PART II - SECTION F : TECHNICAL DATA SHEETS

TDS 2C - BALANCE OF PLANT, ELECTRICAL WORKS


REQUIREMENTS

DESCRIPTIONS
C. MV CABLES
1
MANUFACTURER/BRAND

By Bidder

OFFER
Phelps Dodge

MANUFACTURING STANDARDS

IEC 60502 & IEC 60811

VOLTAGE

By Bidder

18/30 (36)kV

NO. OF CORES

By Bidder

single core

CONDUCTOR

5.1

MATERIAL

COPPER

5.2

DESIGN

STRANDED, SECTORAL

5.3
6

CROSS-SECTIONAL AREA, mm 2
CONDUCTOR INSULATION

IEC 60502 & IEC 60811

Copper
Circular Compacted

By Bidder

95mm
XLPE

6.1

MATERIAL

XLPE

6.2

THICKNESS, mm

By Bidder

8.0

6.3

DIAMETER OF INSULATION, mm

By Bidder

28.40

CONDUCTOR SCREEN

7.1

MATERIAL

By Bidder

Semiconductive XLPE

7.2

THICKNESS, mm

By Bidder

0.3
Semiconductive XLPE

CORE SCREEN

8.1

MATERIAL

By Bidder

8.2

THICKNESS, mm

By Bidder

0.6

8.3

DIAMETER OVER SCREEN, mm

By Bidder

30.80

By Bidder

N/A

FILLERS MATERIAL

10

BINDERS OVER LAID UP CORES

10.1

MATERIAL

By Bidder

N/A

10.2

THICKNESS, mm

By Bidder

N/A

10.3

DIAMETER OVER BINDER, mm

By Bidder

N/A
Copper Tape

11

METALLIC LAYER/SCREEN

11.1

MATERIAL

By Bidder

11.2

NO. OF WIRES AND SIZE

By Bidder

N/A

11.3

NO. OF TAPES AND SIZE

By Bidder

0.1016 mm

11.4

By Bidder

N/A

11.5

CROSS-SECTION, mm 2
BEDDING MATERIAL

By Bidder

PVC

11.4

THICKNESS, mm

By Bidder

1.2

12

VERMIN PROTECTION / ARMOUR

12.1

TYPE

TERMITE/RODENT

12.2

ARMOUR TYPE

By Bidder

Aluminum Wire Armour

By Bidder

44 wires x 2.5mm

With Anti-termite Additive

on Jacket
12.2.1
13

NO. OF WIRES AND SIZE


OUTER COVERING

13.1

MATERIAL

PVC

13.2

MINIMUM AVERAGE THICKNESS, mm

By Bidder

2.4
43.91

15

PVC

COMPLETED CABLE

15.1

OVERALL DIAMETER, mm

By Bidder

15.2

WEIGHT PER METER, kg/m

By Bidder

2.91

15.3

MAXIMUM DRUM LENGTH, m

By Bidder

2,000

15.4

DRUM OVERALL DIAMETER, mm

By Bidder

500

15.5

DRUM OVERALL WEIGHT, kg

By Bidder

1,555

16

CONTINUOUS CURRENT CARRYING CAPACITY

16.1

LAID IN GROUND, ONE CIRCUIT, amp

By Bidder

279

16.2

LAID IN GROUND, TWO CIRCUITS, amp

By Bidder

259

16.3

LAID IN GROUND, THREE CIRCUITS, amp

By Bidder

240
90

17

MAXIMUM CONDUCTOR TEMPERATURE

17.1

LAID DIRECT IN GROUND, C

By Bidder

17.2

DRAWN INTO DUCTS, C

By Bidder

90

18

CONDUCTOR SHORT CIRCUIT CURRENT, kA

By Bidder

N/A

19

SCREEN EARTH FAULT CURRENT, kA

By Bidder

9.0

20

MAXIMUM DIELECTRIC STRESS

20.1

AT CONDUCTOR SURFACE, kV/mm

By Bidder

3.34568

20.2

AT INSULATION SURFACE, kV/mm

By Bidder

1.48049

BURGOS WIND PROJECT


EDC 09-029

PART II - SECTION F : TECHNICAL DATA SHEETS


TDS 2C - BALANCE OF PLANT, ELECTRICAL WORKS
REQUIREMENTS

DESCRIPTIONS

OFFER

C. MV
21 CABLES
MAXIMUM BENDING RADIUS
21.1

LAID DIRECT IN GROUND, m

By Bidder

790 mm (18 x OD)

21.2

DRAWN INTO DUCTS, m

By Bidder

790 mm (18 x OD)

21.3

DURING INSTALLATION W/OUT DAMAGE, m

By Bidder

790 mm (18 x OD)

21.4

AT TERMINATIONS, m

By Bidder

790 mm (18 x OD)

