT RTEDrive toolbox. These converter modules can be integrated with the RTE PWM signal generation
function from the Opal-RT RT-EVENTS toolbox to generate drive pulses for very fast and
accurate simulation of power converters [64]. Figure 5.9 shows I-V and P-V characteristics of
the PV array. The control modules are developed with detailed consideration of digital control
system natures, including sample and hold, digital signal processing, and time delays. The
measured voltage and current signals first pass through sampling blocks, which converts
measured continuous signals to discrete signals. Then, a digital filtering mechanism is
applied to remove high frequency components caused by noises or rapid switching of power
converters [13].

Fig. 5.8. Solar PV generator under the control of a dc/dc power converter
using SPS and Opal-RT RT-LAB
97

60

60
40

30

20
0

200

400
600 800
Voltage (V)

1000

Power (kW)

Current (A)

80

0
1200

Fig. 5.9. Solar PV array characteristics used in simulation

Table 5.1

Parameters of electrical components in grid-integrated PV system with ESUs


Parameters

Value

Parameters

Value

L1

0.3mH

C1

0.3mF

RL1

0.5 +1.2mH

RL2

1m +33mH

RL3

0.9 +1.2mH

RL4

1m +33mH

Cdc

16mF

Lf1

0.55mH

Lf2

0.55mH

Cf

2.5F

Figures 5.10-12 show results of a case study for the three control schemes presented in
Section 5.3. The solar irradiation is initialized at a value of S=0.75 (Fig. 5.13), where S stands
for the ratio of the present solar irradiation over the nominal irradiation of 1000W/m2. Then, it is
simulated as a parabola curve starts at t=6s with a highest value of S=1 at t=12s. Finally, S
maintains at a value of 0.75 after t=18s.
98

PV
Grid
Q

-50

10

15

25
0
PV
Grid
Q

-25
-50

20

10

Time (s)

15

25
0
PV
Grid
Q

-25
-50

20

10

15

20

Time (s)

Time (s)

a) Active power of PV system

a) Active power of PV system

a) Active power of PV system

and grid along with grid side

and grid along with grid side

and grid along with grid side

reactive power

reactive power

reactive power

1550
1500
1450
1400

10

15

1550
1500
1450
1400

20

10

Time (s)

battery
SC

320

20

battery
SC
5

10

20

69.5

Time (s)

Current (A)

70
Current
SOC

battery
SC
5

10

30

70

15

Current
SOC
5

10

15

15

20

c) Battery & SC voltage profiles

70.5

45

20

Time (s)

60

SOC (%)

30

15

310

20

c) Battery & SC voltage profiles

70.5

45

15

15

320

Time (s)

60

15

330

20

69.5

Time (s)

60
Current (A)

15

330

310

c) Battery & SC voltage profiles

Current (A)

10

340

Time (s)

10

b)Dc-link voltage

SOC (%)

320

1400

Time (s)

ESU Voltage (V)

ESU Voltage (V)

ESU Voltage (V)

330

10

1450

20

340

1500

b)Dc-link voltage

340

15

1550

Time (s)

b)Dc-link voltage

310

1600

Dc-link Voltage(V)

1600

Dc-link Voltage(V)

Dc-link Voltage(V)

1600

70.5

45
30

70

15
0

Current
SOC
5

10

15

20

69.5

Time (s)

d)Current & SOC of battery

d)Current & SOC of battery

d)Current & SOC of battery

Fig. 5.10. Simulation results of

Fig. 5.11. Simulation results of

Fig. 5.12. Simulation results of

the control scheme in Section

the control scheme in Section

the control scheme in Section

5.3.1

5.3.2

5.3.3

99

SOC (% )

50

P(kW)and Q(kVar)

25

-25

50

P(kW)and Q(kVar)

P(kW)and Q(kVar)

50

Irradiation

1
0.9
0.8
5

10
15
Time (s)

20

Fig. 5.13. Solar irradiation over the nominal irradiation of 1000W/m2

Power balancing between supply and demand is the most critical task in the system. To
check the demand-following services, the initial grid reference active power is given as 15kW,
which has a positive value when gird power inflow to the dc-link direction (Fig. 5.1).Then grid
demand changes to -35 kW and 5kW separately at t=8s and t=15s. The reactive power reference
is set at 0kVar practically. The simulation results of three control schemes include: PV and gridside generated power and grid-side reactive power (Figs. 5.10a, 5.11a and 5.12a), dc-link voltage
(Figs. 5.10b, 5.11b and 5.12b), battery and SC voltage profiles (Figs. 5.10c, 5.11c and 5.12c),
and battery SOC and current profiles (Figs. 5.10d, 5.11d and 5.12d).
The simulation shows that by using any of the coordinated control schemes, the active
and reactive power can follow the reference well with no error at steady state (Figs. 5.10a, 5.11a
and 5.12a). However, the methods described in Section 5.3.1 and 5.3.2 present a power
overshoot of tens of kilowatts when a change of reference active power occurs at t=8s and t=15s,
which causes voltage fluctuations, distribution losses, power quality and power balancing
reduction, and increase wear and tear on grid hardware. The proposed coordinated control has
the ability to provide the grid with the desire power at both transient and steady state
environments. PV generation maximum power point can be achieved in this situation due to the
roundness and fast response of applied adaptive MPPT control scheme (Section 3.3.2). The

100

reactive power generated in the grid side keeps at 0Var as designed through GCC direct-current
vector control.
Compared the dc-link voltage results (Figs. 5.10b, 5.11b and 5.12b), the proposed control
method which controls dc-link voltage using direct current control has the most accurate
response to the dc-link voltage. This is due to the reason that direct-current vector control
strategy is applied to the dc/ac inverter. Dc-link Voltage control through ESUs will have a delay
on the dc-link voltage performance because the chemical storage process needs a certain period
of time. Additionally, dc-link voltage control through power-balancing control of ESUs has a
delay response not only due to chemical storage process but also a result from calculation error
of the variation of system parameters and the neglect of power loss in the system.
The charging and discharging-voltage profiles present how battery and SC respond to
power regulations. The charging voltage in SC is continuously increasing because power inflows
to ESU in the whole process. However, the low frequency component in the surplus power
decides the discontinuousness of battery charging voltage and current. In Figs 5.10d, 5.11d and
5.12d, there is a point where SOC is larger than 70%, the charging current is switched to
constant-voltage control which is regulated at 335V. The charging current is smooth because the
initial value is set to be same as constant-current control reference current for the constantvoltage controller.
The three-phase current waveforms on the grid side are shown in Fig. 5.14. Reactive
power is regulated at 0Var, which indicates that iq =0, therefore, the amplitude of three-phase
current is proportional to the value of id, which is decided by the grid-side power (Fig. 5.14a and
5.12a). A zoomed-in of three-phase currents (Fig. 5.14b) shows that the currents are balanced
and smooth in Opal-RT simulator. This is because RT-Event allows multiple events in a single

101

simulation time-step, and it is used to generate fast and accurate PWM pulses for high-frequency
switches.

