Sie sind auf Seite 1von 14

IMI Hydronic Engineering

Technical report
Office 2107, Jafza View 19,
PO Box 262611, Jafza, Dubai,
U.A.E
Tel +971 (0) 4 8864500
Fax +971 (0) 4 8864500
www.imi-hydronic.com

CONTROL PHILOSOPHY
FOR CHILLED WATER
INSTALLATIONS

23rd of May 2016

DISTRICT COOLING CONNECTION (ETS ROOM):


Most of the current District Cooling Systems are variable flow, thus subject to differential pressure
variations which occur at partial load conditions. In this report we refer to DC systems with Independent
Building Connection, where each load (building) is connected with the set of Plate Heat Exchangers
(PHEX).
While manual balancing, as a typical solution shown on Fig. 1, is essential and effective in order to
achieve PHEX design flow rate, it is important to note that the same cannot be obtained at partial loads.
The static balancing valves (DRV) do not compensate for any stabilization of differential pressures
occurring at partial and varying load conditions.

2
Fig. 1. Typical PHEX arrangement
Thats why DC system is subject to overflow and underflow scenarios during most part of the year. This
leads to supply & return water temperature fluctuation and poor indoor conditions of the building resulting
on low system delta T, hence increase in energy cost apart from many other limitations.
Recommendations:
We recommend use of Pressure Independent Balancing & Control Valves (PIBCV) with adjustable Kvs
and EQM characteristic (TA-FUS1ON-P model) on the primary side of each Plate Heat Exchanger
instead of typically proposed control valve and DRV, as shown on Fig. 2. Each valve shall be equipped
with modulating actuator.
PIBCV selection shall be based on design flow rate, available differential pressure. Actuator selection
shall be based on required closing force of the PIBCV, power supply voltage, control and feedback
signals provided by BMS supplier.
Once selected and installed, the Kvs value of PIBCV should be adjusted to required value in order to
regulate design flow rate and maintain it at valves fully open position and design load conditions.
Differential Pressure Controller of PIBCV maintains a constant differential pressure across the control
part of the valve, thus provides good valves authority at any load conditions.
We recommend equipping of the hot (secondary) side of each PHEX with Balancing valve (VODRV) for
proportional balancing of the plate heat exchangers and on/off Motorized Butterfly Valve (MBTV) to
connect/disconnect each PHEX.

Fig. 2. PHEX arrangement with PIBCV


If the flow rates for each Plate Heat Exchanger are higher than 50 l/s, we recommend 2 or 3 numbers of
Pressure Independent Balancing & Control Valves to be installed in parallel for each PHEX, as shown on
Fig. 3.

Fig. 3. PHEX arrangement with set of PIBCVs


Primary side of PHEX to be controlled by set of connected in parallel 2-way Pressure Independent
Balancing & Control Valves. PIBCV valve shall be equipped with modulating actuator in order to provide
enough closing force at maximal available differential pressure.
Both PIBCVs will be controlled simultaneously to work as a pair in order to avoid distortion of the total
EQM characteristic.
The final number of valves in parallel shall be evaluated as a division of the total flow rate for PHEX by
50-55 l/s (as a maximum recommended flow rate for the PIBCV).
The use of few PIBCVs in parallel gives:

much accurate modulating control especially at the partial load conditions,


better rangeability of the set of the valves compared to only one device,
control redundancy (backup),
easy service & maintenance without system shut down.