22

MAXIMUM CONDUCTOR DC RESISTANCE, ohm/km

By Bidder

0.193

23

MAXIMUM CONDUCTOR AC RESISTANCE, ohm/km

By Bidder

0.19348

24

INSULATION RESISTANCE, per km of cable per core

24.1

AT 20C, Megaohms

By Bidder

129.75381

24.2

AT MAXIMUM RATED TEMP., Megaohms

By Bidder

1.29754

25

EQUIVALENT REACTANCE OF CONDUCTOR, ohm/km By Bidder

0.17523

26

EQUIVALENT CAPACITANCE, F/km

By Bidder

0.17035

27

MAXIMUM CHARGING CURRENT, A/km

By Bidder

1.11243

28

MAXIMUM DIELECTRIC LOSS OF CABLE, W/m

By Bidder

20

per meter of 3 phase circuit when laid direct in


ground at nominal voltage and frequency at
maximum conductor temperature
29

CORE IDENTIFICATION FOR 3 CORE

30

Manufacturer's Experience

30.1

WHITE, RED, BLUE

N/A

The manufacturer should have been in the business


of manufacturing power cables for
not less than : years

30.2

50 years

3 years

15 years

Attached
Attached

The materials to be supplied should have been in


the actual service for not less than (years):

31

15 years

Submittals

31.1

Descriptive materials, brochures, drawings, etc.

yes

31.2

Reference Lists

yes

Name of Bidder:

PHELPS DODGE PHILIPPINES ENERGY PRODUCTS CORP.

Name & Signature of Representative:

ABRAHAM V. SANCHEZ

Designation:

Vice-President (Sales)

Date:

April 29, 2011

FOR ENERGY DEVELOPMENT CORPORATION USE ONLY

1
REV.

ISSUED FOR BID


DESCRIPTION
ENERGY DEVELOPMENT CORP.

AMLR/RMBA/DDA
DATE

PREPARED

MJVL
APPROVED

ELECTRICAL - MEDIUM VOLTAGE CABLES

ENGINEERING DESIGN DEPT.

BURGOS WIND PROJECT

BURGOS WIND PROJECT


EDC 09-029

TDS 2A

TECHNICAL SPECIFICATION
FOR
Single-Core 95mm CU/XLPE/CTS/PVC/AWA/PVC 18/30 (36)kV Power Cable
Cable Profile

Compact Stranded Copper Conductor

PVC Bedding

Conductor Shield
Aluminum Wire Armour (AWA)
XLPE Insulation
Mylar Tape
Insulation Shield

Copper Tape Shield (CTS)

Specification : IEC 60502 - 2


Voltage Rating : 18/30 (36)kV

PVC Jacket

Temperature Rating : Normal condition


Emergency condition
Short-circuit condition

90C
105C
250C

TECHNICAL SPECIFICATION
FOR
Single-Core 95mm CU/XLPE/CTS/PVC/AWA/PVC 18/30 (36)kV Power Cable
CABLE CONSTRUCTION
Code

Details

Part Name

A.

Conductor

Size :
Type of Stranding :
No. of wires
Diameter :
Approx. Weight :

95mm Plain Annealed Copper (PAC)


Circular Compacted
15 wires (minimum)
11.00 mm (nominal)
859.30 Kg/Km (nominal)

B.

Semi-conductive Conductor Screen

Wall Thickness:
Material Designation:
Diameter over Screen:

0.7 mm (nominal)
Semiconductive XLPE
12.40 mm (approx)

C.

XLPE Insulation

Wall Thickness:
Material Designation:
Diameter over XLPE:

8.0 mm (nominal)
XLPE Insulation
28.40 mm (approx)

D.

Semi-conductive Insulation Screen

Wall Thickness:
Material Designation:
Diameter over Screen:

1.2 mm (minimum)
Semiconductive XLPE
30.80 mm (approx)

E.

Copper Tape Shield (CTS)

Thickness
% Overlap
Diameter over CTS:

0.1016 mm (4 mils)
10% (nominal)
31.21 mm (approx)

F.

Bedding

Wall Thickness:
Type:
Color:
Diameter over Bedding:

1.2 mm (nominal)
PVC
Black
33.61 mm (approx)

G.1

Aluminum Wire Armour (AWA)

2.5 mm x 44 Wires
Left-hand

G.2

Armour Wrap

Diameter x No. of Wires


Lay direction:
Type:
Diameter over Armour :

helically applied non-hygroscopic polypropylene tape.


39.11 mm (approx)

H.

Oversheath

Type:
Color:
Wall Thickness:

PVC
Black
2.4

I.

Finished Cable

Approx. Cable Diameter :


Approx. Weight :
Bending Radius :
Packaging :
Approx. Weight in Reel :

43.91 mm (nominal)
2,914.31 Kg/Km (nominal)
790.0 mm (minimum, 18 x Approx. Cable Diameter)
500 meters / 1800 mm Wooden Reel
1.55 MT

I.

Electrical Properties:

Rated Voltage:
Ampacity (Direct Burial):
Fault Current Rating:
D.C. Resistance @ 20C :
AC Voltage Test:

18/30 (36)kV
285 A (Based from IEC 60502 - 2)
19 kA for 1 sec.
0.199 /km (maximum)
must withstand 63kV for 5 minutes

Note: Unless specified, the above figures are nominal and subject to standard manufacturing tolerances.