Grid Current (A)

50
25
0
-25
-50

13
Time (s)

18

22

a) Three-phase currents in grid side

Grid Current (A)

50
25
0
-25
-50
12.95

12.975

13
Time (s)

13.025

13.05

b) A zoomed in three-phase currents


Fig. 5.14. Three-phase grid-side currents

So far, this chapter studies the configuration and detailed components of the gridconnected PV system with energy storage units. It also investigates and compares three
coordinated control designs. In general, the PV array is controlled for MPPT, the battery is used
for slow charging or discharging control, and the suppercapacitor is used for fast charge or
discharge control. However, there are differences in detailed ESU control design depending on
whether the GCC is used for dc-link voltage control or not. If the GCC is used for dc-link
voltage control, the ESUs must be controlled in such a way to meet grid power control demand.
102

If the GCC is used for active power control, the ESUs must provide dc-link voltage control either
directly or through a power balance control mechanism. The simulation results using three
different control schemes shows that when the GCC is used for dc-link voltage and grid reactive
power control, a stable dc-link voltage can be obtained and the integrated PV system can follow
the grid reference power properly.

5.5 Other Applications of Coordinated Control

This dissertation also discusses other applications of coordinated control including the
coordinated control of single-phase system and considering about the ramp rate limit.

5.5.1 Coordinated Control in Single-phase System

With the increasing need for electric power, small distributed generation (DG) systems
are becoming more common. Small DG systems are usually built close to the end-users and they
take advantage of using different energy sources such as wind and solar [105-108]. A few
examples are hybrid cars, solar houses, data centers, or hospitals in remote areas where providing
clean, efficient and reliable electric power is critical to the loads [105-108]. The configuration of
above mentioned systems are similar to Fig.5.8, and the only difference is that there is a singlephase inverter, which is the only interface between sources connected to DC bus and loads
connected to an AC bus. By using the control method proposed in Section 5.3.3 to the singlephase grid-connected PV system, the single-phase inverter is responsible for the control of dcbus voltage and the AC bus reactive power. AC bus active power management is achieved by
charging and discharging ESUs.
103

The DQ rotating frame transformation used in the direct-current vector control of GCC
makes all time-varying state variables become DC variables, thus making the analysis easier
because the GCC can be treated as a dc-dc converter. Because of the limitation of only one
available phase in single-phase converters, this transformation cannot be realized unless a second
phase is created for every state variable in the circuit. Therefore, based on the real circuit model
of the inverter, an imaginary orthogonal circuit is created [105, 107]. Assuming the steady state
real circuit variable is expressed as
X R X M cos t

(5.13)

where, XR is the peak value of sinusoidal waveform which may represent either the voltage or the
current in the rotating frame, is the initial phase and is the fundamental frequency. Ideally
the corresponding imaginary orthogonal circuit variable would be:
X I X M sin t

(5.14)

Equation (5.15) defines the transformation from stationary to rotating frame and from
rotating frame to stationary frame
Xd
XM
X T
XI
q

and

X
XM
1 d
X T X
I
q

(5.15)

where,
cos(t ) sin(t )
T

sin(t ) cos(t )

(5.16)

cos(t ) sin(t )
T 1

sin(t ) cos(t )

(5.17)

It is important to notice that the variables in the rotating frame become constants (DC
values), as shown in (5.15). Those DC values define the DC operating point of the single-phase

104

converters in the rotating DQ frame. All of the control methods developed for DC/DC converters
can be applied.

Fig. 5.15. Single-phase grid connected solar PV generator under the control of a dc/dc power
converter using SimPowerSystems and Opal-RT RT-LAB

A computational experiment platform of the single-phase grid-connected PV system with


ESUs has also been developed using SimPowerSystems and Opal-RT RT-LAB. Both the real
and imaginary signals are implemented in GCC direct-current vector control (Fig. 5.4) with real
circuit electrical signals as d-axis components and imaginary orthogonal circuit electrical signals
as q-axis components. In this low-voltage DG system, the PV array has a series-parallel
connection configuration having 10 parallel strings with each string consisting of 3 series panels
and the dc bus voltage is initialized and expected to be at 440V. Assuming the solar irradiation is
constant at 750kW/m2 and the ac load changes from -10kW to -2 kW at t=1.5min, and then
changes to -6kW at t=3 min. The reactive power reference is set to be 0kVar practically.
105

P(kW)and Q(kVar)

4
0
-4
-8
PV

-12
0.5

1.5

Load

2
2.5
Time (min)

Q
3.5

Dc-link Voltage(V)

a) Active power of PV system and single-phase load active power and reactive power
500

450

400
0.5

1.5

2
2.5
Time (min)

3.5

b) DC-bus voltage
150

200

50

0
-50

-200
-400
0.5

1.5

2
2.5
Time (min)

3.5

Current (A)

Voltage (V)

400

-150
4

c) Single-phase voltage and current


150

200

50

0
-50

-200
-400
1.55

1.5505

1.551
Time (min)

1.5515

Current (A)

Voltage (V)

400

-150
1.552

d) A zoomed in single-phase voltage and current


Fig. 5.16. Simulation results of the proposed method applications in single-phase inverter
106

Simulation results of the proposed coordinated control method applications in singlephase inverter and ESUs are shown in Fig. 5.16. In fig. 5.16a, it is shown that the proposed
control method can provide the ac-bus load with the demanded active power when the PV
system outputs a same value of generated power. This is achieved by charging and discharging
battery and SC.
Also, it shows that the GCC vector control effectively maintains the reactive power of
system at 0kVar and regulates the dc-bus voltage at 440V steadily as requested (Fig. 5.16b).
With the steady performance of the DC-link voltage, MPPT enables the system to capture the
maximum power of the PV array, which stays the same value because of the same solar radiation
during this period of time.
Ac-bus load single-phase voltage and current are shown in Fig. 5.16c. The amplitude of
voltage is 220 V and it is noted that the amplitude of current is proportional to the amplitude of
active power. The reason is that the regulated reactive power is 0kVar, which determines that the
q-axis component of current is zero (Eq. 5.6), and then according to Eq. 5.5, the d-axis
component of current is proportional to the active power. Figure 5.16d is a zoomed-in of Fig.
5.16c, where a balanced and smooth profile of single-phase current is presented to demonstrate
the effective real-time simulation of OPAL-RT. As it can be seen from simulation results, the
proposed decoupled vector control can control power feeding into the grid, maintain reactive
power of grid and dc-link voltage.
In conclusion, Section 5.5.1 demonstrates that the proposed coordinated control method
presents its effectiveness in controlling load demand and maintaining dc-bus voltage in a singlephase system. The control method allows the single-phase inverter for reactive power and dc-link
voltage control, and makes use of ESUs to control the active power flow. The method uses the

107

DQ synchronous reference frame transformation for a single-phase inverter. Therefore, it is


important to create an imaginary orthogonal circuit for control. To validate the control method, a
grid-tied PV system with ESUs model has been built for simulation. Simulation results present
that the synchronous rotating frame current control for the single-phase inverter can fulfill
control objectives of following active and reactive power from the DMS, maintaining the
stability of the dc link voltage of the PV and energy storage system. Therefore, the coordinated
control scheme prosed in Section 5.3.3 can also be applied in single-phase grid-connected PV
system with ESUs.