Operation sequence:
The BMS shall take over the operations of the secondary pumps and Pressure Independent Balancing &
Control Valves in Auto mode. Temperature sensors shall be located in the supply and return water lines
of the Primary and Secondary sides of each PHEX. The temperatures shall be continuously monitored
and controlled by PLC/DDC controller.
The Pressure Independent Balancing & Control Valve should be set to maintain the differential
temperature in the primary circuit.
When demand chilled water flow in the secondary circuit is less than supply flow rate from the primary
side and the temperature difference will decrease the set limit, BMS shall send a signal to the actuators
in order to close the Pressure Independent Balancing & Control Valves in sequence until primary delta T
reaches the set value.
When the demand chilled water flow in the secondary circuit is more than supply flow rate from the
primary side and the temperature difference will increase the set limit, BMS shall send a signal to the
actuators in order to open the Pressure Independent Balancing & Control Valves in sequence until
primary delta T reaches the set value.
The set point of the secondary pumping station to be controlled by the signal from differential pressure
sensor (DPS) installed on the index circuit/branch (to be submitted with Hydronic Calculation).
Temperature difference between T3 and T4 equal to 9oC has to be considered in the control sequence of
the secondary pumping station and maintained by BMS.
Balancing valves should be equipped with test points in order to provide flow, differential pressure,
4 on site. They can be proportionally balanced during
temperature and power (cooling load) measurement
commissioning using TA Hydronics Methodology (TA Diagnostics, TA Wireless) with TA-SCOPE
balancing instrument.
TERTIARY PUMPING STATIONS:
In order to avoid interactivity between Secondary and Tertiary pumping stations, we recommend
modification of the direct connection to the auto adapting variable flow decoupling circuit (as shown on
Fig. 4).

Fig. 4. Connection details for the Tertiary pumping station


The Differential Pressure Control Valve (DPCV) keeps constant and very low flow (1% of design flow
rate for the load) through the bypass. Secondary flow rate is automatically adapted to the tertiary flow
variations. Both secondary and tertiary flow rates are variable. This circuit was designed for supply water
temperature preserving (secondary supply water temperature will remain
unchanged).
4

Auto adapting variable flow decoupling circuit is entirely self-acting. It has to be equipped with robust
Differential Pressure Control Valve for accurate control and long lifetime. We recommend pilot operated
DPCV model TA-PILOT-R.
Differential pressure stabilized through the bypass (PAB) can be deducted from needed pump head in
the tertiary side. This circuit provides optimization of the Tertiary pumping station since available
differential pressure from the Secondary pumping station is directly transferred to the Tertiary side.
Available differential pressure for connection of each Tertiary station can be calculated during the
Hydronic calculation with the help of HySelect software.
Balancing valve (VODRV) in the bypass should be sized for qB that is 1% of the design tertiary flow rate
qT.
SMALL TERMINAL UNITS:
Each Fan Coil Unit to be controlled by 2 port Pressure Independent Balancing & Control Valve (model
TBV-CMP or KTCM512) as shown on Fig. 5 with the following features:
stroke of 4 mm,
EQM characteristic,
modulating actuator in order to satisfy required indoor climate conditions at any system load
variations,
direct flow measurement based on Kv-methodology.

Fig. 5. Connection details for group of FCUs.


Design flow rates will be adjusted on every valve based on presetting given in the PIBCV selection and
actual flow rate is measured with TA-SCOPE balancing instrument in order to provide design flow rate
for each FCU at full load conditions and avoid over/under flows in the consumption/dissipation chilled
water side.
MEDIUM AND LARGE TERMINAL UNITS:
Air Handling Units (and also secondary plate heat exchangers or other medium terminal units) to be
controlled by 2 port Pressure Independent Balancing & Control Valves (model TA-FUS1ON-P) with
adjustable Kvs and EQM characteristic (as shown on Fig. 6). PIBCV will be equipped with MC55/MC100
Modulating actuator in order to provide accurate flow control and enough closing force at maximal
available differential pressure.

Fig. 6. Connection details for AHU.


Design flow rates will be adjusted on every PIBCV based on presetting given in the PIBCV selection and
actual flow rate is measured with TA-SCOPE balancing instrument in order to provide design flow rate
for each AHU at full load conditions and avoid over/under flows in the consumption/dissipation chilled
water side.
Pressure Independent Balancing & Control Valves from IMI Hydronic Engineering are combining and not
compromising functions of control valve, balancing valve and differential pressure controller in one body.
The Kvs value of PIBCV will be adjusted to required value in order to regulate design flow rate and
maintain it at valves fully open position and design load conditions. Differential Pressure Controller of
PIBCV maintains a constant differential pressure across the control part of the valve, thus provides good
valves authority at any load conditions, even in circumstances
where the inlet pressure is very unstable.
6
FUTURE CONNECTIONS:
If CHW system commissioning and balancing require flow rate and differential pressure limitation for
future connections and also verification that installed pumping stations can deliver required flow rate to
every part of the entire installation, we recommend the following arrangement for stub out connections.
Future extensions can be equipped with balancing valve (VODRV) installed on the supply line and
differential pressure control valve (DPCV) installed on the return (as indicated on Fig. 7).

