Beruflich Dokumente
Kultur Dokumente
1, JANUARY 2013
467
I. INTRODUCTION
IFFERENTIAL relay can theoretically provide the desired level of security and dependability for transformer
protection. However, in practice, its operation can be adversely
affected by the inrush current [1], [2]. A variety of methods has
been proposed to overcome this problem [3][5] which are not
necessarily readily implementable nor can guarantee proper operation under all scenarios. It is also possible that a differential
relay improperly blocks when a low phase-to-ground fault current is accompanied by the inrush current [1]. Moreover, the differential relay cannot fully cover the total length of winding for
phase-to-ground faults, especially in a case where the winding
is not directly grounded.
The restricted earth fault (REF) relay is utilized as a complementary protection unit to partially resolve the aforementioned
problems. The transformer REF relay is a differential type protection which operates for phase-to-ground faults of a grounded
winding. This relay also can be employed for the delta winding
protection, if a grounding transformer is installed between the
current transformers (CTs) and the delta winding [6].
Manuscript received May 23, 2012; accepted July 06, 2012. Date of publication December 12, 2012; date of current version December 19, 2012. This work
was supported by the University of Tehran under Grant 8101064-1-04. Paper
no. TPWRD-00521-2012.
M. Davarpanah and M. Sanaye-Pasand are with the Electrical and Computer
Engineering School, College of Engineering, University of Tehran, Tehran
14395-515, Iran (e-mail: m.davarpanah@ut.ac.ir; msanaye@ut.ac.ir).
R. Iravani is with the Department of Electrical and Computer Engineering,
University of Toronto, Toronto, ON M5S 3G4 Canada (e-mail: iravani@ecf.
utoronto.ca).
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org.
Digital Object Identifier 10.1109/TPWRD.2012.2208204
468
Fig. 1 shows a digital REF relay recorded inrush current corresponding to a 230/63 kV, 180 MVA transformer which reaches
to 4.4 p.u. and exhibits distortion at the end of the third cycle
subsequent to energization. The peak current values of the other
two phases are 2.5 and 3 p.u., based on the CT rated current of
5 A. Fig. 2 highlights the difference between the actual zero-sequence current measured by the neutral CT
and the calculated value
by adding up the three-phase currents [7].
To analyze the adaptive restraint current method, its performance is compared with the conventional REF relay algorithm
which utilizes the summation of
and
as the restraint current [7]. The relay characteristic slope and the pickup current are
25% and 0.2 p.u., respectively. Fig. 3 shows that the current trajectory enters the operational region, and the conventional REF
relay incorrectly issues a trip command. Fig. 4 illustrates the
current trajectory when the adaptive restraint current results in
shifting of the calculated currents toward the stable region of the
relay characteristic. However, the shift is not adequate and the
relay misoperates. The test concludes the severe CT saturation,
caused by the inrush current, and can lead to REF relay maloperation despite the adaptive restraint current scheme. Therefore,
there is a need to improve the performance of the relay.
If the CT secondary side, between the CT and the relay, experiences an open circuit or a short circuit, the REF relay measures a false current which leads to an artificial differential current. Such a condition is known as the CT failure. The relay
blocking, upon detection of a CT failure, is widely reported
[13]. Thus, the REF relay should be equipped with a reliable
CT failure detection algorithm to block the relay and issue an
alarm. This requirement is experimentally investigated in the
REF relay during a CT failure as explained in the following.
Fig. 5 shows measured current waveforms of a 230/63 kV,
160 MVA transformer. The sequence of events that lead to zero
current in each half-cycle in phase-A are due to the following:
A loose connection is present in the CT secondary circuit
which behaves as an open circuit and interrupts the CT
output current.
The CT open circuit results in an impulse overvoltage and
leads to a short circuit at a weak insulation part of the CT
secondary circuit [14] and causes an arcing fault.
Current division between the arc fault resistance and the
remaining part of the CT circuit supplying the relay causes
the CT output current to pass mainly through the short circuit, and the input relay current becomes almost zero.
The arc fault energy decreases significantly around the next
current zero-crossing point. Therefore, low fault current
passing through the insulation of a plastic-type cable is
interrupted near the current zero-crossing instant due to
reseal of the cable insulation [15], [16]. In this case, the
relay measures the actual CT secondary current.
The field observations indicate that after replacement of the
CT secondary cable, the relays connected to the CT do not experience the aforementioned problem. This scenario highlights the
fact that the REF relay must remain stable and not issue a false
trip command when the CT current, due to the CT secondary
issues, becomes (almost) zero.
As illustrated in Fig. 6, the false trip command, due to the
first current interruption, was issued by the REF unit of the
transformer low-voltage (LV) side, third row of Fig. 6. The
recorded signals are analyzed by the modeled relay which
uses the adaptive restraint current. Fig. 7 shows that the calculated zero-sequence current passing through the neutral
CT is insignificant, except during the two half-cycle current
469
Subsequent to a lightning strike on a transmission line, protective relays can be subject to interferences via coupling paths,
for example, radiated electromagnetic waves, instrument transformers, and cable shields [17], [18]. Consequently, the performance of fast and sensitive protective relays can be impacted.