5.5.2 Coordinated Control Considering about Ramp Rate Limit

Mitigation of the variability in output power of renewable generators such as solar


photovoltaic (PV) systems is a growing concern as these generators reach higher penetrations on
electric grids [109]. Solar resource short-term variability where the PV system is installed may
be high from the standpoint that most days are partly cloudy. The irradiance patterns from a
plane of array (POA) at the Tennessee plant is presented in Ill. 5.1.
It can been seen that some weather events in Ill. 5.1 can increase PV generation from
negligible levels to maximum output in a very short period of time, therefore, PV can have very
volatile real power flows. The resulting output fluctuations can adversely affect the grid in the
form and voltage sags if steps are not taken to quickly counteract the change in generation. In
small power systems, frequency can also be adversely affected by sudden changes in renewable
energy generation. ESUs, whether located at the PV generation system or distributed along a
feeder, can provide power quickly in such scenarios so as to minimize disturbances. With the
proper control schemes, ESUs can mitigate the above challenges while improving system
108

reliability and improving the effectiveness of the renewable resource, thus providing a solution to
the integration of distributed renewable energy sources to the electric grid.

Ill. 5.1 Measured solar irradiance profiles (blue areas) for each day in August 2012 [109]
One-min average data are shown from a POA at the Tennessee plant

In this application, the hybrid system of battery and SC are used to smooth the output
power of a PV array. The proposed control is designed to provide active power support with
power smoothing and power ramp control by charging and discharging ESUs (Fig. 5.17) while
maintaining dc-link voltage by GCC direct vector control shown in Section 5.3.3.
In the control structure for ESUs, the difference between the desired and the actual PV
output power can be either injected or drawn from ESUs. Therefore, this energy becomes the
reference generated/ absorbed power from storage units, Psto_ref.. Reference charging or

109

discharging power of battery Pb_ref is obtained after applying a low-pass filter on Psto_ref , and
then the reference current of battery ib_ref is calculated. The rest is used as the SC reference power
Psc_ref and to calculate reference current of SC, isc_ref.

i pv

p pv

vb

psto _ ref

pb _ ref

vsc

v pv

psc _ ref

ib _ ref

ib

i
isc _ ref sc

1/ vdc
1/ vdc

Fig. 5.17. Energy storage units connected converters control structure

ESU control strategy shown in Fig. 5.17 is implemented in the computational experiment
platform (Fig. 5.8) for simulation. To evaluate the control schemes, solar radiation data of two
random days in Adair Casey [54] is used as two simulation scenarios (Fig. 5.18). Because the
data is provided in minute-scale, a linear interpolation is used for prediction of data between

Solar Radiation (kW/m2)

Solar Radiation (kW/m2)

minutes.

1.5

0.5

12
Time (h)

16

20

24

a) Scenario 1

1.5

0.5

12
Time (h)

16

b) Scenario 2

Fig. 5.18. Hourly solar radiation data of two random days in Adair Casey

110

20

24

20

40

PPV

30

PPV +PESU

P (k W )and Q (k V ar)

P (k W )and Q (k V ar)

50

Grid Q

20
10
0

10

12
14
Time (h)

16

18

20

a) PV generated power, smooth power

5
0

P(kW)and Q(kVar)

P(kW)and Q(kVar)

30
20
PPV +PESU

13.5

14

14.5
15
Time (h)

15.5

16

15

10

12
14
Time (h)

16

18

20

PPV +PESU

7.5

8.5

9
9.5
Time (h)

10

10.5

b) Zoomed-in PV and ESU power of a)


5

Battery
SC

Battery
SC

2.5
P(kW)

P(kW)

16.5

0
-2.5

-20
4

10

12
14
Time (h)

16

18

-5

20

10

12
14
Time (h)

16

18

20

c) ESU Charging and discharging power

c) ESU Charging and discharging power

30

10

Original
Controlled

15

P(kW/min)

P(kW/min)

PPV

10

b) Zoomed-in PV and ESU power of a)

20

after ESU and grid reactive power

40

13

Grid Q

a) PV generated power, smooth power

50

PPV

PPV +PESU

10

after ESU and grid reactive power

10

PPV

15

0
-15
-30

10

12
14
Time (h)

16

18

0
-5
-10

20

Original
Controlled

10

12
14
Time (h)

16

18

20

d) Comparison of min-to-min ramp rates

d) Comparison of min-to-min ramp rates

Fig. 5.19 Simulation results of scenario 1

Fig. 5.20 Simulation results of scenario 2

111

Figures 5.19 and 5.20 present simulation results in both solar irradiation scenarios, based
on which the following conclusions are obtained:
1) Figures. 5. 19a and 5.20a present the PV generated power, active power injected to
grid and grid reactive power. The reactive power reference can follow the reference at 0kVar.
The power injected to gird consists of PV generated power and ESUs charging and discharging
power. It is noted that the ramp rate refers only to real power, and that the reactive power
capabilities of the ESUs can be dispatched simultaneously and independently to achieve other
power system goals. According to Fig 5.19a, 5.20a and their corresponding zoomed-in in Fig.
5.19b and 5.20b, the power captured by PV array is nearly proportional to the solar irradiation.
Therefore, large amount of solar irradiation fluctuations produce relatively large changes in the
captured PV power. Also, it is observed that the proposed ramp rate control can smooth real
power fluctuations from an associated POA, following the moving average of trend of the PV
output. Therefore, the solar PV system with ESUs inject less fluctuated power into the network.
Different low-pass filter parameters are used in these two scenarios for desired performance.
Therefore, two necessary considerations for the control design are indicated: 1) using dynamic
ramp control instead of fix ramp control; and 2) predicting solar radiation profile.
2) Figure 19c and 20c are the charging and discharging power profiles for two scenarios,
the power profile of SC has a much larger frequency than that of battery. The power output of a
POA does not necessarily consist of an equal number of upward and downward deviations, so
the ESUs could have a tendency to discharge or charge outside of its desired operating range.
Therefore, it is observed that one important factor that needs to be considered when
implementing a ramp rate control, is keeping the battery at an appropriate level of charge. The
historical solar irradiation and its probabilities should be applied to design an economic ESU

112

systems associated with the PV generation. Actually, in this real-time simulation, it is remarked
that those factors that can limit the real power output, including the maximum power generation/
absorption of the ESUs, ESUs current limit, battery state of charge, which are satisfied and
simplified in this dissertation for testing the effectiveness of the proposed control method.
3) 1-min ramp rate of original PV generated power and power after ramp rate control are
presented in Fig. 19d and 20d. 1-minute ramp rate is defined as the absolute value of the
difference between the instantaneous power at the beginning and at the end of a 1-minute period
[111]. It should be noted that ramp rate values are highly dependent on the time range used to
determine the scalar ramp rate value. The 1-second ramp rates are far different than the 10minute ramp rate. Formally, ramp rates over different time scales (t) can be calculated using the
equation [111]
Ramp Rate

P(t0 ) P(t0 t )
t

(5.18)

where, P(t0) and P(to+t) are the instantaneous power at t0 and after t. Both comparisons of 1minute ramp rate in Fig. 19d and 20d depict the operation of ramp rate control smooth the
volatile ramp rate of PV array under different irradiation profiles. This behavior translates to a
significant reduction in wear and tear on the electrical grid, and helps to maintain system
electrical frequency.
In order to see the performance of ramp rate control, Table 5.2 shows a comparison of
mean and maximum values of ramp rate before and after ramp rate control in two scenarios. In
the table, ramp rate under scenario 1, which has more severe variations in the solar irradiation,
presents a larger improvement in controlled ramp rate value. It is concluded that integration of
ESUs into the grid to manage the real power variability of PV generation by providing ramp rate

113

control can optimize the benefits of PV resources because of the evident reduction of ramp rate
under both scenarios.
Figure 5.21 is profiles of dc-link voltage for two scenarios, which proves that GCC vector
control effectively regulates and maintains the dc-bus voltage at 1500V steadily as desired.

Table 5.2. Comparison of ramp rate value before and after designed
ramp rate control in two scenarios
Study Case
Scenario 1 (kW/min) Scenario 2 (kW/min)

Mean value before control

3.00

0.12

Mean value after control

0.72

0.07

Maximum value before control

27.47

4.95

Maximum value after control

6.67

1.28

1520
1510
1500
1490
1480

10

12 14
Time (h)

16

18

20

Dc -link V oltage(V )

Dc -link V oltage(V )

Ramp Rate

a) Scenario 1

1520
1510
1500
1490
1480

10

12 14
Time (h)

b) Scenario 2

Fig. 5.21 Dc-link voltages of two solar irradiation scenarios

114

16

18

20

In conclusion, the proposed coordinated control scheme is effective to provide active


power support with power smoothing, power ramp control, and dc-link voltage support.
Coupling PV generation and energy storage devices will drastically increase reliability of the
grid, enables more effective grid management. The rapid-response characteristic of the ESUs
makes storage especially valuable as a regulation resource and enables it to compensate for the
variability of PV generation. It is indicated that both dynamic ramp rate control and solar
radiation profile prediction are necessary for the control design, also, factors that can limit the
real power output include: the maximum power generation/absorption of the ESUs, ESUs current
limit, battery state of charge should be consider for ramp rate control effectively and
economically.

5.6 Conclusion

Energy storage systems are a promising solution regarding the integration of fluctuating
renewable energy into grids. This chapter focuses on control designs of grid-connected
photovoltaic system with ESUs and how to coordinate all the electrical devices in the whole
system by the control of power electronics. In the proposed method, GCC is operated at VQ
mode to maintain a stable dc-link voltage and adapt to the reactive power command, PVCC is
designed to implement the MPPT of PV array, and ESUs connected converters control are
conceived to achieve the power balance of the whole system. A comprehensive computational
simulation study demonstrates that the proposed control structure can effectively supply the
desired reactive and active power to the grid and achieve the stability of dc link voltage through
power electronic converters coordination.

115

The proposed coordinated control has also been modified and tested in other applications
considering single-phase DQ control and ramp rate control. In single-phase grid-connected PV
system with ESUs, it is demonstrated that the proposed method allows inverter for active and dclink voltage control with active power buffered through ESUs. An imaginary orthogonal circuit
has been successfully created and applied into the DQ control. In ramp rate control, the proposed
system control scheme can be used to provide active power support with power smoothing,
power ramp control, and dc-link voltage support. Coupling PV generation and storage devices
will drastically increase reliability of the grid, enabling more effective grid management. It is
indicated that parameters of ESUs and desired level of smooth should be taken into consideration
to make control economical.

116

CHAPTER 6
CONCLUSIONS AND FUTURE WORK

6.1 Contributions of the Dissertation

This dissertation demonstrates solar photovoltaic energy generation and conversion from
devices to grid integration.
Firstly, this dissertation investigates solar PV system performance under uneven shading
and dissimilar conditions, especially using both simulation tools and Newton-Raphson algorithm
to study and cross-verify the I-V and P-V characteristics of shaded and unshade cells. It is found
that a traditional PV module with one single shaded cell is the most hazardous condition to affect
proper function of a PV module. It is observed that, with bypass diodes, the performance of PV
device is more complicated and different from the traditional understanding of the PV I-V and PV characteristics and each PV cell with a bypass diode will have the most significant
improvement in the performance of a PV module/array under uneven shading.
Secondly, this dissertation provides a fast and robust MPPT technique and compares it
with typical conventional MPPT algorithms used in solar PV industry. Through both software
and hardware simulation, it is concluded that the proposed MPPT approach has the least
oscillation and the highest stability. Both the sampling rate affects and variable solar irradiance
levels are considered in the comparison. The comparison between the traditional and proposed
adaptive methods shows that the hyperbolic processing of the derivation is important for high
performance of a solar PV system.
117

Thirdly, this dissertation compares the energy extraction characteristics of a solar PV


system for different converter schemes, including central, string and micro converter
configurations especially uneven shadings. It is concluded that the central converter based PV
system with properly built-in bypass diodes is an effective and economic approach to improve
efficiency, performance, and reliability of a PV system.
Last but not least, this dissertation discusses control designs of grid-connected
photovoltaic system with ESUs and how to coordinate all the electrical devices in the whole
system by the control of power electronics. In the proposed method, GCC is operated at VQ
mode to maintain a stable dc-link voltage and adapt to the reactive power command, PVCC is
designed to implement the MPPT of PV array, and ESUs connected converters control are
conceived to achieve the power balance of the whole system. A comprehensive computational
simulation study demonstrates that the proposed control structure can effectively supply the
desired reactive and active power to the grid and achieve the stability of dc-link voltage through
power electronic converters coordination. Additionally, the proposed coordinated control has
also been modified and tested in other applications considering single-phase DQ control and
ramp rate control. The simulation results present an effective performance in these two
applications.

6.2 Limitations and Future Work

In ramp rate control of gird-connected PV system with ESUs, it is noted that a dynamic
ramp control design instead of fix ramp is necessary for a practical control in the future work
because of volatile solar radiation.

