Beruflich Dokumente
Kultur Dokumente
DESCRIPTIONS
C. MV CABLES
1
MANUFACTURER/BRAND
By Bidder
OFFER
Phelps Dodge
MANUFACTURING STANDARDS
VOLTAGE
By Bidder
18/30 (36)kV
NO. OF CORES
By Bidder
single core
CONDUCTOR
5.1
MATERIAL
COPPER
5.2
DESIGN
STRANDED, SECTORAL
5.3
6
CROSS-SECTIONAL AREA, mm 2
CONDUCTOR INSULATION
Copper
Circular Compacted
By Bidder
95mm
XLPE
6.1
MATERIAL
XLPE
6.2
THICKNESS, mm
By Bidder
8.0
6.3
DIAMETER OF INSULATION, mm
By Bidder
28.40
CONDUCTOR SCREEN
7.1
MATERIAL
By Bidder
Semiconductive XLPE
7.2
THICKNESS, mm
By Bidder
0.3
Semiconductive XLPE
CORE SCREEN
8.1
MATERIAL
By Bidder
8.2
THICKNESS, mm
By Bidder
0.6
8.3
By Bidder
30.80
By Bidder
N/A
FILLERS MATERIAL
10
10.1
MATERIAL
By Bidder
N/A
10.2
THICKNESS, mm
By Bidder
N/A
10.3
By Bidder
N/A
Copper Tape
11
METALLIC LAYER/SCREEN
11.1
MATERIAL
By Bidder
11.2
By Bidder
N/A
11.3
By Bidder
0.1016 mm
11.4
By Bidder
N/A
11.5
CROSS-SECTION, mm 2
BEDDING MATERIAL
By Bidder
PVC
11.4
THICKNESS, mm
By Bidder
1.2
12
12.1
TYPE
TERMITE/RODENT
12.2
ARMOUR TYPE
By Bidder
By Bidder
44 wires x 2.5mm
on Jacket
12.2.1
13
13.1
MATERIAL
PVC
13.2
By Bidder
2.4
43.91
15
PVC
COMPLETED CABLE
15.1
OVERALL DIAMETER, mm
By Bidder
15.2
By Bidder
2.91
15.3
By Bidder
2,000
15.4
By Bidder
500
15.5
By Bidder
1,555
16
16.1
By Bidder
279
16.2
By Bidder
259
16.3
By Bidder
240
90
17
17.1
By Bidder
17.2
By Bidder
90
18
By Bidder
N/A
19
By Bidder
9.0
20
20.1
By Bidder
3.34568
20.2
By Bidder
1.48049
DESCRIPTIONS
OFFER
C. MV
21 CABLES
MAXIMUM BENDING RADIUS
21.1
By Bidder
21.2
By Bidder
21.3
By Bidder
21.4
AT TERMINATIONS, m
By Bidder
22
By Bidder
0.193
23
By Bidder
0.19348
24
24.1
AT 20C, Megaohms
By Bidder
129.75381
24.2
By Bidder
1.29754
25
0.17523
26
By Bidder
0.17035
27
By Bidder
1.11243
28
By Bidder
20
30
Manufacturer's Experience
30.1
N/A
30.2
50 years
3 years
15 years
Attached
Attached
31
15 years
Submittals
31.1
yes
31.2
Reference Lists
yes
Name of Bidder:
ABRAHAM V. SANCHEZ
Designation:
Vice-President (Sales)
Date:
1
REV.
AMLR/RMBA/DDA
DATE
PREPARED
MJVL
APPROVED
TDS 2A
TECHNICAL SPECIFICATION
FOR
Single-Core 95mm CU/XLPE/CTS/PVC/AWA/PVC 18/30 (36)kV Power Cable
Cable Profile
PVC Bedding
Conductor Shield
Aluminum Wire Armour (AWA)
XLPE Insulation
Mylar Tape
Insulation Shield
PVC Jacket
90C
105C
250C
TECHNICAL SPECIFICATION
FOR
Single-Core 95mm CU/XLPE/CTS/PVC/AWA/PVC 18/30 (36)kV Power Cable
CABLE CONSTRUCTION
Code
Details
Part Name
A.
Conductor
Size :
Type of Stranding :
No. of wires
Diameter :
Approx. Weight :
B.
Wall Thickness:
Material Designation:
Diameter over Screen:
0.7 mm (nominal)
Semiconductive XLPE
12.40 mm (approx)
C.
XLPE Insulation
Wall Thickness:
Material Designation:
Diameter over XLPE:
8.0 mm (nominal)
XLPE Insulation
28.40 mm (approx)
D.
Wall Thickness:
Material Designation:
Diameter over Screen:
1.2 mm (minimum)
Semiconductive XLPE
30.80 mm (approx)
E.
Thickness
% Overlap
Diameter over CTS:
0.1016 mm (4 mils)
10% (nominal)
31.21 mm (approx)
F.
Bedding
Wall Thickness:
Type:
Color:
Diameter over Bedding:
1.2 mm (nominal)
PVC
Black
33.61 mm (approx)
G.1
2.5 mm x 44 Wires
Left-hand
G.2
Armour Wrap
H.
Oversheath
Type:
Color:
Wall Thickness:
PVC
Black
2.4
I.
Finished Cable
43.91 mm (nominal)
2,914.31 Kg/Km (nominal)
790.0 mm (minimum, 18 x Approx. Cable Diameter)
500 meters / 1800 mm Wooden Reel
1.55 MT
I.
Electrical Properties:
Rated Voltage:
Ampacity (Direct Burial):
Fault Current Rating:
D.C. Resistance @ 20C :
AC Voltage Test:
18/30 (36)kV
285 A (Based from IEC 60502 - 2)
19 kA for 1 sec.
0.199 /km (maximum)
must withstand 63kV for 5 minutes
Note: Unless specified, the above figures are nominal and subject to standard manufacturing tolerances.