Fig. 7. Connection details for future loads


VODRV has to be sized as per design flow rate for future extension and P = 3kPa with presetting close
to full opening. DPCV has to be sized as per design flow rate and Pmin = 5kPa, DPCV spring range
has to be selected with respect to expected circuit (future load) pressure drop.
Commissioning of the Shall & Core will be done in two steps:
1) VODRV has to be adjusted to presetting which, at design flow has the pressure drop equal to sum of
retail unit (load) pressure drop and pressure drop across balancing valve at fully
open position and design flow (at least 3 kPa). Isolation valve (IV) has to be fully
6

open. DPCV has to be adjusted to design flow using balancing valve as a flow measuring device.
2) When the retail tenant will be connected balancing valve (VODRV) has to be adjusted to hand wheel
setting which, at design flow provides pressure drop equal to 3kPa. Isolation valve should be closed.
Retail unit flow rate will be maintained dynamically regardless of other circuit activity or pump speed
changes.
When future loads get connected to existing buildings, installed PIBCVs and DPCVs will see the
variation in differential pressure and will dynamically move to adjust to the new situation. Hence the
balancing of the branches will not be affected and thereby do not require any re-adjustment.
PRESSURIZATION EQUIPMENT:
Each individual CHW Zone should be equipped with the pressurization unit containing expansion
vessel(s), buffer vessel, pumps, break tank and all controls, interlocks and ancillary equipment
necessary to maintain the system static pressure in accordance with the operating conditions (as shown
on Fig. 8). The pressurization unit shall be connected to the suction side of the pumping station if it is
possible, however other locations are also acceptable, but requires detailed selection for correct static
pressure maintenance.
Each unit shall be provided with sufficient number and capacity of expansion vessels. These shall handle
the full expansion volume of the system from normal cold fill or ambient conditions to normal working
temperature and minimal water reserve. We recommend the use of expansion and buffer vessels with
butyl rubber bladder.
7

Fig. 8. Pressurization unit and Vacuum Degasser


The actual system water contents and the capacity of the expansion vessels, buffer vessel and break
tank shall be calculated by the contractor to achieve and accept the total system contraction/expansion
volume of water.
Instead of indicated on the drawings air separators, we recommend the use of pressure-step Vacuum
degasser as a standalone device or integrated part of the pressurization unit in order to remove air from
a closed water system.
The vacuum degasser shall be selected based on the system volume. Where a single degassing unit
cannot deal with the system volume separate multiple degassers shall be installed in parallel. The feed
line to the deaerator shall be provided with dirt separator.

The pressure step degasser works on the basis of exposing part of the system water to a vacuum which
forces all dissolved gases from the water. These gases then will be expelled via an automatic air vent.
Once the water sample has been deaerated it will be fed back in to the main system. This cycle will be
repeated every 30 seconds to gradually remove all air from the system.
IMI Hydronic Engineering has a wide range of pump based pressurization units with combined function
of water make-up and vacuum degassing called Transfero TV Connect and Transfero TI (fig. 9.)

Fig. 9. Pump based pressurization units Transfero TV Connect and Transfero TI


Transfero is a precision pressure maintenance device
recommended in high rise installations where high
8
performance, compact design and precision within 0.2 bar are required. In the medium performance
range they can also be used as combination devices with integrated degassing and water make-up.
The pressure is measured on the water side with the pressure transducer PIS and compared to the
calculated target value of the BrainCube control. If the pressure falls below this target value, the pump
(P1) switches on, and if the pressure exceeds the target value, the spill valve (V1) opens. In systems
with 2 pumps and 2 spill valves, switching occurs alternately depending on the load, but with the same
level of precision.
The water level is measured by the measuring foot LIS, analyzed in the BrainCube and displayed
graphically. If it is signaled that the water level has dropped below the minimum, then the pumps are
locked.
If the temperature in the system increases, then the pressure also rises. The spill valve opens when the
target value is exceeded, and system water flows into the airproof butyl bag of the primary vessel. The
air between vessel wall and the bag is displaced to the atmosphere through an open vent.
If the temperature in the system falls, the pressure also decreases. When the pressure drops below the
target value, the pump switches on and pumps the expanded water back into the system.
So that the smallest volume changes do not immediately run the pump or spill valve, a small pressure
buffer vessel is integrated into the Transfero range.
Transfero consists of a TecBox, a primary vessel and optional secondary vessel(s), supplemented by a
pressure buffer vessel from the Statico range.
The TecBox includes hydraulics and the BrainCube which controls and monitors all processes of
precision pressure maintenance, fillsafe water make-up and oxystop degassing.
The hydraulics of the Transfero are housed in a steel case and installed on the basement plate. All the
hydraulic connections to the primary vessel needed for assembly are included in
the delivery scope.