118

Also, it is not yet considered how to keep ESUs at an appropriate level of charging/
discharging when implementing ramp rate control.
The parameters of ESUs in this dissertation are given ideally to verify the effectiveness of
ramp rate control without optimizing the cost. It is important to design economically considering
factors that can limit the real power output including the maximum power generation/ absorption
of the ESUs, ESUs current limit, ESUs state of charge. With great certainty, we can say that the
demand for development and improvement of grid-integrated renewable energy will remain.

119

REFERENCES

[1]

Global Trends in Sustainable Energy Investment 2007, United Nations Environment


Pogramme/New Energy Finance Ltd. 2007.

[2]

E. Lorenzo, G. Araujo, A. Cuevas, M. Egido, J. Miano and R. Zilles, Solar electricity:


engineering of photovoltaic systems, Progensa, 1994.

[3]

J. M. Carrasco, L. G. Franquelo, J. T. Bialasiewicz, E. Galvn, R. C. P. Guisado, M. .


M. Prats, J. I. Len, and N. Moreno-Alfonso, Power-Electronic Systems for the Grid
Integration of Renewable Energy Sources: A Survey, IEEE Trans. On Industrial
Electronics, Vol. 53, No. 4, August, 2006.

[4]

J. Nelson, The Physics of Solar Cells, London: Imperial College press, 2003.

[5]

E. F. Camacho, T. Samad, M. G. Sanz, and I. Hiskens, Control for Renewable Energy


and Smart Grids.

[6]

L. Gao, R. A. Dougal, S. Liu, and A. P. Iotova, Parallel-Connected Solar PV System to


Address Partial and Rapidly Fluctuating Shadow Conditions, IEEE Trans. On
Industrial Electronics, Vol. 56, No. 5, May 2009.

[7]

H. Patel and V. Agarwal, MATLAB-Based Modeling to Study the Effects of Partial


Shading on PV Array Characteristics, IEEE Trans. On Energy Conversion, Vol. 23,
No. 1, March 2008.

[8]

Y. H. Ji, D. Y. Jung, C. Y. Won, B. K. Lee, and J. W. Kim, Maximum Power Point


Tracking Method for PV Array under Partially Shaded Condition, in Proceedings of
IEEE 2009 Energy Conversion Congress and Exposition, R. Candela, V. Di Dio , E.
Riva Sanseverino, and P. Romano, Reconfiguration Techniques South Korea, Sep. 2024, 2009, pp. 307-312.

[9]

R. Candela, V. D. Dio , E. R. Sanseverino, and P. Romano, Reconfiguration


Techniques of Partial Shaded PV Systems for the Maximization of Electrical Energy
Production, in Proceedings of 2007 International Conference on Clean Electrical
Power, Capri, Italy, May 21-23, 2007, pp. 716-719.

120

[10]

R. Ramaprabha and B.L. Mathur, Modelling and Simulation of Solar PV Array under
Partial Shaded Conditions, in Proceedings of IEEE International Conference on
Sustainable Energy Technologies (ICSET 2008), Singapore, November 24-27, 2008.

[11]

H. C. Chang, C. C. Chen, L. C. Huang and C. C. Lin, Implementation of a power


supply with the characteristics of solar panels under partially shaded, in Proceedings of
IEEE 2010 Instrumentation and Measurement Technology Conference, Austin, TX, May
3-6, 2010, pp. 14272-1476.

[12]

Y. H. Ji, J. G. Kim, S. H. Park, J. H. Kim, and C. Y. Won, C-language Based PV Array


Simulation Technique Considering Effects of Partial Shading, in Proceedings of 2009
IEEE International Conference on Industrial Technology, Gippsland, Australia, Feb. 1013 2009.

[13]

R. Faranda and S. Leva, Energy comparison of MPPT techniques for PV Systems,


WSEAS Trans. on Power Systems, Vol.3, No.6 2008, pp. 4462455.

[14]

S. Li, T. A. Haskew, D. Li and F. Hu, Integrating Photovoltaic and Power Converter


Characteristics for Energy Extraction Study of Solar PV Systems, Renewable Energy
(Elsevier), Vol. 36, Issue 12, Deecmber 2011, pp. 3238-3245.

[15]

R. Mallwitz, B. Engel, Solar Power Inverters, CIPS 2010, March, 16-18, 2010,
Nuremberg/Germany.

[16]

P. Chapman, G. Madianos, AC modules and solar power electronics, in Solar Bridge


technologies, Rev. 1.0 October 8, 2010.

[17]

S. B. Kjaer, J. K. Pedersen, and F. Blaabjerg, A review of single-phase grid-connected


inverters for photovoltaic modules, IEEE Transactions on Industry Applications, vol.
41, no. 5, pp. 1292-1306, 2005.

[18]

R. W. Erickson, A.P. Rogers, A Microinverter for Building-Integrated Photovoltaics,


Applied Power Electronics Conference and Exposition, 2009 (APEC 2009), 15-19 Feb.
2009, pp. 911-917.

[19]

Y. Chen, K. Lo, and Y. Chang, Multi-String Single-Stage Grid-Connected Inverter for


PV system, Energy Conversion Congress and Exposition (ECCE), 2011 IEEE, 01 Nov.
2011, pp. 2751-2756.

[20]

M. A. Guerrero, E. Romero, F. Barrero. M.I. Milanes and E. Gonzalez, Overview of


Medium Scale Energy Storage Systems, Compatibility and Power Electronics, 2009.

[21]

Z. Zheng, X. Wang and Y. Li, A Control Method for Grid-friendly Photovoltaic


Systems with Hybrid Energy Storage Units, Electric Utility Deregulation and
Restructuring and Power Technologies, 2011.

121

[22]

G. W. Neudeck, PN Junction Diode, 2nd ed., Prentice Hall, ISBN-10: 0201122960, 1988.

[23]

G. M. Masters, Renewable and Efficient Electric Power Systems, 2004 Wiley-IEEE


Press.
Y. Chen, H. Wu, and Y. Chen, DC Bus Regulation Strategy for Grid-Connected PV
Power Generation System, Proceedings of IEEE International Conference on
Sustainable Energy Technologies (ICSET 2008), Singapore, Nov. 24-27, 2008.

[24]

[25]

K. K. Tse, M. T. Ho, Henry S. H. Chung, S. Y. Hui, A Novel Maximum Power Point


Tracker for PV Panels Using Switching Frequency Modulation, IEEE Trans. on Power
Electronics, 2002, Vol. 17(6), pp. 980-989.

[26]

V. M. Senjyu, T. Uezato, Maximum power point tracking control of IDB converter


supplied PV system, IEEE Proc. Electronics Power Application, 2001, vol. 148(6), pp.
494-502.

[27]

V. Quaschning and R. Hanitsch, Numerical Simulation of Current-Voltage


Characteristics of Photovoltaic System with Shaded Solar Cells, Solar Energy, Vol. 56,
No. 6, pp.513-520, 1996.