Figs. 9 and 10 show the recorded peak line current and its corresponding calculated trajectory by the REF relay model, subsequent to a lightning strike, respectively. Fig. 9 shows the current
reaches 28 p.u., and the trajectory enters the relay operation zone
as shown in Fig. 10. The field records also show that the REF
relay of the transformer LV side incorrectly issues a trip command due to the high current. The measured waveform of Fig. 9
corresponds to a 230/63-kV substation which is connected to
two 230-kV lines through two 90-MVA transformers and multiples unshielded 63-kV lines.
The reported event clearly shows that the adaptive restraint
current technique cannot prevent the REF relay maloperation
when subjected to severe disturbances and, thus, requires performance enhancement.
III. REF RELAY RESPONSE SUBSEQUENT
SIMULATED DISTURBANCES
TO
470
Fig. 12. Calculated zero-sequence current compared with the measured neutral
current.
Fig. 14. Calculated zero-sequence current compared with the neutral current.
Fig. 15. Calculated current trajectory for a three-phase fault based on the modeled REF.
471
where
is the calculated raw adaptive restraint current,
is the actual restraint current used in the REF unit, represents
a new sample,
represents the previous sample, and is a
constant
.
This approach provides a decaying memory to the restraint
signal of (1). Thus, when the raw restraint current
significantly drops, especially after CT saturation, the actual restraint
current
is not instantly reduced. It should be noted that
the CT deeply saturates at 7.5 ms after the CB recloses.
The studied relay also incorrectly operates for some phasephase or three-phase faults at the transformer LV side when
the CT remanent flux is considered. This occurs despite utilization of the modified adaptive restraint current calculated by (1).
Thus, the REF unit should be improved to remain stable during
CT saturation.
IV. REF RELAY PERFORMANCE IMPROVEMENT
To improve the REF relay performance subject to system
transients, an approach based on improved configuration relay
is proposed and evaluated.
The REF relay should operate only for earth faults on the protected winding during the interval that current flow through the
neutral CT is inevitable. However, the previous reported studied
cases indicate the REF relay can incorrectly operate when there
is no significant neutral current.
An earth-fault (EF) relay operates when the measured zerosequence current is more than the preset pickup value. The zerosequence current can be measured based on the sum of the threephase currents
. However, the saturated CT current due to
a short circuit can generate an artificial zero-sequence current.
Therefore, to determine the actual zero-sequence current value,
the current through the transformer neutral should be examined.
An EF relay cannot discriminate between the transformer and
the system phase-to-ground faults. Therefore, a large delay is
often imposed to avoid the relay maloperation due to external
faults.
It must be noted that drawbacks associated with the REF and
EF relays can be compensated by the scheme of Fig. 18 where
the trip command of the REF unit is not issued, if the instantaneous EF unit does not operate. Thus, the protection scheme
reliability is highly dependent on proper EF unit operation as
follows.
472
Fig. 20. Current ratio for the earth fault at the solidly grounded star winding.
Fig. 19. Calculated current trajectory for a phase-to-ground fault at 20% of the
HV winding by the differential unit.
473
APPENDIX
TRANSFORMER AND CT PARAMETERS
TABLE II
CT1- AND CT2- RATED VALUES
TABLE I
MAXIMUM NEUTRAL CURRENT RMS VALUE DURING INRUSH CURRENT
TABLE III
CT3- AND CT4-RATED VALUES
which is less than the prespecified pickup current (16%). Moreover, based on the simulation studies, the REF unit incorrectly
operates in four cases for which the maximum rms values of the
corresponding inrush currents are 11%, 9.8%, 9.2%, and 9.5%
(Table I). Since there is a large margin between the pickup current of the EF unit and the aforementioned inrush current rms
values, the modified REF protection scheme is also stable during
power transformer energization.
Time-domain simulation studies show that the EF unit often
operates before the REF unit and there is a delay of less than
1 ms only in a few cases. Therefore, the combined protection
scheme imposes almost no additional delay compared with the
REF unit. Consequently, the combined scheme does not jeopardize the REF relay dependability.
TABLE IV
POWER TRANSFORMER-RATED VALUES
V. CONCLUSION
The transformer REF relay is inherently a sensitive relay due
to its low-setting value and fast response. Therefore, it is intrinsically prone to maloperation when subjected to the inrush
current due to transformer core saturation and severe power
system disturbances, for example, lightning strikes. This paper
provides a comprehensive performance evaluation of an REF
relay, which is augmented with an adaptive restraint current
method for stabilization. The results reveal the REF relay maloperation when subjected to: 1) three-phase faults in conjunction with CT saturation; 2) phase-to-phase faults in conjunction
with deep CT saturation; 3) CT saturation during low-amplitude
current with a prolonged dc component, for example, inrush
current; and 4) system disturbances with low restraint current,
for example, CT failure and impulse currents entering the relay
analog input. Since digital relays are configurable by combining
specific functionalities of independent internal units, this capability is exploited to improve the relay performance by combining an earth fault (EF) unit with the REF unit. The proposed
settings of EF pickup current at the HV side star winding and LV
side delta winding are 0.8 and 0.5 times the corresponding REF
pickup current, respectively. The investigation results, based
on experiments and simulation test cases, indicate the modified
relay scheme is stable during all studied disturbances.
Fig. 23. Measured major hysteresis loop of the magnetic core material.
REFERENCES
[1] M. M. A. Ibrahim, Disturbance Analysis for Power Systems, 1st ed.
Hoboken, NJ: Wiley, 2012.
474