The necessary vessel volume can be shared between a primary vessel and optional additional
secondary vessel(s). The primary vessel is equipped with a measuring foot for content measurement.
The content is indicated on the graphical display of the BrainCube. The primary vessel is connected to
the TecBox on the water side.
Air sides of both primary and secondary vessels are open to atmosphere. Water is accommodated in
airproof butyl bag with extraordinary diffusion tightness that has been proven in countless practical
applications and laboratory tests. The vessel can be filled up to 90% of its total volume. If it is signaled
that the water content has reached the maximum, then the spill valves are locked. Both primary and
secondary vessels are available from 200 up to 5000 l and have maximal operating pressure equal to 2
bar. They are used as open water storage vessels in principle and hydraulically protected against
exceeding of pressure higher the maximal limit. In addition to BrainCube protection there is pressure
safety valve which protects the vessels in case of failure or leakage of spill valve(s). That is why
Transfero stations can be used in HVAC applications with different operating pressures up to 25 bar.
Benefits:

Precision pressure maintenance with tight pressure tolerances 0.2 bar.

Compact design. Almost the entire vessel volume is available for water acceptance.

Speed control permits elastic starting and stopping of pumps, smooth pump operation and
system protection against abrupt pressure variations.

The pump switching frequency is minimized due to buffer vessel.

9
Smaller Vessel size compared to conventional
solution.

Simple integration of water make-up and degassing.

Almost unlimited performance.

The BrainCube guarantees fully automatic self-optimizing operation and control of system
parameters, shows on graphical display all relevant parameters as well as the digital and
analogue display of pressure and water content, sends feedback to BMS via RS 485 interface
or 2 volt-free outputs in case of any alarm, stores alarm messages.

ENGINEERING SUPPORT CENTER:


Engineering Support Centre (ESC) is a part of IMI Hydronic Engineering. ESC is a centralized technical
team to support with complex, intensive and precise HVAC engineering to enhance IMI HE value to our
customer and stakeholders. IMI Hydronic Engineering, as leading global provider and expert in hydronic
distribution systems and room temperature control, has experience in more than 100,000 projects
worldwide, delivering significant energy savings, extending the longevity of the system and ultimately
increasing the building value to our customers.
ESC covers everything within:
Product selection;
Detailed Hydronic calculation;
HVAC design & redesign;
System re-engineering;
Reducing installation, maintenance and life cycle costs;
Optimization of the energy consumption in the HVAC installation.

The expertise of the Engineering Support Center was used in many projects where IMI Hydronic
Engineering provided efficient solutions and our products were successfully installed and commissioned.
In 2014 2015 we have extended our support through ESC to the following projects in the Middle East
Region:
City Walk Phase 1, Dubai, UAE
City Walk - The Avenue Phase 2, Dubai, UAE
Nikki Beach Resort, Dubai, UAE
Four Season Hotel, Abu Dhabi, UAE
Musheirab, Doha, Qatar
Al Bandary, Doha, Qatar
IMG Theme Park, Dubai, UAE
Sulaiman Al Habib Hospital, Dubai, UAE
Sheikh Khalifa Medical City, Abu Dhabi, UAE
Kingdom Tower, Jeddah, KSA
Government Agencies Compound, Riyadh, KSA
Dubai Mall Fashion Avenue, Dubai, UAE
Manazir Al Khor, Dubai, UAE
King Fahd Medical City, Riyadh, KSA
King Abdul Aziz International Airport, Jeddah, KSA
Al Suwaidi Hospital, Riyadh, KSA
World Trade Center Residences, Dubai, UAE
Madinat Jumeirah Phase 4, Dubai, UAE
Lusail Marina, Doha, Qatar
Sky Views, Dubai, UAE
10

10

PROPOSED PRODUCTS:
TA-MODULATOR (shown in Fig. 10) is Pressure Independent Balancing and Control Valve for Fan Coil
Units combining the key hydronic functions of control and balancing in one valve with differential
pressure controller. EQM characteristic of TA-MODULATOR allows compensation of non-linear coil
characteristic and provides stable and accurate temperature control. The Measuring points enable
accurate measurement of flow, differential pressure, temperature, cooling power and available
differential pressure.

11

Fig. 10 TA-MODULATOR with TA-SLIDER actuator


KTCM 512 (shown on Fig. 11) is a high differential pressure model of Pressure Independent Balancing
and Control valve for Fan Coil Units combining the key hydronic functions of control and balancing in one
valve with differential pressure controller. KTCM 512 valve has EQM characteristic, measuring points for
flow measurement based on Kv-methodology. Maximal differential pressure for the KTCM 512 is 800
kPa (8 bar).

Fig. 11. KTCM 512

11

TA-FUS1ON-P (shown in Fig. 12) is innovative Pressure Independent Balancing and Control Valve for
chilled water applications combining the key hydronic functions of control, balancing and differential
pressure control in one valve. Adjustable Kvs and inherent independent EQM characteristics allow
correct valve sizing and optimum system controllability. The Measuring points enable accurate
measurement of flow, differential pressure, temperature, cooling power and available differential
pressure. This will simplify system commissioning and also offer key diagnostic feature for trouble
shooting. TA-FUS1ON-P valve is equipped with pressure balanced cone that gives possibility to use
actuators with smaller closing force. Maximal differential pressure for the TA-FUSION-P is 800 kPa
(8 bar).

12
Fig. 12. TA-FUS1ON-P with MC55 and MC100 actuators
KTCM 512 and TA-FUSION-P valves have special inline design, robust construction and durable
materials (AMETAL, Ductile Iron and Stainless Steel) in order to assure:

High system performance.

Stable and precise control at any load conditions and differential pressure variations.

Accurate flow measurement, easy system commissioning and troubleshooting.

Compact installation.

Low noise generation.


Differential pressure control valves from IMI Hydronic Engineering are compact controllers with
adjustable set-point for cooling applications. Those DPCVs are particularly effective in situations
requiring high differential pressure up to 8 bar and even 16 bar with low noise generation.
Differential pressure controllers are required to protect control valves and system branches from large
differential pressure variations experienced at varying load on the system. This will give better authority
and controllability of control valves which provide a stable and accurate room temperature control
throughout the system, whatever the control mode and Dp sensor location were selected. DPCVs help to
reduce the risk of noise and cavitation in control valves and other equipment, decrease required
actuation close-off force for the control valves that depends on: differential pressure applied on the plug;
tension of the return spring if available; frictions in O-rings, seals, etc.

12

Fig. 13. TA-PILOT-R and DA 516


Balancing valves from IMI Hydronic Engineering deliver accurate hydronic performance in cooling &
heating applications. All balancing valves are equipped with measuring points that provides accurate
measurement of flow, differential pressure, temperature, cooling power and available differential
pressure and simplifies the balancing procedure with TA-SCOPE balancing instrument and IMI Hydronic
Engineering Methodology (TA Diagnostics, TA Wireless), increases its accuracy and enables
troubleshooting and delivers desired differential pressure ensuring accurate balancing.
13

Fig. 14. STAD & STAF

TA-SCOPE is a tough, effective, accurate and easy-to-use balancing instrument for measuring and
logging of differential pressure, flow, temperature and power in hydronic systems. TA-SCOPE delivers
quicker, more cost-efficient balancing with new TA-Diagnostics and TA-Wireless methods and enables
rapid troubleshooting. TA-SCOPE links effortlessly to the HySelect PC software gaining the maximum
benefit from recorded data and enabling professional report writing and automatic software upgrades.

13

Fig. 15. TA-SCOPE

14 IMI Hydronic Engineering as a reputable and high


We trust this information is of use when evaluating
quality supply partner.
Should further information or clarifications be required, please do not hesitate to contact the
undersigned.
Your Faithfully,
Roman Yerema
Regional Technical Manager - Middle East

14

Das könnte Ihnen auch gefallen