[28]

J.W. Bishop, "Computer Simulation of the Effects of Electrical Mismatches in


Photovoltaic Cell Interconnection Circuits," Solar Cells, 25(1988), 73-89.

[29]

C. Zhang, J. Zhang, Y. Hao, Z. Lin and C. Zhu, A simple and efficient solar cell
parameter extraction method from a single current-voltage curve, Journal of Applied
Physics, Vol. 110, Iss. 6, pp. 064504-064504-7, Sep. 2011.

[30]

M. Ye, X. Wang and Y. Xu, Parameter extraction of solar cells using particle swarm
optimization, Journal of Applied Physics, Vol. 105, Iss. 9, pp. 094502-094502-8, 2009

[31]

S. Li and H. Zheng, Energy Extraction Characteristic Study of Solar Photovoltaic Cells


and Modules, Proceedings of 2011 IEEE PES General Meeting, Detroit MI, July 24-28,
2011.

[32]

H. Zheng, S. Li, T. Haskew and Y. Xiao, Impact of uneven shading and bypass diodes
on energy extraction characteristics of solar photovoltaic modules and arrays,
International Journal of Sustainable Energy, ISSN. 1478-6541, Aug. 2012.

[33]

P. W. Tuinenga, SPICE - A Guide to Circuit Simulation & Analysis Using PSpice,


Upper Saddle River, NJ: Prentice Hall, 1995.

[34]

M. H. Rashid, Introduction to PSpice Using OrCAD for Circuits and Electronics, Upper
Saddle River, NJ: Prentice Hall, 3rd ed., 2004.

[35]

National Instruments, "Introducing NI Multisim 11.0: Easy Design, Better Simulation,"


available from http://www.ni.com/multisim/, last time viewed December 2012.
122

[36]

Bypass
diodes,
available
from
Photovoltaic
Education
Network:
http://pveducation.org/pvcdrom/modules/bypass-diodes , last viewed: Nov. 10, 2011.

[37]

C. Hua, J. Lin, and C. Shen,Implementation of a DSP Controlled Photovoltaic System


with Peak Power Tracking, IEEE Transactions on Industrial Electronics, vol. 45, no. 1,
pp 99-107, Feb 1998.

[38]

N. Femia, G. Petrone, G. Spagnuolo, and M. Vitelli, .Optimization of perturb and


observe maximum power point tracking method, IEEE Trans. on Power Electronics,
Vol. 20, No. 4, July 2005, pp. 963-973.

[39]

M. Veerachary, T. Senjyu, and K. Uezato, Voltage-based maximum power point


tracking control of PV system, IEEE Trans. on Aerospace Electronic System, Vol. 38,
No. 1, Jan. 2002, pp. 262.270.

[40]

T. Tafticht, K. Agbossou, M.L. Doumbia and A. Chriti, An improved maximum


power point tracking method for photovoltaic systems, Renewable Energy, vol. 33, no.
7, July 2008, Pages 1508-1516.

[41]

N. Mohan, T. M. Undeland, and W. P. Robbins, Power Electronics: Converters,


Applications, and Design, 3rd Ed., John Wiley & Sons Inc., October 2002.

[42]

R. Faranda and S. Leva, Energy comparison of MPPT techniques for PV Systems,


WSEAS Trans. on Power Systems, Vol.3, No.6 2008, pp. 4462455.

[43]

T. Noguchi, S. Togashi and R. Nakamoto, "Short-current pulse-based maximum-powerpoint tracking method for multiple photovoltaic-and-converter module system", IEEE
Trans. on Industrial Electronics, Vol. 49, pp. 217-223, Feb 2002.

[44]

K. Kobayashi, H. Matsuo and Y. Sekine, A novel optimum operating point tracker of


the solar cell power supply system, in 35th Annual IEEE Power Electron. Specialists
Conf., 2004, pp. 2147-2151.

[45]

R. Faranda, S. Leva and V. Maugeri, MPPT Techniques for PV Systems: Energetic and
Cost Comparison. Proceedings of IEEE Power and Energy Society General MeetingConversion and Delivery of Electrical Energy in the 21st Century, 2008, pp-1-6.

[46]

A. Al-Amoudi and L. Zhang, Optimal control of a grid-connected PVsystem for


maximum power point tracking and unity power factor, 7th International Conf. on
Power Electronics and Variable Speed Drives, No. 456, Sep. 2123,1998, pp. 8085.

[47]

N. Femia, D. Granozio, G. Petrone, G. Spaguuolo, and M.Vitelli, Optimized One-Cycle


Control in Photovoltaic Grid Connected Applications, IEEE Trans. Aerosp. Electron.
Syst., Vol. 2, No. 3, July 2006.

123

[48]

R. A. Mastromauro, M. Liserre and A. D. Aquila, Control Issues in Single-Stage


Photovoltaic Systems: MPPT, Current and Voltage Control, IEEE Trans. on Industrial
Informatics, Vol. 8, No. 2, May 2012.

[49]

W. Wu, N. Pongratananukul, W. Qiu, K. Rustom, T. Kasparis and I. Batarseh, DSPbased Multiple Peak Power Tracking for Expandable Power System, Proc. APEC,
2003, pp. 525-530.

[50]

B. Szabados and F. Wu, A maximum power point track control of a photovoltaic


system, IEEE International Instrumentation and Measurement Technology Conference,
Vancouver Island, Canada, May 2008.

[51]

N. Femia, G. Petrone, G. Spagnuolo and M. Vitelli, Optimization of Perturb and


Observe Maximum Power Point Tracking Method, IEEE Trans. Power Electronics,
Vol. 20, pp. 963-973, July 2005.

[52]

M. Veerachary, T. Senjyu and K. Uezato, Neural-network-based maximum-powerpoint tracking of coupled-inductor interleaved-boost-converter-supplied PV system
using fuzzy controller, IEEE Trans. Ind. Electron., Vol. 50, pp. 749-758, Aug. 2003.

[53]

N. Khaehintung, K. Pramotung, B. Tuvirat, and P. Sirisuk, RISC-microcontroller builtin fuzzy logic controller of maximum power point tracking for solar-powered lightflasher applications, in 30th Annual Conf. of IEEE Ind. Electron. Society, 2004, pp.
2673-2678.

[54]

Air
temperature
and
solar
radiation
data,
available
http://www.schoolnet8.com/dl/index.phtml , last time viewed: Sep. 19, 2011.

[55]

T. Esram and P. L. Chapman, Comparison of Photovoltaic Array Maximum Power


Point Tracking Techniques, IEEE Trans. Energy Conversion, Vol.22, No.2, pp.360-7,
1995.

[56]

A. Abdelsalam and A. Massoud, High-Performance Adaptive Perturb and Observe


MPPT Technique for Photovoltaic-Based Microgrids, IEEE Trans. Power. Electronics.
Vol. 26, No. 4, Apr. 2011.

