SITE TEST REPORT

GT-1

SEC-COA CONTRACT NO:


SULTANAH

Date: 12/08/2015

BUSHING CURRENT
TRANSFORMER

Sheet 1 of 5

1) General Data

Transformer No
Transformer Serial No

: GT-1
: 143068

2) Name plate details


BCT NO.

LOCATION

RATIO

BCT1

R, Y, B

300/1A

BCT2

R, Y, B

BCT3

R, Y, B

BCT4

300/1A
1200800/1A
2510/5A

BCT5

BCT6

CLASS

BURDEN

X
10P10

TECHNICAL DATA
Vkp
Im
>360V

<50mA

Rct

FUNCTION

<1ohm

spare

30VA

spare
>1400V

<25mA

<2ohm

spare

0.5FS10

50VA

AVC

3000/2A

3FS10

15VA

LV-WTI

300/1A

>360V

<50mA

<1ohm

HV REF box-2

BCT7

300/1A

>360V

<50mA

<1ohm

BCT8

800/1A

10P10

15VA

BCT9

800/1A

10P10

15VA

BCT10

380/2A

3FS10

15VA

HV REF box-1
LV stand by
E/F box-2
LV stand by
E/F box-1
HV-WTI

BCT11

r, y, b

3000/1A

0.2FS10

15VA

SPARE (AMR)

BCT12

3000/1A

BCT13

3r, 3y, 3b

850/1A

10P10

BCT14

3000/1A

>765V

<25mA

<10ohm

30VA

LV REF box-2
PROTECTION

>765V

<25mA

<10ohm

LV REF box-1

3) Serial No:
LOCATION

R-phase

Y-phase

B-phase

NEUTRAL

HV

000049

000043

000050

000046

LV

000058

000055

000059

000073

TV

000067

000068

000069

N/A

4) Insulation Resistance Test:

TESTED BY SSEM

Name:
Signature:

HV

Temp: 39C

Witnessed by SEC-CSD
Name:
Signature:

SITE TEST REPORT

GT-1

SEC-COA CONTRACT NO:


SULTANAH

Date: 12/08/2015

BUSHING CURRENT
TRANSFORMER

Sheet 2 of 5

Measured Values at 1 Min.

Ref

Megger
Voltage

Primary to Earth

5000V

46.9 G

51.1 G

44.8 G

Primary to Sec 1

2500V

29.1 G

39.1 G

27.8 G

Primary to Sec 2

2500V

38.0 G

36.0 G

31.8 G

Primary to Sec 3

2500V

22.5 G

31.7 G

31.9 G

Primary to Sec 4

2500V

N/A G

27.4 G

N/A

Sec 1 to Earth

1000V

10.6 G

18.9 G

9.21 G

Sec 2 to Earth

1000V

11.1 G

17.7 G

7.55 G

Sec 3 to Earth

1000V

7.26 G

11.7 G

7.79 G

Sec 4 to Earth

1000V

N/A

9.09 G

N/A

Sec 1 to Sec 2

1000V

18.1 G

34.4 G

19.3 G

Sec 1 to Sec 3

1000V

14.0 G

27.1 G

17.1 G

Sec 1 to Sec 4

1000V

N/A

30.1 G

N/A

Sec 2 to Sec 3

1000V

14.9 G

27.2 G

16.6 G

Sec 2 to Sec 4

1000V

N/A

25.3 G

N/A

Sec 3 to Sec 4

1000V

N/A

21.6 G

N/A

5) Insulation Resistance Test:

TESTED BY SSEM

Name:
Signature:

HV N

Witnessed by SEC-CSD
Name:
Signature:

SITE TEST REPORT

GT-1

SEC-COA CONTRACT NO:


SULTANAH

Date: 12/08/2015

BUSHING CURRENT
TRANSFORMER

Sheet 3 of 5

Megger
Voltage

Ref

Measured Values at
1 Min.
N

Primary to Earth

5000V

50.4 G

Primary to Sec 1

2500V

34.7 G

Primary to Sec 2

2500V

35.2 G

Sec 1 to Earth

1000V

18.8 G

Sec 2 to Earth

1000V

17.9 G

Sec 1 to Sec 2

1000V

34.5 G

6) Insulation Resistance Test:

LV
Measured Values at 1 Min.

Ref

Megger
Voltage

Primary to Earth

5000V

37.9 G

38.0 G

40.6 G

Primary to Sec 1

2500V

72.1 G

65.3 G

84.7 G

Primary to Sec 2

2500V

N/A

65.5 G

N/A

Primary to Sec 3

2500V

N/A

59.5 G

N/A

Sec 1 to Earth

1000V

115 G

138 G

128 G

Sec 2 to Earth

1000V

N/A

128 G

N/A

Sec 3 to Earth

1000V

N/A

108 G

N/A

Sec 1 to Sec 2

1000V

N/A

256 G

N/A

Sec 1 to Sec 3

1000V

N/A

218 G

N/A

Sec 2 to Sec 3

1000V

N/A

204 G

N/A

7) Insulation Resistance Test:

TESTED BY SSEM

Name:
Signature:

LV n

Witnessed by SEC-CSD
Name:
Signature:

SITE TEST REPORT

GT-1

SEC-COA CONTRACT NO:

BUSHING CURRENT
TRANSFORMER

Sheet 4 of 5

Measured Values at
1 Min.
n

Primary to Earth

5000V

35.5 G

Primary to Sec 1

2500V

10.2 G

Primary to Sec 2

2500V

10.4 G

Primary to Sec 3

2500V

16.6 G

Primary to Sec 4

2500V

20.0 G

Sec 1 to Earth

1000V

365 G

Sec 2 to Earth

1000V

393 G

Sec 3 to Earth

1000V

366 G

Sec 4 to Earth

1000V

407 G

Sec 1 to Sec 2

1000V

20.0 G

Sec 1 to Sec 3

1000V

21.6 G

Sec 1 to Sec 4

1000V

21.2 G

Sec 2 to Sec 3

1000V

19.6 G

Sec 2 to Sec 4

1000V

30.1 G

Sec 3 to Sec 4

1000V

21.4 G

8) Insulation Resistance Test:

Name:
Signature:

Date: 12/08/2015

Megger
Voltage

Ref

TESTED BY SSEM

SULTANAH

TV

Witnessed by SEC-CSD
Name:
Signature:

SITE TEST REPORT

GT-1

SEC-COA CONTRACT NO:


SULTANAH

Date: 12/08/2015

BUSHING CURRENT
TRANSFORMER

Sheet 5 of 5

Measured Values at 1 Min.

Ref

Megger
Voltage

3r

3y

3b

Primary to Earth

5000V

32.4 G

38.6 G

41.7 G

Primary to Sec

2500V

73.1 G

55.0 G

38.3 G

Sec to Earth

1000V

53.8 G

55.6 G

52.8 G

9) Equipments Used
Name

Make

Serial number

Calibration due date

INSULATION
TESTER

FLUKE

2140012

04/02/2015

10) Note

CT Analyzer Report Attached Below.

11) Remarks

OK

TESTED BY SSEM

Name:
Signature:

Witnessed by SEC-CSD
Name:
Signature: