Sie sind auf Seite 1von 1

pp

VE FV 1 1O2 M

PROCESS INDUSTRY PRACTICES


FABRICATION/INSTALLATION DETAILS

DRAWING DATE:

05/01/06

f--------------------------,

VESSEL; TOLERANCES
(ELEVATION)

PAGE 1 OF 2

PRACTICE REF. VEFV1100

1. HEIGHT FROM BASE LINE TO FACE OF TOP NOZZLE


6mm OR 4mm PER 3DDDmm OF HEIGHT 19mm MAX.
2. NOZZLES FOR AGITATOR MOUNTING SHALL HAVE
FLANGE FACE ALIGNED WITHIN 1/4 DEG. OF SPECIFIED
PLANE PLUS REQUIREMENTS OF NOTE 28.
3. DISTANCE FROM BOTTOM TO TOP OF TRAY SUPPORTS 3mm
4. WEIR HEIGHT 1.6mm MEASURED AT HIGH POINT OF V>!EIR
5. VERTICAL CLEARANCE UNDER DOWNFLOW PLATE FOR

----c;f-t-9?

INSTALLED TRAYS

1.6mm

6. FACE OF NOZZLE TO CENTERLINE OF VESSEL 3mm


7. ALIGNMENT OF FLANGE FACE OF NOZZLE SHALL BE
WITHIN 1/2 DEG. OF SPECIFIED PLANE.
B. LOCATION OF SHELL NOZZLES FROM BASE LINE SHALL

15

BE

6mm FOR SHOP F AB RI CA TED VESSELS OR SUB-

ASSEMBLIES AND 12mm FOR FIELD ASSEMBLED


VESSELS. WHEN LOCATION IS SPECIFIED FROM OTHER
REFERENCE POINTS, TOLERANCE SHALL BE

ii
19

6>----+~
,------,--{ 20

3mm.

9. ALIGNMENT OF FLANGE FACE OF MANWAY SHALL BE


WITHIN 1 DEG. OF SPECIFIED PLANE .
10. FACE OF MAN WAY TO CENTERLINE OF VESSEL 12mm
11. LOCATION OF MAN WAYS FROM BASE LINE SHALL BE
12mm FOR SHOP FABRICATIED VESSELS AND SUBASSEMBLIES AND 25mm FOR FIELD ASSEMBLED VESSELS.
12. BOTIOM OF VESSEL SUPPORT TO BASE LINE +0mm,-1mm
PER 400mm OF VESSEL DIAMETER, 12mm MAX.
13. FOR SUPPORTS LOCATIED ABOVE BASELINE, TOLERANCES
SHALL BE +0mm,-1mm PER 400mm OF VESSEL DIA.,
12mm MAX.
14. ALIGNMENT OF CYLINDRICAL SHELL SECTIONS SHALL BE
TRUE AND STRAIGHT V>!THIN 1mm PER 1200mm OF HEIGHT
FROM BASE LINE BUT SHALL NOT EXCEED 19mm.

r---l--.....!21

15. HIGH-POINT TO LOW-POINT OF INSTALLED TRAY LEVEL


AND PLANE V>!THIN THE FOLLOV>!NG:

VESSEL ID
~

CLASS A

1500mm

3mm

1500mm TO ~3000mm
> 3000mm

~--

CLASS B

5mm
6mm

5mm
6mm

10mm

16. FAR SIDE OF TOV>!ER TO WEIR PLATE 3mm


17. WEIRS SHALL BE LEVEL WITHIN 1.6mm FROM A LEVEL
PLANE AT THE MIDPOINT OF THE WEIR.
18. TRAY SPACING 3mm.
19. LOCATION OF TRAY PLATES FROM BASE LINE 3mm.
20. DEVIATION FROM AVERAGE I.D. (AS DETERMINED BY
STRAPPING) FROM NOMINAL I.D.: 6mm ASME CODE
SECTION \1111 TO APPLY TO OUT-OF-ROUNDNESS EXCEPT
WHEN NOTED OTHERV>!SE.
21. PIPE OR WALKWAY SUPPORTS AND STRUCTURAL

11

ATTACHMENTS TO: VESSEL CENTERLINE


BASE LINE 6mm.

3mm;

22. LOCATION OF HORIZONTAL VESSEL SUPPORT FROM


VESSEL CENTIERLINES +Omm , -3mm.
23. LOCATION OF HORIZONTAL VESSEL SUPPORTS FROM
BASE LINE

6mm; SUPPORTS LOCATED FROM

OTHER REFERENCE POINTS 3mm.


24. LOCATION OF BOTTOM NOZZLE FLANGE FACE FROM
BASE LINE SHALL BE

12

6mm.

25. LIGHT CENTER PUNCH MARK (WITH A ROUND NOSE


STAMP) THE PRINCIPAL CENTIER LINES SHOWN ON
ORIENTATION PLAN. CIRCLE PUNCH MARKS WITH
PAINT TO DESIGNATE LOCATION.
26. SUPPORTS OUT OF LEVEL OVER ANY DIAMETIER THE
GREATER OF 3mm OR 1mm
VESSEL DIAMETER, 10mm MAX.

PER 600mm OF

27. BOLT HOLES WITHIN 3mm OF SPECIFIED LOCATION


28. IF BOTTOM FLANGE IS USED AS FOOT BEARING MOUNT
AND WITH AGITATOR MOUNTING FLANGE HORIZONTAL,
BY THE TYPE OF TRAY SPECIFIED. THIS INFORMATION
CENTER OF TOP FLANGE SHALL FALL V>!THIN 1mm PER
V>!LL BE PER THE TRAY SPECIFICATION SHEET/HYDRAULICS.
500mm (OF DISTANCE BETWEEN FLANGE FACES) OF CENTER
OF BOTTOM FLANGE AND BOTTOM FLANGE SHALL BE NOT
NOT MORE THAN 1/4 DEG. OFF HORIZONTAL.
29. HORIZONTAL CLEARANCE BETWEEN DOV>!NFLOW PLATE
THESE TOLERANCES APPLY TO VERTICAL & HORIZONTAL
AND TOP OF INLET WEIR 1.6mm
VESSELS EXCEPT AS OTHERWISE NOTED ON VESSEL
30. FOR POST SUPPORTED TRAYS, CLEARANCE BETV>!EEN
DRAWING/DATA SHEET RELATING TO SPECIFIC VESSELS.
TRAY COLLAR AND SHELL 0.4mm MAX. OVER 90% OF
CLASS A AND CLASS B TOLERANCES WILL BE GOVERNED

CIRCUMFERENCE, 1.6mm MAX. OVER REMAINING 10%.

FV1102M-1.0WG