[57]

R. Faranda, S. Leva, and V. Maugeri, MPPT techniques for PV systems: energetic and
cost comparison. IEEE Power and Energy Society General Meeting-Conversion and
Delivery of Electrical Energy in the 21st Century, 2008, pp-1-6.

[58]

C. Otieno, G. Nyakoe and C. Wekesa, A Neural Fuzzy Based Maximum Power Point
Tracker for a Photovoltaic System, IEEE AFRICON, 2009, pp.1-6.

[59]

Z. Yu, Study of MPPT Technique Based on Fuzzy Logic Control in PV System.


Huazhong University of Science and Technology, Wuhan, 2007.

124

from

[60]

A. Hussein, K. Hirasawa, J. Hu and J. Murata, The dynamic performance of


photovoltaic supplied dc motor fed from DCDC converter and controlled by neural
networks, Int. Joint Conf. Neural Netw. 2002, pp. 607612.

[61]

X. Sun, W. Wu, X. Li and Q. Zhao, A research on photovoltaic energy controlling


system with maximum power point tracking, in Proc. Power Convers. Conf., 2002, pp.
822826.

[62]

P. Midya, P. T. Krein, R. J. Turnbull, R. Reppa, and J. Kimball, Dynamic maximum


power point tracker for photovoltaic applications, Proc. 27th Annu. IEEE Power
Electron. Spec. Conf., 1996, pp. 17101716.

[63]

S. Brunton, C. W. Rowley, S. R. Kulkarni, and C. Clarkson, Maximum Power Point


Tracking for Photovoltaic Optimization Using Ripple-Based Extremum Seeking
Control, IEEE Transaction on Power Electronics, Vol. 25, No. 10, Oct. 2010.

[64]

Real-Time Modeling
rt.com/node/292.

[65]

S. Li, T.A. Haskew, K.A. Williams and R.P. Swatloski, Control of DFIG Wind Turbine
with Direct-Current Vector Control Configuration, IEEE Trans. on Sustainable Energy,
Vol. 3, No. 1, Jan. 2012, pp. 1-11.

[66]

K. Bao, S. Li, and H. Zheng, Battery Charge and Discharge Control for Energy
Management in EV and Utility Integration, Proceedings of 2012 IEEE PES General
Meeting, San Diego, CA, July 22-26, 2012.

[67]

A. Mills, M. Ahlstrom, M. Brower, A. Ellis, R. George, T. Hoff, B. Kroposki, C. Lenox,


N. Miller, M. Milligan, J. Stein, and Y. Wan, Dark Shadows, IEEE Power and Energy
Magazine, May- June 2011.

[68]

E4360A Modular Solar Array Simulator Mainframe,


http://www.home.agilent.com/agilent/product.jspx?nid=35489.771280.00&lc=eng&cc=US&pselect=SR.Looking.

[69]

M. A. G. Brito, G. J. Luigi, L. P. Sampaio, A. M. Guilherme and C. A. Canesin,


Evaluation of the Main MPPT Techniques for photovoltaic Application, IEEE Trans.
on Industrial Electronics, No. 99, 2011.

[70]

Embedded success dSPACE DS1103 PPC Controller Board, available from:


ttp://www.dspaceinc.com/en/inc/home/products/hw/singbord.cfm.

[71]

A. Rubaai, A. R. Ofoli and D. Cobbinah, DSP-Based Real-Time Implementation of a


Hybrid H Adaptive Fuzzy Tracking Controller for Servo-Motor Drives, IEEE Trans.
on Industry Applications, Vol. 43, No. 2, pp476-484, March/April 2007.

tools:

RT-EventsTM,

125

available

from

http://www.opal-

available

from:

[72]

K. Kobayashi, H. Matsuo and Y. Sekine, "A novel optimum operating point tracker of
the solar cell power supply system," in 35th Annual IEEE Power Electron. Specialists
Conference, 2004, pp. 2147-2151.

[73]

Evergreen
Renewable
Energy,
available
from:
http://www.evergreenrenewableenergy.co.uk/index.php, last viewed: Nov. 10, 2011

[74]

Solar
Novus
Today,
available
from:
http://www.solarnovus.com/index.php?option=com_content&view=article&id=4138:nat
ional-electrical-code-auto-shutdown-vote-this-week&catid=76:guest-blogs&Itemid=353
, last viewed: Oct. 15th, 2012.

[75]

S. Li and H. Zheng, Energy Extraction Characteristic Study of Solar Photovoltaic Cells


and Modules, Proceedings of 2011 IEEE PES General Meeting, Detroit MI, July 24-28,
2011.

[76]

H. Zheng, S. Li, T. Haskew and Y. Xiao, Impact of uneven shading and bypass diodes
on energy extraction characteristics of solar photovoltaic modules and arrays,
International Journal of Sustainable Energy, ISSN. 1478-6541, Aug. 2012.

[77]

S. Luo, A. Luo, Z. Lv, Y. Shen, G. Lu, and W. Jiang, Power quality active control
research of building integrated photovoltaic, Power Electronics for Distributed
Generation Systems (PEDG), 2010 2nd IEEE International Symposium, 16-18 June
2010.

[78]

Y. Zhang, S. Zhu, and A. and A. Chowdhury, Reliability Modeling and Control


Schemes of Composite Energy Storage and Wind Generation System with Adequate
Transmission Upgrades, IEEE Trans. on Sustainable Energy, Vol. 2, No. 4, 2011.

[79]

H. Kanchev, D. Lu, F. Colas, V. Lazarov, and B. Francois, Energy Management and


Operational Planning of a Microgrid With a PV-Based Active Generator for Smart Grid
Applications, IEEE Trans. on Industrial Electro., Vol. 58, No. 10, 2011.

[80]

Y. Riffonneau, S. Bacha, F. Barruel, and S. Ploix, Optimal Power Flow Management


for Grid Connected PV Systems With Batteries, IEEE Trans. on Sustainable Energy,
Vol. 2, No. 3, 2011.

[81]

M. A. Guerrero, E. Romero, F. Barrero. M.I. Milanes and E. Gonzalez, Overview of


Medium Scale Energy Storage Systems, Compatibility and Power Electronics, 2009.

[82]

I. Hadjipaschalis, A. Poullikkas, and V. Efthimiou, Overview of current and future


energy storage technologies for electric power applications, Renewable and Sustainable
Energy, Vol. 13, Issue. 6, Aug., 2009, P15131522.

126

[83]

A. A. Hussein, N. Kutkut, Z. J. Shen, and I. Batarseh, Distributed Battery MicroStorage Systems Design and Operation in a Deregulated Electricity Market, IEEE
Trans. on Sustainable Energy, Vol. 3, No. 3, 2012.

[84]

M. Takagi, Y. Iwafune, K. Yamaji, H. Yamamoto, K. Okano, R. Hiwatari, and T. Ikeya,


Economic Value of PV Energy Storage Using Batteries of Battery-Switch Stations,
IEEE Trans. on Sustainable Energy, Vol. 4, No. 1, Jan. 2013.

[85]

Q. Kang, X. Xiao, H. Yi, and Z. Nie, Energy Management in Grid Connected PV


Systems with Supercapacitor Energy Storage, International Electrical Machines and
Systems (ICEMS) Conference, 2011.

[86]

H. Seo, C. Nat, G. H. Kim, S.Y. Kim, N. Kim, H. G. Lee, C. Hwang, M. Park, and I. K.
Yu, Power quality control strategy for grid-connected renewable energy sources using
PV array and supercapacitor, International Electrical Machines and Systems (ICEMS)
Conference, 2010.

[87]

Z. Zheng, X. Wang and Y. Li, A Control Method for Grid-friendly Photovoltaic


Systems with Hybrid Energy Storage Units, Electric Utility Deregulation and
Restructuring and Power Technologies, 2011.

[88]

R. Teodorescu, M. Liserre and P. Rodrguez, Grid Converters for Photovoltaic and


Wind Power Systems, Wiley-IEEE Press, 2010.

[89]

H. Fakham, D. Lu, and B. Francois, Power Control Design of a Battery Charger in a


Hybrid Active PV Generator for Load-Following Applications, IEEE Trans. on Ind.
Electron., Vol. 58, No. 1, 2011.

[90]

A. Gabash, and P. Li, Active-Reactive Optimal Power Flow in Distribution Networks


With Embedded Generation and Battery Storage, IEEE Trans. on Power System, Vol.
27, No. 4, Nov. 2012.

[91]

X. Hu, K. J. Tseng and M. Srinivasan, Optimization of Battery Energy Storage System


with Super-Capacitor for Renewable Energy Applications, 8th International
Conference on Power Electronics - ECCE Asia, May 30-June 3, 2011, The Shilla Jeju,
Korea.

[92]

C. Wang, and M. H. Nehrir, Power Management of a Stand-Alone


Wind/Photovoltaic/Fuel Cell Energy System, IEEE Trans. on Energy Conversion., Vol.
23, No. 3, 2008.

[93]

C. Cecati, C. Citro, and P. Siano, Combined Operations of Renewable Energy Systems


and Responsive Demand in a Smart Grid, IEEE Trans. on Sustainable Energy, Vol. 2,
No. 4, 2011.

127

[94]

I. Hong, B. Kang and S. Park Design and implementation of intelligent energy


distribution management with photovoltaic system, IEEE Trans. on Consumer
Electronics, Vol. 58, Iss. 2, 2012.

[95]

S. Li and K. Bao, Study of Battery Modeling using Mathematical and Circuit Oriented
Approaches, 2011 IEEE PES General Meeting.

[96]

S. Li, H. T. Haskew and S. Richard, Control of DFIG Wind Turbine with Optimal and
Direct- Current Vector Control Configuration, IEEE Trans. on Sustain. Energy, Vol. 3,
Issue 1, 2012

[97]

A. Roshan, R. Burgos, A. Baisden, F. Wang and D. Boroyevich, A D-Q Frame


Controller for a Full-Bridge Single Phase Inverter Used in Small Distributed Power
Generation Systems, Applied Power Electronics Conference, APEC 2007.

[98]

R. Pena, J.C. Clare, and G. M. Asher, Doubly fed induction generator using back-toback PWM converters and its application to variable speed wind-energy generation,
IEEE Proc.-Electr. Power Appl., Vol. 143, No 3, May 1996.

[99]

A. D. Hansen, P. Srensen, F. Iov and F. Blaabjerg, Control of variable speed wind


turbines with doubly-fed induction generators, Wind Engineering, Vol. 28, No. 4, June
2004, pp. 411-432.

[100] A. Mullane, G. Lightbody, and R. Yacamini, Wind-Turbine Fault Ride-Through


Enhancement, IEEE Trans. on Power Systems, Vol. 20, No. 4, Nov. 2005.
[101] B. C. Rabelo, W. Hofmann, J. L. Silva, R. G. Oliveira, and S. R. Silva, Reactive Power
Control Design in Doubly Fed Induction Generators for Wind Turbines, IEEE
Transactions on Industrial Electronics, Vol. 56, No. 10, October 2009, pp. 4154-4162.
[102] J. C. Vasquez, J. M. Guerrero, A. Luna, P. Rodrguez, and R. Teodorescu, Adaptive
Droop Control Applied to Voltage-Source Inverters Operating in Grid-Connected and
Islanded Modes, IEEE Trans. on Industrial Electronics, Vol. 56, No. 10, October 2009,
pp. 4088-4096.
[103] N. Mohan, Advanced Electric Drives Analysis, Modeling and Control using Simulink,
MN: Minnesota Power Electronics Research & Education, ISBN 0-9715292-0-5, 2001.
[104] Shuhui Li, Tim Haskew, and Ling Xu, Control of HVDC Light Systems using
Conventional and Direct-Current Vector Control Approaches, IEEE Transactions on
Power Electronics, Vol. 25, No. 12, December 2010, pp. 3106-3118.
[105] R. Arman, A Dq Rotating Frame Controller for Single Phase Full-Bridge Inverters
Used in Small Distributed Generation Systems.

128

[106] S. Samerchur, S. Premrudeepreechacharn, Y. Kumsuwun, and K. Higuchi, Power


Control of Single-Phase Voltage Source Inverter for Grid-Connected Photovoltaic
Systems, Power Systems Conference and Exposition (PSCE), 2011 IEEE/PES.
[107] Miranda, R. Janeiro, and M. Aredes, A DQ Synchronous Reference Frame Current
Control for Single-Phase Converters, IEEE 36th Power Electronics Specialists
Conference, 2005.
[108] B. Crowhurst, E.F. El-Saadany, L. El Chaar and L.A. Lamont, Single-Phase Grid-Tie
Inverter Control Using DQ Transform for Active and Reactive Load Power
Compensation, 2010 IEEE International Conference on Power and Energy
(PECon2010), Kuala Lumpur, Malaysia.
[109] J. Traube, F. Lu, D. Maksimovic, J. Mossoba, M. Kromer, P. Faill, S. Katz, B. Borowy,
S. Nichols, and L. Casey, Mitigation of Solar Irradiance Intermittency in Photovoltaic
Power Systems With Integrated Electric-Vehicle Charging Functionality, IEEE Trans.
On Power Electronics, Vol. 28, No. 6, June 2013.
[110] C. Trueblood, PV Measures Up for Fleet Duty, IEEE Power & Energy Magzine, Vol.
11, 2013.
[111] Jay Johnson, Benjamin Schenkman, Abraham Ellis, Jimmy Quiroz, and Carl Lenox
Initial Operating Experience of the La Ola 1.2-MW Photovoltaic System.

129

Das könnte Ihnen auch gefallen